Plan Review Details - Permit 18030542
Plan Review Stops For Permit 18030542
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2018-06-06 Cont ID  
Sent By skennedy Date 2018-06-06 Time 14:57 Rev Time 0.00
Received By skennedy Date 2018-06-06 Time 14:57 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2018-06-04 Cont ID  
Sent By shill Date 2018-06-04 Time 12:10 Rev Time 0.00
Received By shill Date 2018-06-04 Time 12:10 Sent To  
Notes
2018-06-04 12:10:28SEE THRESHOLD REVIEW
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2018-05-03 Cont ID  
Sent By shill Date 2018-05-03 Time 18:49 Rev Time 0.00
Received By shill Date 2018-05-03 Time 18:49 Sent To  
Notes
2018-05-03 18:55:07****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 PLEASE CONTACT ME IF YOU DO NOT UNDERSTAND THESE
 COMMENTS. DO NOT RESUBMIT WITHOUT ADDRESSING THE
 COMMENTS. NOTE THAT COMMENT #1, IF RESUBMITTED WITHOUT
 BEING ADDRESSED A THIRD TIME, REQUIRES A 4X FEE
 ASSESSED PER FLORIDA STATUTE 553.80.
  
 COMMENTS FROM PREVIOUS LIST:
  
 1. I WAS UNABLE TO LOCATE THE THRESHOLD STATEMENT
 REQUIRED BY FS553.79(7)(D); PLEASE REVISE TO INCLUDE OR
 ADVISE WHERE THIS CAN BE FOUND, SEE ALSO FBC 110.8.4.
  
 2ND REVIEW, THE SIGNED AND SEALED RESPONSE LETTER
 STATES THAT THIS WILL BE ADDRESSED BY THE CONTRACTOR.
 PLESE READ THE STATUTE REFERENCED; THIS IS THE
 RESPONSIBILITY OF THE ENGINEER AND CANNOT BE DELEGATED
 TO ANOTHER INDIVIDUAL.
  
 2. I WAS UNABLE TO LOCATE A BN LICENSE (STANDARD
 BUILDING INSPECTOR) FOR THE PROPOSED INSPECTOR, STAN
 CHARLES LONG. CITY OF WEST PALM BEACH REQUIRES A BN,
 PE, OR ARCHITECT LICENSE TO PERFORM INSPECTION SERVICES
 UNDER A SI, FBC 110.8.6. IT APPEARS THAT CHARLES S LONG
 PER DBPR WEBSITE IS AN EIT 1100018521. THIS IS NOT
 PERMITTED PER FBC 110.8.6. IF YOU WOULD LIKE TO PLEAD
 YOUR CASE TO USE AN SI, PLEASE SEND HIS RESUME AND YOUR
 RATIONALE TO ME VIA EMAIL AND I'LL TAKE TO THE BUILDING
 OFFICIAL. THIS HAS NOT BEEN PERMITTED IN THE PAST (SEE
 APPLICABLE CODE SECTION BELOW).
  
 RESPONSE LETTER STATES THIS INDIVIDUAL WILL NOT BE
 DOING INSPECTIONS AND TO REMOVE HIM FROM THE AGREEMENT.
 PLEASE HAVE CONTRACTOR COORDINATE; DUE TO WORK LOAD I
 AM UNABLE TO PERFORM CLERICAL WORK ON HIS BEHALF,
 ESPECIALLY SINCE THE AGREEMENT IS STILL INCOMPLETE,
 OTHER COMMENTS PENDING.
  
 3. AS COMMENT #1 IS NEW, UPON REQUEST THE PERMIT CAN BE
 A WALK THROUGH IF RESUBMITTED TIMELY (WITHIN THE THE
 NEXT TWO WEEKS) IF OTHER ITEMS ARE ADDRESSED IN ADVANCE
 VIA EMAIL.
  
