Plan Review Details - Permit 18030447
Plan Review Stops For Permit 18030447
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2018-03-23 Cont ID  
Sent By jwitmer Date 2018-03-23 Time 14:20 Rev Time 0.00
Received By jwitmer Date 2018-03-23 Time 13:33 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-03-13 Cont ID  
Sent By jwitmer Date 2018-03-13 Time 16:52 Rev Time 0.00
Received By jwitmer Date 2018-03-13 Time 15:27 Sent To  
Notes
2018-03-13 16:52:152017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 18030447
 ADD: 809 BELVEDERE RD.
 CONT: HOMESTAR SERVICES
 TEL: 561-201-3629
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: TUES. MARCH 13/ 2018
 ACTION: DENIED
  
 1) SHEET A3 SHOWS A CORRIDOR WIDTH OF 4 FEET AND A
 OUTSWING RESTROOM DOOR, THE DOOR IS NOT IDENTIFIED BY A
 DOOR TAG. THIS SHEET IDENTIFIES DOOR TYPE A AS A 3 FOOT
 WIDE DOOR. PLEASE SHOW COMPLIANCE WITH THE 2017 FBC-B
 SECTION 1005.7.1 DOORS. DOORS, WHEN FULLY OPENED, SHALL
 NOT REDUCE THE REQUIRED WIDTH BY MORE THAN 7 INCHES.
 DOORS IN ANY POSITION SHALL NOT REDUCE THE REQUIRED
 WIDTH BY MORE THAN ONE-HALF.
 THE MINIMUM WIDTH OF THE CORRIDOR FINISH WALL TO WALL
 WOULD BE 36 + 18 = 54 INCHES FOR THE OUTSWING DOOR OF
 THE RESTROOM.
 OR
 2017 FBC-ACCESSIBILITY CODE SECTION 603.2.3 DOOR SWING.
 DOORS SHALL NOT SWING INTO THE CLEAR FLOOR SPACE OR
 CLEARANCE REQUIRED FOR ANY FIXTURE. DOORS SHALL BE
 PERMITTED TO SWING INTO THE REQUIRED TURNING SPACE.
 EXCEPTIONS:
 2.WHERE THE TOILET ROOM OR BATHING ROOM IS FOR
 INDIVIDUAL USE AND A CLEAR FLOOR SPACE COMPLYING WITH
 305.3 IS PROVIDED WITHIN THE ROOM BEYOND THE ARC OF THE
 DOOR SWING, DOORS SHALL BE PERMITTED TO SWING INTO THE
 CLEAR FLOOR SPACE OR CLEARANCE REQUIRED FOR ANY
 FIXTURE.
  
 2) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2018-03-23 Cont ID  
Sent By jpearson Date 2018-03-23 Time 15:54 Rev Time 0.00
Received By jpearson Date 2018-03-23 Time 15:53 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-03-15 Cont ID  
Sent By jpearson Date 2018-03-15 Time 08:54 Rev Time 0.00
Received By jpearson Date 2018-03-15 Time 08:07 Sent To  
Notes
2018-03-15 08:54:51CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE THE ADDITIONAL AUTOMATIC LIGHTING CONTROLS
 STIPULATED IN THE FBC ENERGY CODE. FBC EC C405.2
 2. EMERGENCY AND EXIT LIGHTS ARE REQUIRED TO BE FED
 FROM THE GENERAL LIGHTING CIRCUIT IN THE AREA. PROVIDE
 CORRECTION. NEC 700.12(F)
 3. BREAKER FOR WATER HEATER IS STATED AS 30 AMP, WHICH
 IS TOO LARGE FOR THIS LOAD. BREAKER SHOULD BE SIZED AT
 125% OF THE LOAD, WHICH WOULD REQUIRE A 25 AMP BREAKER.
 PROVIDE CORRECTION. NEC 422.13
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2018-03-27 Cont ID  
Sent By pleduc Date 2018-03-27 Time   Rev Time 0.00
Received By pleduc Date 2018-03-27 Time 13:24 Sent To I
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2018-03-14 Cont ID  
Sent By pleduc Date 2018-03-14 Time   Rev Time 0.00
Received By pleduc Date 2018-03-14 Time 15:19 Sent To  
Notes
2018-03-14 15:49:35THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) TWO EXITS ARE INDICATED ON SHEET A 3 AND E 1. THE
 DOOR TO THE BATHROOM IS OUT SWINGING OBSTRUCTUNG THE
 EXIT TRAVEL PATH.
  
