Plan Review Details - Permit 18030550
Plan Review Stops For Permit 18030550
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2018-04-11 Cont ID  
Sent By rmcdouga Date 2018-04-11 Time 07:48 Rev Time 0.00
Received By rmcdouga Date 2018-04-11 Time 06:52 Sent To I
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2018-03-26 Cont ID  
Sent By rmcdouga Date 2018-03-26 Time 09:22 Rev Time 0.00
Received By rmcdouga Date 2018-03-26 Time 09:22 Sent To  
Notes
2018-03-26 09:21:29PLAN
 REVIEW COMMENTS
  
 2ND REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE TRUSS DRAWINGS THAT WERE SUBMITTED DO NOT HAVE
 THE ENGINEER'S ORIGINAL SIGNATURE.
 61G15-23.003 PROCEDURES FOR PHYSICALLY SIGNING AND
 SEALING PLANS, SPECIFICATIONS, REPORTS OR OTHER
 DOCUMENTS.
 ENGINEERING PLANS, SPECIFICATIONS, REPORTS OR OTHER
 DOCUMENTS WHICH MUST BE SIGNED, DATED AND SEALED IN
 ACCORDANCE WITH THE PROVISIONS OF SECTION 471.025,
 F.S., AND RULE 61G15-23.001, F.A.C. MAY BE PHYSICALLY
 SIGNED, DATED AND SEALED AS PROVIDED HEREIN BY THE
 PROFESSIONAL ENGINEER IN RESPONSIBLE CHARGE.
 (1) THE LICENSEE SHALL SIGN BY HAND AN ORIGINAL OF THE
 LICENSEE'S SIGNATURE ON EACH PAGE REQUIRED TO BE
 SEALED. A SCANNED, FACSIMILE, DIGITALLY CREATED OR
 COPIED IMAGE OF THE LICENSEE'S SIGNATURE SHALL NOT BE
 USED.
 (2) THE LICENSEE MUST THEN USE A WET SEAL, A DIGITALLY
 CREATED SEAL, OR AN EMBOSSING SEAL PLACED PARTIALLY
 OVERLAPPING THE LICENSEE'S SIGNATURE ON EACH PAGE
 REQUIRED TO BE SEALED. THE PLACEMENT OF THE SEAL SHALL
 NOT RENDER THE SIGNATURE ILLEGIBLE.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-03-14 Cont ID  
Sent By rmcdouga Date 2018-03-14 Time 19:08 Rev Time 0.00
Received By rmcdouga Date 2018-03-14 Time 18:35 Sent To  
Notes
2018-03-14 19:08:34PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 TRUSS DRAWINGS DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE TRUSS PLACEMENT PLAN AND TRUSS DRAWINGS ARE NOT
 SIGNED AND SEALED BY THE TRUSS ENGINEER. FS 471 & FAC
 61G15-31.003
  
 2) THE TRUSS PLACEMENT PLAN IS A MIRROR IMAGE OF THE
 PROPOSED STRUCTURE. SUBMIT TWO SETS OF THE PLACEMENT
 PLANS THAT MATCH THIS STRUCTURE. FBC 107.2.1
  
 3) THE FLOOR TRUSS LAYOUT DOES NOT MATCH THE FLOOR
 FRAMING PLANS THAT WERE SUBMITTED. REVISE SO THAT THEY
 MATCH. FBC-R802.1.7
  
 4) THE UPPER ROOF FRAMING PLAN DOES NOT MATCH THE TRUSS
 PLACEMENT PLAN. REVISE SO THAT THEY MATCH. FBC-R802.1.7
  
 5) TWO SETS OF FRAMING DETAILS ARE REQUIRED TO BE
 SUBMITTED FOR THE AREAS THAT WILL BE CONVENTIONALLY
 FRAMED. FBC-R802..2 & FBC 107.2.1
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2018-04-11 Cont ID  
Sent By lmarchan Date 2018-04-11 Time 09:13 Rev Time 0.00
Received By lmarchan Date 2018-04-09 Time 11:58 Sent To  
Notes
2018-04-10 11:58:49RESUB ROUTED TO RMCDOUGAL

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-03-26 Cont ID  
Sent By rmcdouga Date 2018-03-26 Time 09:22 Rev Time 0.00
Received By rmcdouga Date 2018-03-20 Time 15:07 Sent To  
Notes
2018-03-21 15:08:00RESUB ROUTED TO RMCDOUGAL

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-03-14 Cont ID  
Sent By rmcdouga Date 2018-03-14 Time 19:08 Rev Time 0.00
Received By rmcdouga Date 2018-03-13 Time 13:36 Sent To  
Notes
2018-03-14 13:36:16SUBMITTAL ROUTED TO RMCDOUGAL