 2ND REVIEW, COMMENT #1 IS NO LONGER NEW, BUT I'LL STILL
 WALK THROUGH IF POSSIBLE.
  
 4. THE THRESHOLD AGREEMENT WAS NOT SIGNED BY OWNER OR
 CONTRACTOR. PLEASE SEND A ***COMPLETE*** AGREEMENT
 SIGNED BY ALL PARTIES. YOU MAY SEND FOR PRELIMINARY
 REVIEW VIA EMAIL.
  
 110.8.6 THE BUILDING DEPARTMENT MAY ALLOW A SPECIAL
 INSPECTOR TO CONDUCT THE MINIMUM
 STRUCTURAL INSPECTION OF THRESHOLD BUILDINGS REQUIRED
 BY THIS CODE, SECTION 553.73, FLORIDA
 STATUTES, WITHOUT DUPLICATIVE INSPECTION BY THE
 BUILDING DEPARTMENT. THE BUILDING OFFICIAL IS
 RESPONSIBLE FOR ENSURING THAT ANY PERSON CONDUCTING
 INSPECTIONS IS QUALIFIED AS A BUILDING
 INSPECTOR UNDER PART XII OF CHAPTER 468, FLORIDA
 STATUTES, OR CERTIFIED AS A SPECIAL INSPECTOR
 UNDER CHAPTER 471 OR 481, FLORIDA STATUTES. INSPECTIONS
 OF THRESHOLD BUILDINGS REQUIRED BY
 SECTION 553.79(5), FLORIDA STATUTES, ARE IN ADDITION TO
 THE MINIMUM INSPECTIONS REQUIRED BY
 THIS CODE.
  
 2ND REVIEW, NOT ADDRESSED. PLEASE NOTE THAT THE
 AGREEMENT SUBMITTED IS OUTDATED. A NEW AGREEMENT AND
 SOP WILL BE SENT TO YOU VIA EMAIL UPON REQUEST.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2018-04-21 Cont ID  
Sent By shill Date 2018-04-21 Time 09:25 Rev Time 0.00
Received By shill Date 2018-04-21 Time 09:04 Sent To  
Notes
2018-04-21 09:25:56****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. I WAS UNABLE TO LOCATE THE THRESHOLD STATEMENT
 REQUIRED BY FS553.79(7)(D); PLEASE REVISE TO INCLUDE OR
 ADVISE WHERE THIS CAN BE FOUND, SEE ALSO FBC 110.8.4.
  
 2. I WAS UNABLE TO LOCATE A BN LICENSE (STANDARD
 BUILDING INSPECTOR) FOR THE PROPOSED INSPECTOR, STAN
 CHARLES LONG. CITY OF WEST PALM BEACH REQUIRES A BN,
 PE, OR ARCHITECT LICENSE TO PERFORM INSPECTION SERVICES
 UNDER A SI, FBC 110.8.6. IT APPEARS THAT CHARLES S LONG
 PER DBPR WEBSITE IS AN EIT 1100018521. THIS IS NOT
 PERMITTED PER FBC 110.8.6. IF YOU WOULD LIKE TO PLEAD
 YOUR CASE TO USE AN SI, PLEASE SEND HIS RESUME AND YOUR
 RATIONALE TO ME VIA EMAIL AND I'LL TAKE TO THE BUILDING
 OFFICIAL. THIS HAS NOT BEEN PERMITTED IN THE PAST (SEE
 APPLICABLE CODE SECTION BELOW).
  
 3. AS COMMENT #1 IS NEW, UPON REQUEST THE PERMIT CAN BE
 A WALK THROUGH IF RESUBMITTED TIMELY (WITHIN THE THE
 NEXT TWO WEEKS) IF OTHER ITEMS ARE ADDRESSED IN ADVANCE
 VIA EMAIL.
  
