Plan Review Details - Permit 18030381
Plan Review Stops For Permit 18030381
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2018-05-16 Cont ID  
Sent By shill Date 2018-05-16 Time 17:43 Rev Time 0.00
Received By shill Date 2018-05-16 Time 17:43 Sent To  
Notes
2018-05-16 17:43:36****PROVISOS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. SERVICE COUNTER, CONDIMENT COUNTER AND RETAIL
 MERCHANDISE COUNTER TO COMPLY WITH FBC ACCESSIBILITY
 904. SUBJECT TO FIELD INSPECTOR'S DISCRETION, A
 REVISION (WITH APPLICABLE FEES) MAY BE REQUIRED.
  
 2. PRODUCT APPROVALS ARE TO BE REVIEWED BY DESIGNER OF
 RECORD AND SUBMITTED AND REVIEWED BY BUILDING DIVISION
 PRIOR TO INSTALLATION.
  
 3. SIGNS AND AWNINGS REQUIRE SEPARATE PERMITS.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2018-04-28 Cont ID  
Sent By shill Date 2018-04-28 Time 14:29 Rev Time 0.00
Received By shill Date 2018-04-28 Time 11:44 Sent To  
Notes
2018-04-28 14:29:21****PROVISOS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. SERVICE COUNTER, CONDIMENT COUNTER AND RETAIL
 MERCHANDISE COUNTER TO COMPLY WITH FBC ACCESSIBILITY
 904. SUBJECT TO FIELD INSPECTOR'S DISCRETION, A
 REVISION (WITH APPLICABLE FEES) MAY BE REQUIRED.
  
 2. PRODUCT APPROVALS ARE TO BE REVIEWED BY DESIGNER OF
 RECORD AND SUBMITTED AND REVIEWED BY BUILDING DIVISION
 PRIOR TO INSTALLATION.
  
 3. SIGNS AND AWNINGS REQUIRE SEPARATE PERMITS.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-03-13 Cont ID  
Sent By aclange Date 2018-03-13 Time 11:01 Rev Time 0.00
Received By aclange Date 2018-03-12 Time 14:14 Sent To  
Notes
2018-03-13 11:01:45****PLAN REVIEW COMMENTS****
  
 ART LANGE BUILDING PLANS EXAMINER
  
 DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS STREET
 WEST PALM BEACH, FL 33402
 561-805-6718 [email protected]
  
 FBC FLORIDA BUILDING CODE 2017 6TH EDITION W/2010 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 1. ON PAGE A 1.0 THE WALL TYPES A, B, C AND D SHOW WOOD
 AS AN OPTION IN THE FRAMING DETAIL. THE CONSTRUCTION
 TYPE IS IIB. UPDATE THIS TO METAL FRAMING OR FIRE
 RETARDANT TREATED WOOD.
  
 COMBUSTIBLE MATERIAL IN TYPE I AND II CONSTRUCTION
  
 FBC 603.1 ALLOWABLE MATERIALS.
 COMBUSTIBLE MATERIALS SHALL BE PERMITTED IN BUILDINGS
 OF TYPE I OR II CONSTRUCTION IN THE FOLLOWING
 APPLICATIONS AND IN ACCORDANCE WITH SECTIONS 603.1.1
 THROUGH 603.1.3:
 1. FIRE-RETARDANT-TREATED WOOD SHALL BE PERMITTED IN:
 1.1. NONBEARING PARTITIONS WHERE THE REQUIRED
 FIRE-RESISTANCE RATING IS 2 HOURS OR LESS.
  
 2. THE OFFICE / TRAINING ROOM DIMENSIONS ARE TOO SMALL.
  
 FBC 1208.1 MINIMUM ROOM WIDTHS.
 HABITABLE SPACES, OTHER THAN A KITCHEN, SHALL BE NOT
 LESS THAN 7 FEET (2134 MM) IN ANY PLAN DIMENSION.
  
 3. ACCESSIBILITY
  
 A. THE REAR DOOR DOES NOT HAVE A MINIMUM OF 12?
 CLEARANCE ON THE PUSH SIDE OF THE DOOR.
  
 404.2.4.1 SWINGING DOORS AND GATES.
 SWINGING DOORS AND GATES SHALL HAVE MANEUVERING
 CLEARANCES COMPLYING WITH TABLE 404.2.4.1. DETAIL (C).
  
