Plan Review Details - Permit 18030448
Plan Review Stops For Permit 18030448
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2018-04-24 Cont ID  
Sent By rmcdouga Date 2018-04-24 Time 15:52 Rev Time 0.00
Received By rmcdouga Date 2018-04-24 Time 14:33 Sent To I
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2018-04-06 Cont ID  
Sent By rmcdouga Date 2018-04-06 Time 18:13 Rev Time 0.00
Received By rmcdouga Date 2018-04-06 Time 17:51 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-03-14 Cont ID  
Sent By jwitmer Date 2018-03-14 Time 07:31 Rev Time 0.00
Received By jwitmer Date 2018-03-14 Time 06:58 Sent To  
Notes
2018-03-14 07:33:512017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 18030448
 ADD: 516 S. DIXIE HWY.
 CONT: MODERN CONSTRUCTION CORP.
 TEL: 954-422-9901
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: WED. MARCH 14/ 2018
 ACTION: DENIED
  
 1) THE COVERSHEET A.1 AND S1 BOTH INDICATE THEY WERE
 CREATED USING THE 2014 FBC-B. PLEASE BE AWARE THE 2017
 FBC, THE 6TH EDITION OF THE FLORIDA BUILDING CODE WAS
 ADOPTED STATEWIDE ON DEC. 31, 2017, PLEASE UPDATE THE
 CODE REFERENCE.
  
 2) THE COVERSHEET A.1 AND S1 BOTH INDICATE A NEW
 EXTERIOR STAIR AT THE REAR OF THE STORE. THERE ARE 3
 RISERS LABELED 7 INCHES, 7 INCHES AND 4 INCHES A TOTAL
 RISE OF 18 INCHES. 18/3=6 INCHES. PLEASE REVIEW SECTION
 1011.5.4. OF THE FBC-B.
 FBC-B 1011.5.4 DIMENSIONAL UNIFORMITY. STAIR TREADS AND
 RISERS SHALL BE OF UNIFORM SIZE AND SHAPE. THE
 TOLERANCE BETWEEN THE LARGEST AND SMALLEST RISER HEIGHT
 OR BETWEEN THE LARGEST AND SMALLEST TREAD DEPTH SHALL
 NOT EXCEED 3/8 INCH IN ANY FLIGHT OF STAIRS. THE
 GREATEST WINDER TREAD DEPTH AT THE WALKLINE WITHIN ANY
 FLIGHT OF STAIRS SHALL NOT EXCEED THE SMALLEST BY MORE
 THAN 3/8 INCH.
  
 3) SHEET S1 INDICATES THERE WAS A SOILS INVESTIGATIVE
 REPORT FOR RECOMMENDATIONS FOR INSTALLATION, REPORT BY
 NVS INC. REPORT # 15593 FEB. 21/ 2017. PLEASE SUBMIT
 REPORT. FBC-B 1803.5.2 QUESTIONABLE SOIL.
  
 4) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 DEVELOPMENT SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2018-04-08 Cont ID  
Sent By jpearson Date 2018-04-08 Time 12:02 Rev Time 0.00
Received By jpearson Date 2018-04-08 Time 12:02 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-03-15 Cont ID  
Sent By jpearson Date 2018-03-15 Time 09:20 Rev Time 0.00
Received By jpearson Date 2018-03-15 Time 08:06 Sent To  
Notes
2018-03-15 09:20:15CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. SHOW WINDOW CALCULATION REFERENCES THE 2011 NEC,
 WHICH IS NOT THE CURRENT CODE. PROVIDE CORRECTION TO
 2014 NEC. FBC PREFACE
 2. PROVIDE GFCI PROTECTION FOR DRINKING FOUNTAIN. NEC
 422.52
 3. BE ADVISED THAT FIRE ALARM, LOW VOLTAGE SYSTEMS,
 DAS, LIGHTNING PROTECTION, GENERATORS, COMMERCIAL HOOD
 SYSTEMS, WALK IN COOLERS, SIGNS, SITE LIGHTING, AND
 SWIMMING POOLS (WHERE APPLICABLE) ARE NOT INCLUDED IN
 THE SCOPE OF THIS PLAN REVIEW. PROVIDE A BLOCK NOTE
 INDICATING THE REQUIRED SEPARATE PERMITS AND DATA
 SPECIFICATION SHEET SUBMITTALS FOR ANY OF THESE SYSTEMS
 PRESENT. FBC 105.1, 107.2.1
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2018-04-12 Cont ID  
Sent By pleduc Date 2018-04-12 Time   Rev Time 0.00
Received By pleduc Date 2018-04-12 Time 12:46 Sent To I
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2018-03-14 Cont ID  
Sent By pleduc Date 2018-03-14 Time   Rev Time 0.00
Received By pleduc Date 2018-03-14 Time 15:19 Sent To  
Notes
2018-03-14 16:34:10 
  
  
 1) STAIRS INDICATED AT DOOR D 102 DO NOT APPEAR TO MEET
 THE REQUIRMENTS OF NFPA 101.
  
 PER NFPA 101, CHAPTER 38, NEW BUSINESS
  
 38.2.2.3 STAIRS.
 38.2.2.3.1 STAIRS COMPLYING WITH 7.2.2 SHALL BE
 PERMITTED
  
 7.2.2 STAIRS.
 7.2.2.1 GENERAL.
 7.2.2.1.1 STAIRS USED AS A COMPONENT IN THE MEANS OF
 EGRESS SHALL
 CONFORM TO THE GENERAL REQUIREMENTS OF SECTION 7.1 AND
 TO THE
 SPECIAL REQUIREMENTS OF 7.2.2, UNLESS OTHERWISE
 SPECIFIED IN
 7.2.2.1.2.
  