 4. THE THRESHOLD AGREEMENT WAS NOT SIGNED BY OWNER OR
 CONTRACTOR. PLEASE SEND A ***COMPLETE*** AGREEMENT
 SIGNED BY ALL PARTIES. YOU MAY SEND FOR PRELIMINARY
 REVIEW VIA EMAIL.
  
 110.8.6 THE BUILDING DEPARTMENT MAY ALLOW A SPECIAL
 INSPECTOR TO CONDUCT THE MINIMUM
 STRUCTURAL INSPECTION OF THRESHOLD BUILDINGS REQUIRED
 BY THIS CODE, SECTION 553.73, FLORIDA
 STATUTES, WITHOUT DUPLICATIVE INSPECTION BY THE
 BUILDING DEPARTMENT. THE BUILDING OFFICIAL IS
 RESPONSIBLE FOR ENSURING THAT ANY PERSON CONDUCTING
 INSPECTIONS IS QUALIFIED AS A BUILDING
 INSPECTOR UNDER PART XII OF CHAPTER 468, FLORIDA
 STATUTES, OR CERTIFIED AS A SPECIAL INSPECTOR
 UNDER CHAPTER 471 OR 481, FLORIDA STATUTES. INSPECTIONS
 OF THRESHOLD BUILDINGS REQUIRED BY
 SECTION 553.79(5), FLORIDA STATUTES, ARE IN ADDITION TO
 THE MINIMUM INSPECTIONS REQUIRED BY
 THIS CODE.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-03-22 Cont ID  
Sent By cthroop Date 2018-03-22 Time 16:40 Rev Time 0.00
Received By cthroop Date 2018-03-22 Time 14:45 Sent To  
Notes
2018-03-22 16:41:42BUILDING PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER, PX3169
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 PLEASE REVIEW THE FOLLOWING REQUIREMENTS FOR THRESHOLD
 BUILDINGS. RESPOND TO THOSE ITEMS THAT APPLY TO THIS
 PROJECT. IF YOU BELIEVE AN ITEM DOES NOT APPLY INDICATE
 BY MARKING N/A. SHOULD YOU NEED CLARIFICATION DO NOT
 HESITATE TO CALL.
  
