Plan Review Details - Permit 18030517
Plan Review Stops For Permit 18030517
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2018-05-01 Cont ID  
Sent By jleahy Date 2018-05-01 Time 08:10 Rev Time 0.00
Received By jleahy Date 2018-05-01 Time 10:07 Sent To  
Notes
2018-04-19 17:12:10FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 PLANS NEED TO BE SIGNED AND SEALED BY AND ELECTRICAL
 ENGINEER BASED ON 480 VOLT CONTROLER

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-03-23 Cont ID  
Sent By jleahy Date 2018-03-23 Time 11:23 Rev Time 0.00
Received By jleahy Date 2018-03-23 Time 11:23 Sent To I
Notes
2018-03-23 11:30:12FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 CUT SHEETS SUBMITTED ARE NOT FOR THE CONTROLLER
 INSTALLED.
  
 JOCKEY PUMP CONTROLLER PAPER WORK NOT SHOWN.
  
 HAS FIRE PUMP BEEN REPLACED OR JUST REFURBISHED?
  
 VALUE OF $18,690 IS TO LOW FOR THE CONTROLLER AND
 INSTALLATION.
 SHOW BILL OF SALE FOR CONTROLLER, AND CONTRACTORS
 CONTRACT FOR THE INSTALLATION
  
 WHO DID THE PLUMBING PORTION OF THE WORK, PLEASE SUBMIT
 PERMIT FOR THAT WORK ALSO.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2018-04-11 Cont ID  
Sent By pleduc Date 2018-04-11 Time   Rev Time 0.00
Received By pleduc Date 2018-04-10 Time 15:58 Sent To E
Notes
2018-04-11 11:02:23THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
  
 1) THE INSTALLATION SHALL BE INSPECTED AND TESTED PER
 NFPA 20 & 25 AND WITNESSED BY A FIRE INSPECTOR.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2018-03-14 Cont ID  
Sent By pleduc Date 2018-03-14 Time   Rev Time 0.00
Received By pleduc Date 2018-03-13 Time 16:55 Sent To E
Notes
2018-03-14 12:14:50THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
  
 1) THE INSTALLATION SHALL BE INSPECTED AND TESTED PER
 NFPA 20 & 25 AND WITNESSED BY A FIRE INSPECTOR.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2018-05-01 Cont ID  
Sent By jleahy Date 2018-05-01 Time 10:06 Rev Time 0.00
Received By jleahy Date 2018-05-01 Time 10:06 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-04-20 Cont ID  
Sent By jleahy Date 2018-04-20 Time 08:15 Rev Time 0.00
Received By jleahy Date 2018-04-09 Time 11:39 Sent To  
Notes
2018-04-10 11:40:01RESUB ROUTED TO FIRE INBOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-03-23 Cont ID  
Sent By jleahy Date 2018-03-23 Time 11:30 Rev Time 0.00
Received By jleahy Date 2018-03-12 Time 15:37 Sent To  
Notes
2018-03-13 15:37:55ROUTED TO FIRE INBOX

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2018-03-19 Cont ID  
Sent By ccole Date 2018-03-19 Time 16:55 Rev Time 0.00
Received By ccole Date 2018-03-19 Time 16:55 Sent To  
Notes
***NONE***