 B. PROVIDE ELEVATIONS TO SHOW ACCESSIBILITY AT THE
 FRONT SERVICE COUNTER, CONDIMENT COUNTER AND RETAIL
 MERCHANDISE COUNTER AREA.
  
 904 CHECK-OUT AISLES AND SALES AND SERVICE COUNTERS
 CHECK-OUT AISLES AND SALES AND SERVICE COUNTERS SHALL
 COMPLY WITH THE APPLICABLE REQUIREMENTS OF 904.
  
 C. OUTDOOR SEATING NOT SHOWN. IF SEATING WILL BE
 PROVIDED SHOW THIS ON THE PLAN AS WELL.
 FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 4. PROVIDE PRODUCT APPROVALS FOR DRIVE UP WINDOW AND
 ADJACENT STORE FRONT GLASS.
  
 FBC 107.3.4 - PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
 ALTERNATIVELY YOU CAN SUBMIT THESE LATER AS A DEFERRED
 SUBMITTAL BY LISTING THEM ON THE PAGE T 1.0.
  
 FBC 107.3.4.2 DEFERRED SUBMITTALS. FOR THE PURPOSES OF
 THIS SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE
 PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE
 TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO
 THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD.
  
 DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR
 APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED
 DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST
 THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS
 FOR REVIEW BY THE BUILDING OFFICIAL.
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD
 THEM TO THE BUILDING OFFICIAL WITH A NOTATION
 INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL
 ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING
 OFFICIAL.
  
 5. NOTE: SIGNS AND AWNINGS REQUIRE A SEPARATE PERMIT.
  
  
  
 WHEN RESUBMITTING, PLEASE COMPLETE A RESUBMITTAL FORM:
  
 HTTP://WPB.ORG/DEVELOPMENT/WPCONTENT/UPLOADS/SITES/33/2
 013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 THIS FORM IS ALSO AVAILABLE AT THE BUILDING DIVISION.
 WHEN RESUBMITTING, SWAP OUT SHEETS WHICH HAVE CHANGED
 SO THAT THERE ARE TWO COMPLETE, COLLATED SETS OF PLANS
 READY FOR PERMIT ISSUANCE. OLD SHEETS ARE TO BE
 RETAINED IN THE PERMIT APPLICATION PACKAGE (SEPARATE
 FROM THE PERMIT SETS) AND MARKED *OLD SHEETS* OR
 *VOID*. PLEASE KEEP BOTH SETS OF OLD VOIDED SHEETS IN
 THE PERMIT PACKAGE.
  
 A RESPONSE LETTER INDICATING HOW EACH ITEM WAS
 ADDRESSED WILL HELP TO EXPEDITE PLAN REVIEW.
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2018-05-18 Cont ID  
Sent By skennedy Date 2018-05-18 Time 12:57 Rev Time 0.00
Received By skennedy Date 2018-05-18 Time 12:57 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2018-04-27 Cont ID  
Sent By jpearson Date 2018-04-27 Time 08:39 Rev Time 0.00
Received By jpearson Date 2018-04-26 Time 13:27 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-03-23 Cont ID  
Sent By jpearson Date 2018-03-23 Time 15:06 Rev Time 0.00
Received By jpearson Date 2018-03-23 Time 12:16 Sent To I
Notes
2018-03-23 15:06:33CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE LOAD CALCULATION FOR SERVICE, INCLUDE ALL
 LOADS TO CONFIRM CAPACITY OF SERVICE IS ADEQUATE. BASED
 ON THE INFORMATION PROVIDED CURRENTLY, B? IS SHOWN WITH
 A TOTAL OF 413 AMPS, WHICH EXCEEDS THE CAPACITY OF THE
 WIRE AND OF THE DISCONNECT. PROVIDE CORRECTION AS
 NEEDED. NEC 215.2, 220, 408.30
 2. ALL RECEPTACLE OUTLETS IN KITCHEN/PREP AREAS REQUIRE
 GFCI PROTECTION, NOT JUST THOSE THAT ARE COUNTERTOP
 RECEPTACLES. PROVIDE CORRECTION. NEC 210.8
 3. PROVIDE BLOCK NOTE STATING SIGNS REQUIRE A SEPARATE
 PERMIT. FBC 107.2.1
 4. PROVIDE CHART OF INTERIOR LIGHTING POWER ALLOWANCES
 EXPRESSED IN WATTAGE PER THE FBC ENERGY CODE IN
 RELATION TO THE WATTAGE OF THE CONNECTED INTERIOR
 LIGHTING PROPOSED TO COMPLY WITH CODE. FBC EC C405.4.2
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2018-05-11 Cont ID  
Sent By scaldero Date 2018-05-11 Time 11:23 Rev Time 0.00
Received By scaldero Date 2018-05-11 Time 11:23 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2018-04-16 Cont ID  
Sent By scaldero Date 2018-04-16 Time 13:04 Rev Time 0.00
Received By scaldero Date 2018-04-16 Time 13:02 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2018-03-12 Cont ID  
Sent By scaldero Date 2018-03-12 Time 12:44 Rev Time 0.00
Received By scaldero Date 2018-03-12 Time 12:35 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2018-05-18 Cont ID  
Sent By skennedy Date 2018-05-18 Time 12:57 Rev Time 0.00
Received By skennedy Date 2018-05-04 Time 14:05 Sent To  
Notes
2018-05-16 17:44:06TO STEVE KENNEDY'S DESK
  