 THRESHOLD BUILDINGS
 1. SPECIAL INSPECTOR AGREEMENT SHALL BE COMPLETED AND
 SUBMITTED IN TRIPLICATE.
 YOU MAY OBTAIN A COPY OF THE CURRENT S.I. FORM @
 ONESTOPSHOP.WPBGOV.COM.
 2. PROVIDE RESUME OF JOB INSPECTOR (P.E., ARCH. OR 468
 INSPECTOR).
 3. PROVIDE LIST OF SIMILAR PROJECTS COMPLETED BY
 CONTRACTOR.
 4. PROVIDE STRUCTURAL INSPECTION PLAN.
 5. THIS BUILDING MEETS THE DEFINITION OF: THRESHOLD
 BUILDING F.S. 553.71 (12)
 ?THRESHOLD BUILDING? ANY BUILDING WHICH IS GREATER THAN
 (3) STORIES OR 50 FT. IN HEIGHT OR WHICH HAS AN
 ASSEMBLY OCCUPANCY CLASSIFICATION AS DEFINED IN THE
 FLORIDA BUILDING CODE WHICH EXCEEDS 5,000 SQ. FT. IN
 AREA AND HAS AN OCCUPANT CONTENT OF GREATER THAN 500
 PERSONS.
 5A) THE ENFORCING AGENCY SHALL REQUIRE A SPECIAL
 INSPECTOR TO PERFORM STRUCTURAL INSPECTIONS PURSUANT TO
 A STRUCTURAL INSPECTION PLAN PREPARED BY THE ENGINEER
 OF RECORD. THE STRUCTURAL INSPECTION PLAN MUST BE
 SUBMITTED TO THE ENFORCING AGENCY PRIOR TO THE ISSUANCE
 OF A BUILDING PERMIT.
 5B) THRESHOLD INSPECTOR: WPB AMENDMENT 109.3.6.2 W.P.B.
 CONSTRUCTION SERVICES DEPARTMENT REQUESTS FOR THRESHOLD
 BUILDINGS, A SPECIAL INSPECTOR IS REQUIRED BY F.S.
 553.79 (5) TO THE MINIMUM INSPECTIONS REQUIRED BY THIS
 CODE. THE THRESHOLD INSPECTION FORMS ARE REQUIRED TO BE
 FILLED OUT BY ALL PARTIES WITH INTEREST, NOTARIZED AND
 RETURNED TO THIS OFFICE AND REVIEWED AND APPROVED
 BEFORE PERMIT ISSUANCE WILL TAKE PLACE. CONTACT KEN
 CONRAD, MANAGER OF SPECIAL INSPECTOR PROGRAM AT (561)
 805-6666 FOR FURTHER INFORMATION BEFORE THE PERMIT MAY
 BE ISSUED.
 5C) THRESHOLD BUILDING, REQUIRED. W.P.B. AMENDMENT
 110.3.7.4.4. ALL PLANS FOR THE BUILDING WHICH ARE
 REQUIRED TO BE SIGNED AND SEALED BY THE ARCHITECT OR
 ENGINEER OF RECORD CONTAIN A STATEMENT THAT, ?TO THE
 BEST OF THE ARCHITECT?S OR ENGINEER?S KNOWLEDGE, THE
 PLANS AND SPECIFICATIONS COMPLY WITH THE APPLICABLE
 FIRE-SAFETY STANDARDS AS DETERMINED BY THE LOCAL
 AUTHORITY IN ACCORDANCE WITH THIS SECTION AND 633 F.S.?
 5D) FOR THE SPECIAL INSPECTOR & DESIGNATED JOB
 INSPECTORS ? PLEASE PROVIDE A RESUME? OF INSPECTION
 EXPERIENCE ON PREVIOUS PROJECTS. THE RESUME? MUST BE
 ACCOMPANIED BY ALL CERTIFICATES AS SPECIFIED HEREIN.
 THE BUILDING OFFICIAL OR HIS DESIGNEE WILL REVIEW THE
 RESUME?. AFTER THE RESUME? IS REVIEWED, AN INTERVIEW
 MAY BE SCHEDULED.
 5E) JOB INSPECTOR ? FBC 110.3.7.6 THE BUILDING
 DEPARTMENT MAY ALLOW A SPECIAL INSPECTOR TO CONDUCT THE
