Plan Review Details - Permit 18030416
Plan Review Stops For Permit 18030416
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2018-03-30 Cont ID  
Sent By cthroop Date 2018-03-30 Time 10:02 Rev Time 0.00
Received By cthroop Date 2018-03-30 Time 10:02 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-03-26 Cont ID  
Sent By cthroop Date 2018-03-26 Time 13:24 Rev Time 0.00
Received By cthroop Date 2018-03-26 Time 13:13 Sent To  
Notes
2018-03-26 13:28:03BUILDING PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER, PX3169
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. PROPERTY IS OWNED BY A FL CORP.
 2. CORP. MAY NOT APPLY FOR OWNER/BUILDERS PERMIT PER FL
 ATTORNEY GENERAL'S OPINION AGO 91-05. CONTRACTOR
 REQUIRED.
 3. INDICATE ON PLANS IF RACKS ARE ATTACHED TO
 STRUCTURE.
 4. DESIGNER TO PRINT NAME AND SIGN PLAN.
  
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE
 DIMENSIONED AND DRAWN UPON SUITABLE MATERIAL.
 CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY
 TO INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK
 PROPOSED AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE
 PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES,
 RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING
 OFFICIAL.
  
 FBC 107.2.1 ALL INFORMATION, DRAWINGS, SPECIFICATIONS
 AND ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE
 OF THE PERSON RESPONSIBLE FOR THE DESIGN. (SEE ALSO
 SECTION 107.3.5) AND F.S. 481.229.
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2018-03-29 Cont ID  
Sent By pleduc Date 2018-03-29 Time   Rev Time 0.00
Received By pleduc Date 2018-03-29 Time 09:31 Sent To B
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2018-03-14 Cont ID  
Sent By pleduc Date 2018-03-14 Time   Rev Time 0.00
Received By pleduc Date 2018-03-14 Time 15:18 Sent To B
Notes
2018-03-14 16:41:52THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
  
 1) THERE ARE NO MANUFACTURES SPEC SHEETS PROVIDED TO
 REVEIW FOR REQUIRED SECURING TO FLOOR, WEIGHT LIMITS
 FOR PROPOSE PRODUCTS, AND TYPE OF CONSTRUCTION,
 METAL/WOOD/COMPOSIT ETC.
  
 PLEASE PROVIDE DETAILS
  
  
 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-03-30 Cont ID  
Sent By cthroop Date 2018-03-30 Time 10:02 Rev Time 0.00
Received By cthroop Date 2018-03-27 Time 13:27 Sent To  
Notes
2018-03-28 13:27:26RESUB ROUTED TO FIRE INBOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-03-26 Cont ID  
Sent By cthroop Date 2018-03-26 Time 13:28 Rev Time 0.00
Received By cthroop Date 2018-03-09 Time 13:58 Sent To I
Notes
2018-03-14 09:06:053/14 TO FIRE BOX
  
2018-03-12 13:58:47ROUTED TO SHILL