2018-05-07 14:05:38C25

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-04-28 Cont ID  
Sent By shill Date 2018-04-28 Time 14:29 Rev Time 0.00
Received By shill Date 2018-04-11 Time 13:27 Sent To  
Notes
2018-04-12 13:28:06C25

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2018-03-23 Time   Rev Time 0.00
Received By lmarchan Date 2018-03-08 Time 13:34 Sent To  
Notes
2018-03-09 13:34:53C20

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2018-03-13 Cont ID  
Sent By aclange Date 2018-03-13 Time 10:59 Rev Time 0.00
Received By aclange Date 2018-03-13 Time 10:59 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2018-05-15 Cont ID  
Sent By ccole Date 2018-05-15 Time 08:27 Rev Time 0.00
Received By ccole Date 2018-05-14 Time 17:48 Sent To  
Notes
2018-05-15 08:30:03MECHANICAL PROVISOS:
  
 1) SEPARATE PERMITS REQUIRED FOR THE OVEN HOODS, AND
 THE WALKIN COOLER AND FREEZER.
  
 CCOLE- 5/15/18

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2018-04-24 Cont ID  
Sent By ccole Date 2018-04-24 Time 08:20 Rev Time 0.00
Received By ccole Date 2018-04-23 Time 17:22 Sent To  
Notes
2018-04-24 08:28:222ND REVIEW FBC-2017 MECHANICAL , ENERGY CONSERVATION
 CODES, WEST PALM BEACH AMENDMENTS TO THE FBC-17
 PERMIT #18030381
 4/24/18
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE EQUIPMENT IDENTIFICATION NUMBERS ON THE KITCHEN
 PLANS ARE TOO SMALL AND TOO FAINT TO READ OR TO BE
 SCANNED FOR PUBLIC RECORD. PLEASE PROVIDE CLEAR LEGIBLE
 PLANS PER SECTION 107.2.1 WPB AMENDMENTS.
  
 2) IF THE OVENS AND OTHER COOKING EQUIPMENT UNDER THE
 HOODS ARE GAS-FIRED, THEN AS PREVIOUSLY REQUESTED,
 PROVIDE COMBUSTION AIR CALCULATIONS PER SECTION 304
 FBC-17 FUEL GAS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2018-03-19 Cont ID  
Sent By ccole Date 2018-03-19 Time 10:53 Rev Time 0.00
Received By ccole Date 2018-03-19 Time 10:27 Sent To  
Notes
2018-03-19 11:37:451ST REVIEW FBC-2017 MECHANICAL , ENERGY CONSERVATION
 CODES, WEST PALM BEACH AMENDMENTS TO THE FBC-17
 PERMIT #18030381
 3/19/18
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET M-1.0: THE PLAN SHOWS RECIRCULATION OF AIR
 FROM THE KITCHEN INTO THE RETAIL SALES/SEATING AREA
 WHICH IS PROHIBITED PER TABLE 403.1.1 FOOTNOTE B.
  
 2) M-2.0: THE AIR BALANCE SCHEDULE DOES NOT PROVIDE
 CALCULATIONS FOR THE REQUIRED REPLACEMENT AIR FOR THE
 KITCHEN EXHAUST SYSTEMS- SEE SECTION 508.1.2.
  