 MINIMUM STRUCTURAL INSPECTION OF THRESHOLD BUILDINGS
 REQUIRED BY THIS CODE, SECTION 553.73,FLORIDA STATUTES,
 WITHOUT DUPLICATIVE INSPECTION BY THE BUILDING
 DEPARTMENT. THE BUILDING OFFICIAL IS RESPONSIBLE FOR
 ENSURING THAT ANY PERSON CONDUCTING INSPECTIONS IS
 QUALIFIED AS A BUILDING INSPECTOR UNDER PART XII OF
 CHAPTER 468, FLORIDA STATUTES, OR CERTIFIED AS A
 SPECIAL INSPECTOR UNDER CHAPTER 471 OR 481, FLORIDA
 STATUTES. INSPECTIONS OF THRESHOLD BUILDINGS REQUIRED
 BY SECTION 553.79(5), FLORIDA STATUTES, ARE IN ADDITION
 TO THE MINIMUM INSPECTIONS REQUIRED BY THIS CODE.
 5F) THE CONTRACTOR WILL PRODUCE A JOB SUMMARY OR
 HISTORY FOR THIS TYPE OF CONSTRUCTION.
 5G) NOTE FOR PAPER PLANS, 3 SETS OF DOCUMENTS ARE
 REQUIRED.
 5H) 110.3.7.4.1 THE SPECIAL INSPECTOR, UPON COMPLETION
 OF THE BUILDING AND PRIOR TO THE ISSUANCE OF A
 CERTIFICATE OF OCCUPANCY OR COMPLETION, FILE A SIGNED
 AND SEALED STATEMENT WITH THE ENFORCEMENT AGENCY IN
 SUBSTANTIALLY THE FOLLOWING FORM: ?TO THE BEST OF MY
 KNOWLEDGE AND BELIEF, THE CONSTRUCTION OF ALL
 STRUCTURAL LOAD-BEARING COMPONENTS DESCRIBED IN THE
 THRESHOLD INSPECTION PLAN COMPLIES WITH THE PERMITTED
 DOCUMENTS AND THE SPECIALTY SHORING DESIGN PROFESSIONAL
 ENGINEER HAS ASCERTAINED THAT THE SHORING AND RESHORING
 CONFORMS WITH THE SHORING AND RESHORING PLANS SUBMITTED
 TO THE ENFORCEMENT AGENCY?.
 5I) 110.3.7.4.2 ANY PROPOSAL TO INSTALL AN ALTERNATE
 STRUCTURAL PRODUCT OR SYSTEM TO WHICH BUILDING CODES
 APPLY SHALL BE SUBMITTED TO THE ENFORCEMENT AGENCY FOR
 REVIEW FOR COMPLIANCE WITH THE CODES AND MADE PART OF
 THE ENFORCEMENT AGENCY?S RECORDED SET OF PERMIT
 DOCUMENTS. 110.3.7.4.3 ALL SHORING AND RESHORING
 PROCEDURES, PLANS AND DETAILS SHALL BE SUBMITTED TO THE
 ENFORCEMENT AGENCY FOR RECORDKEEPING. EACH SHORING AND
 RESHORING INSTALLATION SHALL BE SUPERVISED, INSPECTED
 AND CERTIFIED TO BE IN COMPLIANCE WITH THE SHORING
 DOCUMENTS BY THE CONTRACTOR.
 5J) NOTICE ONLY. PLEASE CALL THE CITY OF WEST PALM
 BEACH?S AUTOMATED TELEPHONE INSPECTION LINE @ (561)
 805-6700 FOR ALL BUILDING INSPECTIONS FOR AUDITING OF
 JOBSITE INSPECTIONS. WITHOUT THIS, THE PERMIT EXPIRES
 IN 6 MONTHS WHICH WILL RESULT IN ?ABANDONMENT OF JOB,
 NO INSPECTION ACTIVITY?. THE PERMIT WILL BECOME
 EXPIRED.
 6) PLEASE PROVIDE A SITE PLAN SHOWING THE PROPERTY
 LINES, CONSTRUCTION AREAS, STAGING AREAS, HOW THE
 OCCUPANTS OF THE BUILDING WILL BE SAFE GUARDED DURING
