Plan Review Details - Permit 18030471
Plan Review Stops For Permit 18030471
Review Stop E ELECTRICAL
Rev No 1 Status P Date 2018-03-19 Cont ID  
Sent By ppetty Date 2018-03-19 Time 12:47 Rev Time 0.00
Received By ppetty Date 2018-03-19 Time 12:44 Sent To  
Notes
2018-03-19 12:48:10PLEASE SEE F/D PROVISO FOR DUCT DETECTORS

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2018-03-14 Cont ID  
Sent By pleduc Date 2018-03-14 Time   Rev Time 0.00
Received By pleduc Date 2018-03-13 Time 16:55 Sent To E
Notes
2018-03-14 11:59:18THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
  
 1) IF APPLICABLE TO THIS PROJECT, THE ACTIVATION OF A
 DUCT DETECTOR SHALL SEND A SUPERVISORY SIGNAL, NOT A
 FULL ALARM.
  
 NFPA 90A
  
 6.4.3* FUNCTION.
 6.4.3.1 SMOKE DETECTORS PROVIDED AS REQUIRED BY 6.4.2
 SHALL AUTOMATICALLY STOP THEIR RESPECTIVE FAN(S) ON
 DETECTING THE PRESENCE OF SMOKE.
  
 6.4.4.2.1 SMOKE DETECTORS USED SOLELY FOR CLOSING
 DAMPERS OR FOR HEATING, VENTILATING, AND
 AIR-CONDITIONING SYSTEM SHUTDOWN SHALL NOT BE REQUIRED
 TO ACTIVATE THE BUILDING EVACUATION ALARM.
  
 NFPA 72
  
 21.7.4 SMOKE DETECTORS MOUNTED IN THE AIR DUCTS OF HVAC
 SYSTEMS SHALL INITIATE A SUPERVISORY SIGNAL.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-03-19 Cont ID  
Sent By ppetty Date 2018-03-19 Time 12:48 Rev Time 0.00
Received By ppetty Date 2018-03-12 Time 15:13 Sent To  
Notes
2018-03-13 15:13:20ROUTED TO FIRE INBOX