 3) ADVISORY: THE KITCHEN EXHAUST HOODS ARE UNDER
 SEPARATE PERMITS HOWEVER IT IS NECESSARY THAT THE MAIN
 PLAN IS BEING DESIGNED IN COMPLIANCE WITH SECTION
 508.1.1 MAKEUP AIR TEMPERATURE- FBC-17 MECHANICAL, AND
 SECTION C403.2.8 FBC-17 ENERGY CONSERVATION. PLEASE
 SHOW COMPLIANCE.
  
 508.1.1 MAKEUP AIR TEMPERATURE.
 THE TEMPERATURE DIFFERENTIAL BETWEEN MAKEUP AIR AND THE
 AIR IN THE CONDITIONED SPACE SHALL NOT EXCEED 10?F
 (6?C) EXCEPT WHERE THE ADDED HEATING AND COOLING LOADS
 OF THE MAKEUP AIR DO NOT EXCEED THE CAPACITY OF THE
 HVAC SYSTEM.
  
 C403.2.8 KITCHEN EXHAUST SYSTEMS.
 REPLACEMENT AIR INTRODUCED DIRECTLY INTO THE EXHAUST
 HOOD CAVITY SHALL NOT BE GREATER THAN 10 PERCENT OF THE
 HOOD EXHAUST AIRFLOW RATE. CONDITIONED SUPPLY AIR
 DELIVERED TO ANY SPACE SHALL NOT EXCEED THE GREATER OF
 THE FOLLOWING:
 1.THE VENTILATION RATE REQUIRED TO MEET THE SPACE
 HEATING OR COOLING LOAD.
 2.THE HOOD EXHAUST FLOW MINUS THE AVAILABLE TRANSFER
 AIR FROM ADJACENT SPACE WHERE AVAILABLE TRANSFER AIR IS
 CONSIDERED THAT PORTION OF OUTDOOR VENTILATION AIR NOT
 REQUIRED TO SATISFY OTHER EXHAUST NEEDS, SUCH AS
 RESTROOMS, AND NOT REQUIRED TO MAINTAIN PRESSURIZATION
 OF ADJACENT SPACES.
  
 4) PROVIDE COMBUSTION AIR CALCULATIONS FOR THE
 GAS-FIRED COOKING APPLIANCES IN ACCORDANCE WITH SECTION
 304 FBC-17 FUEL GAS. PLEASE INDICATE ON THE PLAN HOW
 THE COMBUSTION AIR IS BEING PROVIDED.
  
 5) SHEETS K-1.0- K-4.0: PLEASE PROVIDE ENLARGED PLANS
 FOR THE TWO KITCHEN COOKING LINES SO THAT THE
 APPLIANCES UNDER THE HOODS ARE EASILY IDENTIFIED.
 PLEASE NOTE THE EQUIPMENT LISTS IS INDICATING A FRYER
 WHICH REQUIRES A GREASE HOOD.
  
 6) PROVIDE COMPLETE WINDLOAD ENGINEERING FOR
 INSTALLATION OF THE RTU INCLUDING THE STRUCTURAL ROOF
 OPENING, THE CURB ATTACHMENT TO THE STRUCTURE, AND THE
 RTU ATTACHMENT TO THE CURB- SECTION 301.15
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2018-05-18 Cont ID  
Sent By skennedy Date 2018-05-18 Time 12:57 Rev Time 0.00
Received By skennedy Date 2018-05-18 Time 12:57 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2018-04-23 Cont ID  
Sent By gjohnson Date 2018-04-23 Time 15:20 Rev Time 0.00
Received By gjohnson Date 2018-04-21 Time 11:00 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2018-03-22 Cont ID  
Sent By gjohnson Date 2018-03-22 Time 15:16 Rev Time 0.00
Received By gjohnson Date 2018-03-22 Time 12:46 Sent To  
Notes
2018-03-22 15:55:391ST REVIEW: FBC 2017 6TH EDITION
  
 PLUMBING COMMENTS:
  
 1. SHT. T-1.0 UNDER DESIGN CODES ACCESSIBILITY SHALL
 COMPLY WITH FBC ACC 6TH EDITION 2017 NOT THE 5TH
 EDITION. PLEASE CORRECT ON PLAN SHEET. PER WPB AMEND TO
 FBC 107.2.1
  
 2. PLEASE SHOW THE DIMENSIONS ON THE CLEAR FLOOR SPACE
 FOR THE TOILET AND LAVATORY IN THE ACCESSIBLE
 BATHROOMS. PER FBC ACC 604.3.1, 606.2
  
