| Plan Review Stops For Permit 18030335 |
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2018-03-23 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2018-03-23 |
Time |
13:03 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2018-03-23 |
Time |
13:03 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
2018-06-22 |
Time |
|
Rev Time |
0.00 |
| Received By |
cpuell |
Date |
2018-06-22 |
Time |
08:18 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
2018-06-21 |
Time |
|
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2018-06-04 |
Time |
16:32 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
2018-05-14 |
Time |
|
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2018-04-25 |
Time |
07:54 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2018-03-23 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2018-03-23 |
Time |
13:12 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2018-03-08 |
Time |
15:16 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
4 |
Status |
P |
Date |
2018-06-22 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2018-06-22 |
Time |
16:40 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2018-06-22 |
Time |
16:40 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
F |
Date |
2018-06-21 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2018-06-21 |
Time |
09:16 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2018-06-21 |
Time |
08:05 |
Sent To |
I |
|
| Notes |
| 2018-06-21 09:41:22 | 4TH REVIEW FBC-2014 MECHANICAL | | | PERMIT #18030335 | | | 5/14/18 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) SHEET M4.01A: THE MODEL NUMBERS LISTED IN THE FA | | | SUBMITTALS FOR SPF-1-1 AND SPF-1-2 DO NOT MATCH THE | | | MODEL NUMBERS IN THE SCHEDULE- PLEASE CORRECT. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE | | | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND | | | KEEP THEM WITH THE SUBMITTALS. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2018-05-14 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2018-05-14 |
Time |
16:52 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2018-05-14 |
Time |
16:52 |
Sent To |
|
|
| Notes |
| 2018-05-14 16:53:25 | 3RD REVIEW FBC-2014 MECHANICAL | | | PERMIT #18030335 | | | 5/14/18 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) AS PREVIOUSLY NOTED, ALL OF THE SMOKE CONTROL FANS | | | MUST BE EQUIPPED WITH A MINIMUM OF TWO BELTS PER | | | SECTION 909.10.5. FBC-10, AND THE SMOKE CONTROL | | | RATIONAL ANALYSIS FOR THE PROJECT BY JOSEPH E. HAUF P.E | | | (SEE FANS- PAGE 21). THE LETTER FROM TOM BARROW COMPANY | | | TO KAST CONSTRUCTION THAT WAS SUBMITTED TO THE BUILDING | | | DEPARTMENT STATES THAT ALL OF THE SMOKE CONTROL FANS | | | | | | ARE UL LISTED AND LABELED FOR SMOKE CONTROL, HOWEVER | | | THIS IS NOT THE ISSUE IN DISPUTE. THE ISSUE IS THE | | | LETTER ALSO STATES THAT THE SMOKE CONTROL FANS GEF-1-1, | | | GEF-1-2, SEF-1-1, LPF-1-1, SPF-1-1, SPF-R-1, AND | | | SPF-R-2 ARE EQUIPPED WITH 1 BELT ONLY, AND THEREFORE | | | ARE NON-COMPLIANT. DUE TO THE FACT THAT THIS IS THE 3RD | | | REVIEW OF THE PROJECT, THE ISSUE WAS REFERRED TO ROBERT | | | BROWN | | | | | | BUILDING OFFICIAL FOR WPB. HIS JUDGEMENT IS THAT THE | | | TWO-BELT MINIMUM REQUIREMENT WILLL BE ENFORCED. AS A | | | RESULT THESE COMMENTS HAVE BEEN WRITTEN, AND A PHONE | | | CALL WAS PLACED TO TWR ENGINEERS TO ALERT THEM. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE | | | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND | | | KEEP THEM WITH THE SUBMITTALS. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2018-03-19 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2018-03-19 |
Time |
14:10 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2018-03-19 |
Time |
14:10 |
Sent To |
|
|
| Notes |
| 2018-03-19 14:17:14 | 1ST REVIEW FBC-2017 MECHANICAL | | | PERMIT #18030335 | | | 3/19/18 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) PROVIDE AN UPDATED PRODUCT SUBMITTAL PACKAGE THAT | | | INCLUDES THE RUSHKIN LOUVER NOA #16-1107.03, AND THE | | | NEW SMOKE CONTROL FANS IN THE BUILDING AND THE PARKING | | | GARAGE. ALL SUBMITTALS SHALL HAVE SHOP DRAWINGS REVIEW | | | AND APPPROVAL STAMPS BY THE EOR. PLEASE NOTE THAT THE | | | PREVIOUS REVIEW COMMENTS FOR FAN SUBMITTALS UNDER | | | #16100030 (7/21/17) STILL EXIST. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE | | | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND | | | KEEP THEM WITH THE SUBMITTALS. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
3 |
Status |
P |
Date |
2018-04-24 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2018-04-24 |
Time |
11:38 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2018-04-24 |
Time |
11:38 |
Sent To |
|
|
| Notes |
| 2018-04-24 11:39:37 | SIGNED & SEALED ORIGINAL PLANS ROUTED TO RECORDS | | | MECHANICAL REVIEW FAILED 1ST REVIEW, BUT DOCUMENTS TO | | | BE SUBMITTED ARE NOT SIGNED & SEALED SO AN ADDITIONAL | | | SIGNATURE REVIEW SHOLD NOT BE REQUIRED | | | | | | |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
2 |
Status |
F |
Date |
2018-04-12 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2018-04-12 |
Time |
13:02 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2018-04-06 |
Time |
16:10 |
Sent To |
|
|
| Notes |
| 2018-04-12 13:04:35 | PEDDS INCOMPLETE. APPLICANT TO PROVIDE ORIGINAL SIGNED | | | AND SEALED DOCUMENTS. | | | | | | | | 2018-04-06 16:11:04 | GIVEN TO SHILL |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
1 |
Status |
F |
Date |
2018-03-23 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2018-03-23 |
Time |
13:11 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2018-03-23 |
Time |
13:11 |
Sent To |
|
|
| Notes |
| 2018-03-23 13:12:34 | ELECTRICAL PLANS NOT ELECTRONICALLY SIGNED JLEAHY | | | 3/23/18 | | 2018-03-19 15:24:37 | MECH PLANS NOT ELECRONICALLY SIGNED AND SEALED. | | | CCOLE- 3/19/18 |
|
|