 THEIR ENTRY AND EXIT OF THE BUILDING. SHOW COMPLIANCE
 WITH 2014 FBC 3306.7 ? COVERED WALKWAYS, INCLUDING
 LIGHTING FOR THE EXIT DISCHARGE. 2014 FBC 3310.2 ?
 MAINTENANCE OF MEANS OF EGRESS. REQUIRED MEANS OF
 EGRESS SHALL BE MAINTAINED AT ALL TIMES DURING
 CONSTRUCTION, DEMOLITION, REMODELING OR ALTERATIONS AND
 ADDITIONS TO ANY BUILDING.
 7) IF SCAFFOLDING EXTENDS BEYOND THE PRIVATE PROPERTY
 AND ONTO CITY RIGHT OF WAY, ENGINEERING WILL REQUIRE
 RIGHT OF WAY PERMITS. PLEASE CONTACT MANNY GONZALEZ AT
 THE ENGINEERING DEPARTMENT ? (561) 494-1085.
 7A) IF SCAFFOLDING IS TO BE USED FOR THE HEIGHT OF THE
 BUILDING, PLEASE PROVIDE HOW THE SCAFFOLDING WILL BE
 BUILT AS WELL AS HOW THE SCAFFOLDING WILL BE ANCHORED
 TO RESIST LATERAL WIND LOADING. THERE APPEARS SAND
 BLASTING WILL ALSO BE AN ELEMENT OF THE OPERATION, HOW
 WILL THE SANDBLASTING BE CONTAINED, WILL THERE BE WIND
 SCREENS, IF SO PLEASE PROVIDE WHAT ELEMENTS WILL BE
 INTRODUCED TO KEEP THE SCAFFOLDING FROM MOVING WITH THE
 LATERAL EFFECT OF WIND ON THE WIND SCREENS. AT WHAT
 SAFETY FACTOR ARE THESE ELEMENTS FACTORED? 107.2.1.3
 ADDITIONAL INFORMATION. 2014 FBC 3302.1 & 3306.1.
 FBC 3309 FIRE EXTINGUISHERS
 [F] 3309.1 WHERE REQUIRED.
 ALL STRUCTURES UNDER CONSTRUCTION, ALTERATION OR
 DEMOLITION SHALL BE PROVIDED WITH NO FEWER THAN ONE
 APPROVED PORTABLE FIRE EXTINGUISHER IN ACCORDANCE WITH
 SECTION 906 AND SIZED FOR NOT LESS THAN ORDINARY HAZARD
 AS FOLLOWS:
 8) PROVIDE COMPLIANCE WITH FBC 3309.1 WHERE REQUIRED.
 ALL STRUCTURES UNDER CONSTRUCTION, ALTERATION OR
 DEMOLITION SHALL BE PROVIDED WITH NO FEWER THAN ONE
 APPROVED PORTABLE FIRE EXTINGUISHER IN ACCORDANCE WITH
 SECTION 906 AND SIZED FOR NOT LESS THAN ORDINARY HAZARD
 AS FOLLOWS:
 8A) AT EACH STAIRWAY ON ALL FLOOR LEVELS WHERE
 COMBUSTIBLE MATERIALS HAVE ACCUMULATED.
 8B) IN EVERY STORAGE AND CONSTRUCTION SHED.
 8C) ADDITIONAL PORTABLE FIRE EXTINGUISHERS SHALL BE
 PROVIDED WHERE SPECIAL HAZARDS EXIST, SUCH AS THE
 STORAGE AND USE OF FLAMMABLE AND COMBUSTIBLE LIQUIDS.
 9) ALL ADD-MIXTURES RHINO PLASTIC CONCRETE ADDITIVES
 ARE TO BE REVIEWED BY THE ENGINEER OF RECORD AS WELL AS
 ALL OTHER ADDITIVES. 107.3.4 DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE.
 10) DURING RESTORATION WORK ON BALCONIES, DEMONSTRATE
 HOW THE TENANTS WILL BE SAFE GUARDED FROM THE WORK AREA
 AND EGRESS ONTO THE BALCONIES. FBC 3306.1 PROTECTION
 REQUIRED.
 SECTION 3302 CONSTRUCTION SAFEGUARDS
  