 3. SHT. K-1.0-4.0 THERE ARE 2 EXTRA BATHROOMS SHOWN ON
 THE BACK WALL OF THE SPACE NEXT TO THE DOOR THEY ARE
 NOT SHOWN ON ANY OTHER SHEETS PLEASE CLARIFY. PER WPB
 AMEND TO FBC 107.2.1
  
 4. THE EQUIPMENT PLAN IS UNCLEAR AND NEEDS TO BE
 ENLARGED TO READ IT CLEARLY TO DETERMINE CODE
 COMPLIANCE THE SCALE IS REQUIRED TO BE 1/8" FT . PER
 WPB AMEND TO FBC 107.2.1.3
  
 5. PLEASE PROVIDE SIZING CALCULATIONS ON THE EXISTING
 GREASE INTERCEPTOR TO INCLUDE EXISTING LOAD AND THE NEW
 LOAD TO DETERMINE IF EXISTING IS LARGE ENOUGH TO HANDLE
 THE ADDITIONAL LOAD. PER FBC PL 1003.2
  
 6. WHO IS RESPONSIBLE FOR THE MAINTENANCE OF THE
 EXISTING GREASE INTERCEPTOR AND HOW OFTEN IS IT PUMPED
 OUT. PROVIDE LETTER FROM PROPERTY OWNER. PER WPB AMEND
 TO FBC 107.2.1
  
 7. PRIOR TO FINAL INSPECTION THE EXISTING INTERCEPTOR
 WILL NEED TO BE CERTIFIED BY UTILITIES DEPARTMENT TO BE
 IN GOOD WORKING ORDER PLEASE CONTACT JEFFERY ODOMS WPB
 UTILITIES PH 561-822-2172
  
 8. SHT. P-1.1 NOTE #4 THE CIVIL SHEET SHOWING LOCATION
 AND SIZE OF THE EXISTING GREASE INTERCEPTOR IS NOT IN
 THE PLAN SET PLEASE CLARIFY. PER WPB AMEND TO FBC
 107.2.1
  
 9. SHT. P 4.0 THERE IS A NOTE AT THE BOTTOM OF THE PAGE
 REQUIERING A BOOSTER PUMP ON THE FILTER SYSTEM PLEASE
 SHOW ON RISER DETAIL AND PROVIDE MANUFACTURE
 SPECIFICATIONS. PER WPB AMEND TO FBC 107.2.1
  
 10. SHT P-0.1 NOTE #1 THE CURRENT CODE IS THE FBC PL
 6TH EDITION 2017 PLEASE CORRECT ON PLAN. PER WPB AMEND
 TO FBC 107.2.1
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop Z ZONING
Rev No 2 Status P Date   Cont ID  
Sent By   Date 2018-04-19 Time   Rev Time 0.00
Received By pgreilic Date 2018-04-19 Time 14:26 Sent To  
Notes
2018-04-19 14:26:29THE FOLLOWING CONDITIONS APPLY TO THIS APPROVAL:
  
 1.) PRIOR TO ISSUANCE OF CERTIFICATE OF OCCUPANCY,
 APPLICANT MUST REPLACE TWO (2) MISSING GREEN BUTTONWOOD
 TREES IN THE LANDSCAPE BUFFER ALONG THE SOUTHERN
 PROPERTY LINE ADJACENT TO THE DRIVE-THRU.
  
  
 PAUL GREILICH, SENIOR PLANNER
 561-822-1443
 [email protected]

Review Stop Z ZONING
Rev No 1 Status P Date   Cont ID  
Sent By PG Date 2018-03-14 Time   Rev Time 0.00
Received By pgreilic Date 2018-03-14 Time 12:13 Sent To  
Notes
2018-03-14 12:13:46THE FOLLOWING CONDITIONS APPLY TO THIS APPROVAL:
  
 1.) PRIOR TO ISSUANCE OF CERTIFICATE OF OCCUPANCY,
 APPLICANT MUST REPLACE TWO (2) MISSING GREEN BUTTONWOOD
 TREES IN THE LANDSCAPE BUFFER ALONG THE SOUTHERN
 PROPERTY LINE ADJACENT TO THE DRIVE-THRU.
  
  
 PAUL GREILICH, SENIOR PLANNER
 561-822-1443
 [email protected]