 7.2.2.3.6* DIMENSIONAL UNIFORMITY.
 7.2.2.3.6.1 VARIATION IN EXCESS OF 3?16 IN. (4.8 MM) IN
 THE SIZES OF
 ADJACENT TREAD DEPTHS OR IN THE HEIGHT OF ADJACENT
 RISERS SHALL BE
 PROHIBITED, UNLESS OTHERWISE PERMITTED IN 7.2.2.3.6.3.
 7.2.2.3.6.2 THE VARIATION BETWEEN THE SIZES OF THE
 LARGEST AND SMALLEST
 RISER OR BETWEEN THE LARGEST AND SMALLEST TREAD DEPTHS
 SHALL NOT EXCEED ?
 IN. (9.5 MM) IN ANY FLIGHT.
  
 PLEASE REVIEW AND CORRECT.
  
  
 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2018-04-24 Cont ID  
Sent By rmcdouga Date 2018-04-24 Time 15:52 Rev Time 0.00
Received By rmcdouga Date 2018-04-16 Time 15:14 Sent To  
Notes
2018-04-17 15:15:10RESUB ROUTED TO CCOLE

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-04-16 Cont ID  
Sent By lmarchan Date 2018-04-16 Time 11:06 Rev Time 0.00
Received By lmarchan Date 2018-04-04 Time 14:06 Sent To  
Notes
2018-04-05 14:06:32B20

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-03-21 Cont ID  
Sent By gjohnson Date 2018-03-21 Time 17:08 Rev Time 0.00
Received By gjohnson Date 2018-03-09 Time 13:28 Sent To  
Notes
2018-03-12 13:29:05B27

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2018-03-14 Time 07:30 Rev Time 0.00
Received By jwitmer Date 2018-03-14 Time 06:58 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2018-04-20 Cont ID  
Sent By ccole Date 2018-04-20 Time 15:19 Rev Time 0.00
Received By ccole Date 2018-04-20 Time 15:19 Sent To B
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2018-04-09 Cont ID  
Sent By ccole Date 2018-04-09 Time 12:49 Rev Time 0.00
Received By ccole Date 2018-04-09 Time 12:49 Sent To  
Notes
2018-04-09 13:11:231ST REVIEW FBC-2017 MECHANICAL, EXISTING BUILDING CODE
 PERMIT #18030448
 4/9/2018
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE NEW AC CLOSET DOOR SHALL BE NON-COMBUSTIBLE PER
 SECTION 602.2.1.
  
 2) REFER TO SECTION 809.1 AND 809.2 FBC-17 EXISTING
 BUILDING CODE AND PROVIDE MINIMUM VENTILATION
 CALCULATIONS FOR ALL ROOMS AND SPACES PER TABLE 403.3
 FBC-17 MECHANICAL. PROVIDE A SCHEDULE THAT INDICATES
 THE REQUIRED AND PROVIDED CFMS OF OUTDOOR AIR.
  
 3) PLEASE PROVIDE THE SUPPLY CFMS AT EACH DIFFUSER
 LOCATION.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2018-03-15 Cont ID  
Sent By ccole Date 2018-03-15 Time 10:24 Rev Time 0.00
Received By ccole Date 2018-03-15 Time 10:24 Sent To  
Notes
2018-03-15 10:29:151ST REVIEW FBC-2014 MECHANICAL , WEST PALM BEACH
 AMENDMENTS TO THE FBC.
 PERMIT #18030448
 3/15/18
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) NO MECHANICAL PLANS WERE INCLUDED WITH THE PLAN
 SETS. PLEASE PROVIDE PLANS FOR REVIEW- SECTION 107.2.1
 WPB AMENDMENTS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2018-04-10 Cont ID  
Sent By gjohnson Date 2018-04-10 Time 13:55 Rev Time 0.00
Received By gjohnson Date 2018-04-10 Time 11:43 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2018-03-21 Cont ID  
Sent By gjohnson Date 2018-03-21 Time 17:08 Rev Time 0.00
Received By gjohnson Date 2018-03-21 Time 17:08 Sent To  
Notes
2018-03-21 17:08:341ST REVIEW: FBC 2017 6TH EDITION
  
 PLUMBING COMMENTS:
  
 1. SHOW COMPLIANCE WITH FBC ACC 602
  
 2. TEMPERED WATER SHALL BE DELIVERED FROM LAVATORIES
 AND GROUP WASH FIXTURES LOCATED IN PUBLIC TOILET
 FACILITIES PROVIDED FOR CUSTOMERS, PATRONS AND
 VISITORS. TEMPERED WATER SHALL BE DELIVERED THROUGH AN
 APPROVED WATER-TEMPERATURE LIMITING DEVICE THAT
 CONFORMS TO ASSE 1070 OR CSA B125.3. PER FBC PL 416.5
  
 3. SHT. P.1 UNDER PLUMB FIXTURE SCHEDULE IT LIST THE
 MIAMI DADE CODE THAT DOES NOT APPLY TO THIS JOB,.ALL
 PLUMBING FIXTURES AND PIPING SHALL COMPLY WITH FBC PL
 2017 6TH EDITION
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  