| 2018-03-13 11:01:45 | ****PLAN REVIEW COMMENTS**** |
| | |
| | ART LANGE BUILDING PLANS EXAMINER |
| | |
| | DEVELOPMENT SERVICES DEPARTMENT |
| | 401 CLEMATIS STREET |
| | WEST PALM BEACH, FL 33402 |
| | 561-805-6718 [email protected] |
| | |
| | FBC FLORIDA BUILDING CODE 2017 6TH EDITION W/2010 WEST |
| | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| | CHAPTER 1 ADMINISTRATION |
| | |
| | 1. ON PAGE A 1.0 THE WALL TYPES A, B, C AND D SHOW WOOD |
| | AS AN OPTION IN THE FRAMING DETAIL. THE CONSTRUCTION |
| | TYPE IS IIB. UPDATE THIS TO METAL FRAMING OR FIRE |
| | RETARDANT TREATED WOOD. |
| | |
| | COMBUSTIBLE MATERIAL IN TYPE I AND II CONSTRUCTION |
| | |
| | FBC 603.1 ALLOWABLE MATERIALS. |
| | COMBUSTIBLE MATERIALS SHALL BE PERMITTED IN BUILDINGS |
| | OF TYPE I OR II CONSTRUCTION IN THE FOLLOWING |
| | APPLICATIONS AND IN ACCORDANCE WITH SECTIONS 603.1.1 |
| | THROUGH 603.1.3: |
| | 1. FIRE-RETARDANT-TREATED WOOD SHALL BE PERMITTED IN: |
| | 1.1. NONBEARING PARTITIONS WHERE THE REQUIRED |
| | FIRE-RESISTANCE RATING IS 2 HOURS OR LESS. |
| | |
| | 2. THE OFFICE / TRAINING ROOM DIMENSIONS ARE TOO SMALL. |
| | |
| | FBC 1208.1 MINIMUM ROOM WIDTHS. |
| | HABITABLE SPACES, OTHER THAN A KITCHEN, SHALL BE NOT |
| | LESS THAN 7 FEET (2134 MM) IN ANY PLAN DIMENSION. |
| | |
| | 3. ACCESSIBILITY |
| | |
| | A. THE REAR DOOR DOES NOT HAVE A MINIMUM OF 12? |
| | CLEARANCE ON THE PUSH SIDE OF THE DOOR. |
| | |
| | 404.2.4.1 SWINGING DOORS AND GATES. |
| | SWINGING DOORS AND GATES SHALL HAVE MANEUVERING |
| | CLEARANCES COMPLYING WITH TABLE 404.2.4.1. DETAIL (C). |
| | |
| | B. PROVIDE ELEVATIONS TO SHOW ACCESSIBILITY AT THE |
| | FRONT SERVICE COUNTER, CONDIMENT COUNTER AND RETAIL |
| | MERCHANDISE COUNTER AREA. |
| | |
| | 904 CHECK-OUT AISLES AND SALES AND SERVICE COUNTERS |
| | CHECK-OUT AISLES AND SALES AND SERVICE COUNTERS SHALL |
| | COMPLY WITH THE APPLICABLE REQUIREMENTS OF 904. |
| | |
| | C. OUTDOOR SEATING NOT SHOWN. IF SEATING WILL BE |
| | PROVIDED SHOW THIS ON THE PLAN AS WELL. |
| | FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | 4. PROVIDE PRODUCT APPROVALS FOR DRIVE UP WINDOW AND |
| | ADJACENT STORE FRONT GLASS. |
| | |
| | FBC 107.3.4 - PROVIDE PRODUCT APPROVALS FOR THOSE |
| | PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED |
| | AND APPROVED IN WRITING BY THE DESIGNER OF RECORD. |
| | ALTERNATIVELY YOU CAN SUBMIT THESE LATER AS A DEFERRED |
| | SUBMITTAL BY LISTING THEM ON THE PAGE T 1.0. |
| | |
| | FBC 107.3.4.2 DEFERRED SUBMITTALS. FOR THE PURPOSES OF |
| | THIS SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE |
| | PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE |
| | TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO |
| | THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD. |
| | |
| | DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR |
| | APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED |
| | DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST |
| | THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS |
| | FOR REVIEW BY THE BUILDING OFFICIAL. |
| | DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE |
| | SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN |
| | RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD |
| | THEM TO THE BUILDING OFFICIAL WITH A NOTATION |
| | INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE |
| | BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO |
| | THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL |
| | ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED |
| | SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING |
| | OFFICIAL. |
| | |
| | 5. NOTE: SIGNS AND AWNINGS REQUIRE A SEPARATE PERMIT. |
| | |
| | |
| | |
| | WHEN RESUBMITTING, PLEASE COMPLETE A RESUBMITTAL FORM: |
| | |
| | HTTP://WPB.ORG/DEVELOPMENT/WPCONTENT/UPLOADS/SITES/33/2 |
| | 013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF |
| | |
| | THIS FORM IS ALSO AVAILABLE AT THE BUILDING DIVISION. |
| | WHEN RESUBMITTING, SWAP OUT SHEETS WHICH HAVE CHANGED |
| | SO THAT THERE ARE TWO COMPLETE, COLLATED SETS OF PLANS |
| | READY FOR PERMIT ISSUANCE. OLD SHEETS ARE TO BE |
| | RETAINED IN THE PERMIT APPLICATION PACKAGE (SEPARATE |
| | FROM THE PERMIT SETS) AND MARKED *OLD SHEETS* OR |
| | *VOID*. PLEASE KEEP BOTH SETS OF OLD VOIDED SHEETS IN |
| | THE PERMIT PACKAGE. |
| | |
| | A RESPONSE LETTER INDICATING HOW EACH ITEM WAS |
| | ADDRESSED WILL HELP TO EXPEDITE PLAN REVIEW. |
| | |