 3302.1 ALTERATIONS, REPAIRS AND ADDITIONS.
 REQUIRED EXITS, EXISTING STRUCTURAL ELEMENTS, FIRE
 PROTECTION DEVICES AND SANITARY SAFEGUARDS SHALL BE
 MAINTAINED AT ALL TIMES DURING ALTERATIONS, REPAIRS OR
 ADDITIONS TO ANY BUILDING OR STRUCTURE.
  
 EXCEPTIONS:
  
 1. WHERE SUCH REQUIRED ELEMENTS OR DEVICES ARE BEING
 ALTERED OR REPAIRED, ADEQUATE SUBSTITUTE PROVISIONS
 SHALL BE MADE.
  
 2. MAINTENANCE OF SUCH ELEMENTS AND DEVICES IS NOT
 REQUIRED WHEN THE EXISTING BUILDING IS NOT OCCUPIED.
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2018-06-04 Cont ID  
Sent By shill Date 2018-06-04 Time 12:14 Rev Time 0.00
Received By shill Date 2018-05-30 Time 15:44 Sent To  
Notes
2018-05-31 15:44:17RESUB ROUTED TO SHILL

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2018-05-03 Cont ID  
Sent By shill Date 2018-05-03 Time 18:55 Rev Time 0.00
Received By shill Date 2018-05-02 Time 15:36 Sent To  
Notes
2018-05-02 15:36:57RESUB ROUTED TO SHILL

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-04-21 Cont ID  
Sent By shill Date 2018-04-21 Time 09:26 Rev Time 0.00
Received By shill Date 2018-04-12 Time 10:48 Sent To  
Notes
2018-04-13 10:48:34RESUB ROUTED TO CTHROOP

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-03-22 Cont ID  
Sent By cthroop Date 2018-03-22 Time 17:12 Rev Time 0.00
Received By cthroop Date 2018-03-13 Time 14:57 Sent To I
Notes
2018-03-14 14:57:31BLDG MISC 1

Review Stop THRESHOLD THRESHOLD INSPECTOR DOCUMENTS
Rev No 4 Status P Date 2018-06-06 Cont ID  
Sent By skennedy Date 2018-06-06 Time 14:58 Rev Time 0.00
Received By skennedy Date 2018-06-06 Time 14:58 Sent To  
Notes
***NONE***

Review Stop THRESHOLD THRESHOLD INSPECTOR DOCUMENTS
Rev No 3 Status F Date 2018-06-04 Cont ID  
Sent By shill Date 2018-06-04 Time 12:07 Rev Time 0.00
Received By shill Date 2018-06-04 Time 12:07 Sent To  
Notes
2018-06-04 12:09:59FROM PREVIOUS LISTS; AGREEMENT LACKS CONTRACTOR'S
 SIGNATURE
  
 CARMELO GIGLIO, PE, SI; UNITED PROFESSIONAL ENGINEERING
 (RESUME AND SIGNATURE ON AGREEMENT RECEIVED & ARE OK)
  
 I AM UNABLE TO LOCATE THE CONTRACTOR'S SIGNATURE IN THE
 AGREEMENT.
  
 STAN CHARLES LONG, EIT WAS CROSSED OFF ON ONE OF THE
 THREE CONTRACTS AS A PE OR BN LICENSE IS REQUIRED.
 PLEASE REMOVE HIM FROM THE OTHER TWO AGREEMENTS.
  
  

Review Stop THRESHOLD THRESHOLD INSPECTOR DOCUMENTS
Rev No 2 Status F Date 2018-05-23 Cont ID  
Sent By shill Date 2018-05-23 Time 14:36 Rev Time 0.00
Received By shill Date 2018-05-23 Time 14:40 Sent To  
Notes
2018-05-23 14:37:13AGREEMENT NEEDS OWNER'S SIGNATURE AND CONTRACTOR'S
 SIGNATURE
  
 CARMELO GIGLIO, PE, SI; UNITED PROFESSIONAL ENGINEERING
 (RESUME AND SIGNATURE ON AGREEMENT RECEIVED & ARE OK)
  

Review Stop THRESHOLD THRESHOLD INSPECTOR DOCUMENTS
Rev No 1 Status F Date 2018-04-21 Cont ID  
Sent By shill Date 2018-04-21 Time 09:26 Rev Time 0.00
Received By shill Date 2018-04-21 Time 09:26 Sent To  
Notes
2018-04-21 09:29:28SEE BUILDING COMMENTS
  
 CARMELO GIGLIO, PE, SI; UNITED PROFESSIONAL ENGINEERING
 (RESUME AND SIGNATURE ON AGREEMENT RECEIVED & ARE OK)
  