Plan Review Details - Permit 18030356
Plan Review Stops For Permit 18030356
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2018-05-02 Cont ID  
Sent By shill Date 2018-05-02 Time 16:06 Rev Time 0.00
Received By shill Date 2018-05-02 Time 14:47 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date   Cont ID  
Sent By   Date 2018-03-15 Time 09:58 Rev Time 0.00
Received By jwitmer Date 2018-03-15 Time 08:47 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2018-04-10 Cont ID  
Sent By jpearson Date 2018-04-10 Time 15:18 Rev Time 0.00
Received By jpearson Date 2018-04-10 Time 14:41 Sent To I
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2018-04-23 Cont ID  
Sent By scaldero Date 2018-04-23 Time 11:40 Rev Time 0.00
Received By scaldero Date 2018-04-23 Time 11:40 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2018-03-12 Cont ID  
Sent By scaldero Date 2018-03-12 Time 12:33 Rev Time 0.00
Received By scaldero Date 2018-03-12 Time 12:26 Sent To  
Notes
2018-03-12 12:33:41PERMIT #18030356
 REVIEW COMMENTS - FIRE DEPARTMENT
  
  
 1) SEPARATE PLANS AND PERMITS ARE REQUIRED FOR THE
 INSTALLATION OR MODIFICATION OF THE FIRE SPRINKLER
 SYSTEM AND/OR FIRE ALARM SYSTEM.
  
 SUE ELLEN CALDERON
 ASSISTANT FIRE MARSHAL
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-05-02 Cont ID  
Sent By shill Date 2018-05-02 Time 16:06 Rev Time 0.00
Received By shill Date 2018-04-17 Time 14:44 Sent To  
Notes
2018-04-18 14:44:25C22

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2018-04-10 Time   Rev Time 0.00
Received By lmarchan Date 2018-03-08 Time 13:45 Sent To  
Notes
2018-03-09 13:45:22C22

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2018-03-15 Cont ID  
Sent By jwitmer Date 2018-03-15 Time 13:23 Rev Time 0.00
Received By jwitmer Date 2018-03-15 Time 08:47 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2018-04-09 Cont ID  
Sent By ccole Date 2018-04-09 Time 17:21 Rev Time 0.00
Received By ccole Date 2018-04-09 Time 16:45 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2018-05-01 Cont ID  
Sent By tklarge Date 2018-05-01 Time 14:53 Rev Time 0.00
Received By tklarge Date 2018-05-01 Time 13:20 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2018-03-28 Cont ID  
Sent By tklarge Date 2018-03-28 Time 06:52 Rev Time 0.00
Received By tklarge Date 2018-03-28 Time 04:59 Sent To  
Notes
2018-03-28 06:52:351) SHT. A0.00 - BUILDING CODE CHECKLIST - THIS PROJECT
 SHALL BE DESIGNED UNDER THE 2017 FBC, NOT THE 2014 AS
 NOTED ON THE PLANS.
 2) ROOM # 953 - GALLEY - SHT.A4.10 - THE BREAK ROOM
 SINK SHALL COMPLY WITH THE 2017FBC-ACCESS. SEC.606.3.
 THE TOP OF THE COUNTER FROM THE FINISH FLOOR SHALL BE A
 MAXIMUM OF 34 INCHES. SHOW THIS ON THE PLAN.WPB AMEND.
 TO FBC SEC. 107.2.1.
 3) SUBMIT A SANITARY RISER FOR THE GALLEY SINK,
 DISHWASHER.
 4) SUBMIT A WATER RISER FOR THE GALLEY SINK,
 DISHWASHER, REFRIGERATOR ( IF IT HAS A WATER OR ICE
 DISPENSER), THE CCOFFEE MAKERS & WATER/ICE DISPENSER.)
 5) THE REFRIGERATOR, COFFEE MAKERS AND ICE/WATER
 DISPENSER SHALL BE EQUIPPED WITH BACKFLOW PREVENTERS
 PER 2017 FBC-PLUMBING SECS. 608.3, 608.16.10.
 6) AIR ARRESTORS SHALL BE INSTALLED ON ALL QUICK
 CLOSING VALVES PER 2017 FBC-PLUMBING SEC.604.9
 (DISHWASHER, REFRIGERATOR, WATER/ICE DISPENSER.
 7) INDICATE THE LEVEL OF ALTERATION ON THE PLAN IN
 ACCORDANCE WITH THE 2017 FBC-EXISTING BUILDING CODE
 SEC.301.1.
 8) THE GALLEY SINK SHALL BE SUPPLIED WITH HOT WATER.
 2017 FBC-PLUMBING SEC. 607.1.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  
  
  