 ONE EXIT MAY BE ALL THAT IS REQUIRED IF IT MEETS THE
 REQUIRMENTS LISTED BELOW. IF SO, THE EXIT SIGN BY THE
 BATHROOM MAY BE REMOVED AND THE BATHROOM DOOR REMAIN.
  
 PLEASE REVIEW ALONG WITH BUILDING COMMENTS.
  
 38.2 MEANS OF EGRESS REQUIREMENTS.
 38.2.1 GENERAL.
 38.2.1.1 ALL MEANS OF EGRESS SHALL BE IN ACCORDANCE
 WITH CHAPTER 7 AND
 THIS CHAPTER.
  
 38.2.4 NUMBER OF MEANS OF EGRESS.
 38.2.4.1 MEANS OF EGRESS SHALL COMPLY WITH ALL OF THE
 FOLLOWING, EXCEPT
 AS OTHERWISE PERMITTED BY 38.2.4.2 THROUGH 38.2.4.6:
 (1) THE NUMBER OF MEANS OF EGRESS SHALL BE IN
 ACCORDANCE WITH
 SECTION 7.4.
 (2) NOT LESS THAN TWO SEPARATE EXITS SHALL BE PROVIDED
 ON EVERY STORY.
 (3) NOT LESS THAN TWO SEPARATE EXITS SHALL BE
 ACCESSIBLE FROM EVERY
 PART OF EVERY STORY.
 38.2.4.2 EXIT ACCESS, AS REQUIRED BY 38.2.4.1(3), SHALL
 BE PERMITTED TO
 INCLUDE A SINGLE EXIT ACCESS PATH FOR THE DISTANCES
 PERMITTED AS COMMON
 PATHS OF TRAVEL BY 38.2.5.3.
 38.2.4.3 A SINGLE EXIT SHALL BE PERMITTED FOR A ROOM OR
 AREA WITH A TOTAL
 OCCUPANT LOAD OF LESS THAN 100 PERSONS, PROVIDED THAT
 ALL OF THE
 FOLLOWING CRITERIA ARE MET:
 (1) THE EXIT SHALL DISCHARGE DIRECTLY TO THE OUTSIDE AT
 THE LEVEL OF EXIT
 DISCHARGE FOR THE BUILDING.
 (2) THE TOTAL DISTANCE OF TRAVEL FROM ANY POINT,
 INCLUDING TRAVEL WITHIN
 THE EXIT, SHALL NOT EXCEED 100 FT (30 M).
 (3) THE TOTAL DISTANCE OF TRAVEL SPECIFIED IN
 38.2.4.3(2) SHALL BE ON THE
 SAME STORY, OR, IF TRAVERSING OF STAIRS IS NECESSARY,
 SUCH STAIRS SHALL
 NOT EXCEED 15 FT (4570 MM) IN HEIGHT, AND BOTH OF THE
 FOLLOWING
 ALSO SHALL APPLY:
 (A) INTERIOR STAIRS SHALL BE PROVIDED WITH COMPLETE
 ENCLOSURES TO
 SEPARATE THEM FROM ANY OTHER PART OF THE BUILDING, WITH
 NO
 DOOR OPENINGS THEREIN.
 (B) A SINGLE OUTSIDE STAIR IN ACCORDANCE WITH 7.2.2
 SHALL BE
 PERMITTED TO SERVE ALL STORIES PERMITTED WITHIN THE 15
 FT (4570
 MM) VERTICAL TRAVEL LIMITATION.
  
