Plan Review Details - Permit 18030386
Plan Review Stops For Permit 18030386
Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date   Cont ID  
Sent By   Date 2018-07-18 Time   Rev Time 0.00
Received By lmarchan Date 2018-07-11 Time 13:38 Sent To  
Notes
2018-07-12 13:39:05RESUB ROUTED TO CCOLE

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date   Cont ID  
Sent By   Date 2018-06-25 Time   Rev Time 0.00
Received By lmarchan Date 2018-06-20 Time 11:09 Sent To  
Notes
2018-06-21 11:09:20RESUB ROUTED TO CCOLE

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date   Cont ID  
Sent By   Date 2018-06-12 Time   Rev Time 0.00
Received By lmarchan Date 2018-06-05 Time 13:47 Sent To  
Notes
2018-06-06 13:47:52RESUB ROUTED TO CCOLE
 *TRAVELLING WITH 18030388*

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-05-02 Cont ID  
Sent By lmarchan Date 2018-05-02 Time 14:59 Rev Time 0.00
Received By lmarchan Date 2018-04-11 Time 13:27 Sent To  
Notes
2018-04-12 13:27:48**TRAVELLING WITH 18030381**

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2018-03-19 Time   Rev Time 0.00
Received By lmarchan Date 2018-03-08 Time 13:29 Sent To  
Notes
2018-03-09 13:29:52**TRAVELLING WITH 18030381**

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2018-07-18 Cont ID  
Sent By ccole Date 2018-07-18 Time 11:39 Rev Time 0.00
Received By ccole Date 2018-07-18 Time 11:39 Sent To I
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2018-06-25 Cont ID  
Sent By ccole Date 2018-06-25 Time 16:07 Rev Time 0.00
Received By ccole Date 2018-06-25 Time 16:07 Sent To I
Notes
2018-06-25 16:24:363RD REVIEW FBC-2017 MECHANICAL
 PERMIT #18030386
 6/25/18
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE $1200.00 JOB VALUE ON THE APPLICATION IS LOW FOR
 A 144 SQ. FT. WALKIN COOLER/FREEZER. PERMIT VALUE IS
 BASED ON LABOR, MATERIAL, AND EQUIPMENT PER SECTION
 109.3 WPB. IT APPEARS THE $1200.00 MAY BE FOR LABOR
 ONLY. PLEASE CLARIFY AND PROVIDE AN ACCURATE VALUE. IF
 THE BOX AND THE REFRIGERATION WERE INCLUDED IN THE
 VALUE OF THE MAIN PERMIT, PLEASE PROVIDE DOCUMENTATION
 TO VERIFY THAT.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2018-06-12 Cont ID  
Sent By ccole Date 2018-06-12 Time 14:54 Rev Time 0.00
Received By ccole Date 2018-06-12 Time 14:54 Sent To I
Notes
2018-06-12 14:58:362ND REVIEW FBC-2017 MECHANICAL
 PERMIT #18030386
 6/12/18
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC R- FLORIDA RESIDENTIAL CODE SIXTH EDITION 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE PROVIDE REFRIGERATION PLANS AND
 SPECIFICATIONS FOR THE WALKIN COOLER AND FREEZER.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2018-03-19 Cont ID  
Sent By ccole Date 2018-03-19 Time 11:40 Rev Time 0.00
Received By ccole Date 2018-03-19 Time 11:40 Sent To  
Notes
2018-03-19 12:04:321ST REVIEW FBC-2017 MECHANICAL , ENERGY CONSERVATION
 CODES, WEST PALM BEACH AMENDMENTS TO THE FBC-17
 PERMIT #18030386
 3/19/18
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) M-2.0: THE AIR BALANCE SCHEDULE DOES NOT PROVIDE
 CALCULATIONS FOR THE REQUIRED REPLACEMENT AIR FOR THE
 KITCHEN EXHAUST SYSTEMS- SEE SECTION 508.1.2.
  
 2) PLEASE SHOW COMPLIANCE WITH SECTION 508.1.1 MAKEUP
 AIR TEMPERATURE- FBC-17 MECHANICAL, AND SECTION
 C403.2.8 FBC-17 ENERGY CONSERVATION.
  
 508.1.1 MAKEUP AIR TEMPERATURE.
 THE TEMPERATURE DIFFERENTIAL BETWEEN MAKEUP AIR AND THE
 AIR IN THE CONDITIONED SPACE SHALL NOT EXCEED 10
 DEGREES F (6 DEGREES C) EXCEPT WHERE THE ADDED HEATING
 AND COOLING LOADS OF THE MAKEUP AIR DO NOT EXCEED THE
 CAPACITY OF THE HVAC SYSTEM.
  
 C403.2.8 KITCHEN EXHAUST SYSTEMS.
 REPLACEMENT AIR INTRODUCED DIRECTLY INTO THE EXHAUST
 HOOD CAVITY SHALL NOT BE GREATER THAN 10 PERCENT OF THE
 HOOD EXHAUST AIRFLOW RATE. CONDITIONED SUPPLY AIR
 DELIVERED TO ANY SPACE SHALL NOT EXCEED THE GREATER OF
 THE FOLLOWING:
 1.THE VENTILATION RATE REQUIRED TO MEET THE SPACE
 HEATING OR COOLING LOAD.
 2.THE HOOD EXHAUST FLOW MINUS THE AVAILABLE TRANSFER
 AIR FROM ADJACENT SPACE WHERE AVAILABLE TRANSFER AIR IS
 CONSIDERED THAT PORTION OF OUTDOOR VENTILATION AIR NOT
 REQUIRED TO SATISFY OTHER EXHAUST NEEDS, SUCH AS
 RESTROOMS, AND NOT REQUIRED TO MAINTAIN PRESSURIZATION
 OF ADJACENT SPACES.
  
 3) M-3.0: PLEASE IDENTIFY ALL THE COOKING APPLIANCES
 SHOWN IN THE HOOD 2 ELEVATION VIEW. CLARIFY IF THE
 HOODS ARE TO BE PERMITTED ASTYPE1 GREASE HOODS, OR TYPE
 II HEAT HOODS- SEE SECTION 507.1.
  
 4) M-3.0: PLEASE SHOW THE ENTIRE EXHAUST DUCT RUNS FOR
 HOODS 1 & 2 FROM HOOD OUTLET TO ROOF TERMINATION.
 INDICATE THE TYPE AND SIZES OF EXHAUST DUCTWORK.
  
 5) PROVIDE A ROOF PLAN SHOWING THE LOCATIONS OF THE
 EXHAUST FANS AND THE REQUIRED MINIMUM CLEARANCES FROM
 EXHAUST OUTLETS TO MECHANICAL OR GRAVITY AIR INTAKES.
 PLEASE INCLUDE AN ELEVATION VIEW WHICH SHOWS THE HEIGHT
 OF THE EXHAUST OUTLETS ABOVE THE FINISH ROOF,
  
 6) PROVIDE COMPLETE WINDLOAD ENGINEERING FOR
 INSTALLATION OF THE ROOF EXHAUST FANS INCLUDING THE
 STRUCTURAL ROOF OPENING, THE CURB ATTACHMENT TO THE
 STRUCTURE, AND THE RTU ATTACHMENT TO THE CURB- SECTION
 301.15
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  