  
 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-03-27 Cont ID  
Sent By cpuell Date 2018-03-27 Time 16:49 Rev Time 0.00
Received By cpuell Date 2018-03-21 Time 13:10 Sent To  
Notes
2018-03-22 13:10:40B05

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-03-15 Cont ID  
Sent By gjohnson Date 2018-03-15 Time 12:06 Rev Time 0.00
Received By gjohnson Date 2018-03-09 Time 13:35 Sent To  
Notes
2018-03-12 13:35:29B29

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2018-03-13 Cont ID  
Sent By jwitmer Date 2018-03-13 Time 16:52 Rev Time 0.00
Received By jwitmer Date 2018-03-13 Time 15:27 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2018-03-26 Cont ID  
Sent By gjohnson Date 2018-03-26 Time 10:54 Rev Time 0.00
Received By gjohnson Date 2018-03-26 Time 10:14 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2018-03-15 Cont ID  
Sent By gjohnson Date 2018-03-15 Time 11:12 Rev Time 0.00
Received By gjohnson Date 2018-03-15 Time 11:11 Sent To  
Notes
2018-03-15 12:04:131ST REVIEW: FBC 2017 6TH EDITION
  
 PLUMBING COMMENTS:
  
 1. THE WASTE ARM FOR THE SINKS SHALL BE VENTED WITH A
 AIR ADMITTANCE VALVE OR REVENTED BACK TO THE VENT
 STACK. IT APPEARS THAT YOU HAVE A DEVELOPED LENGTH OF
 ABOUT 35', THE MAX YOU CAN RUN A 3" WASTE ARM FROM THE
 VENT TO THE FIXTURE TRAP IS 12' BUSHING IT DOWN TO 2"
 DOES NOT EXTEND THAT LENGTH YOUR DEVELOPED LENGTH WOULD
 BE FROM THE VERTICAL STACK TO THE LAST FIXTURE TRAP.
 FBC PL 909.1 AND TABLE 909.1 AND 901.2.1
  
 2. TEMPERED WATER SHALL BE DELIVERED FROM LAVATORIES
 AND GROUP WASH FIXTURES LOCATED IN PUBLIC TOILET
 FACILITIES PROVIDED FOR CUSTOMERS, PATRONS AND
 VISITORS. TEMPERED WATER SHALL BE DELIVERED THROUGH AN
 APPROVED WATER-TEMPERATURE LIMITING DEVICE THAT
 CONFORMS TO ASSE 1070 OR CSA B125.3. PER FBC PL 416.5
  
 3. THE LAVATORY AND TOILET ARE MISSING FROM THE WATER
 ISOMETRIC IF THEY ARE EXISTING TO REMAIN SHOW ON
 ISOMETRIC AND MARK EXISTING THEY SHALL BE CODE
 COMPLIANT TO CURRENT CODE. PER WPB AMEND TO FBC 107.2.1
  
 4. PLEASE SHOW COMPLIANCE WITH FBC ACC 604.7
 DISPENSERS.TOILET PAPER DISPENSERS SHALL COMPLY WITH
 309.4 AND SHALL BE 7 INCHES (180 MM) MINIMUM AND 9
 INCHES (230 MM) MAXIMUM IN FRONT OF THE WATER CLOSET
 MEASURED TO THE CENTERLINE OF THE DISPENSER. THE OUTLET
 OF THE DISPENSER SHALL BE 15 INCHES (380 MM) MINIMUM
 AND 48 INCHES (1220 MM) MAXIMUM ABOVE THE FINISH FLOOR.
  
 5. PLEASE SHOW COMPLIANCE WITH FBC ACC 609.4 POSITION
 OF GRAB BARS. GRAB BARS SHALL BE INSTALLED IN A
 HORIZONTAL POSITION, 33 INCHES (840 MM) MINIMUM AND 36
 INCHES (915 MM) MAXIMUM ABOVE THE FINISH FLOOR MEASURED
 TO THE TOP OF THE GRIPPING SURFACE,
  
 6. SHT. A2 UNDER TOILET FIXTURE SPECIFICATIONS #8 LIST
 A WATER FOUNTAIN IT IS NOT SHOWN ON THE PLUMBING
 DRAWINGS PLEASE CLARIFY. PER WPB AMEND TO FBC 107.2.1
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  