| 2018-03-09 11:43:03 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | |
| | 1) THE DDCA IS NOT LOCATED IN A POSITION THAT MEETS THE |
| | REQUIREMENTS OF NFPA 24. |
| | |
| | |
| | |
| | 6.2.10* ALL CONTROL VALVES SHALL BE LOCATED WHERE |
| | ACCESSIBLE AND |
| | FREE OF OBSTRUCTIONS. |
| | |
| | 6.2.11 ALL CONNECTIONS TO PRIVATE FIRE SERVICE MAINS |
| | FOR FIRE |
| | PROTECTION SYSTEMS SHALL BE ARRANGED IN ACCORDANCE WITH |
| | ONE |
| | OF THE FOLLOWING SO THAT THEY CAN BE ISOLATED: |
| | (1)*A POST INDICATOR VALVE INSTALLED NOT LESS THAN 40 |
| | FT (12 M) |
| | FROM THE BUILDING |
| | (A) FOR BUILDINGS LESS THAN 40 FT (12 M) IN HEIGHT, A |
| | POST |
| | INDICATOR VALVE SHALL BE PERMITTED TO BE INSTALLED |
| | CLOSER THAN 40 FT (12 M) BUT AT LEAST AS FAR FROM THE |
| | BUILDING AS THE HEIGHT OF THE WALL FACING THE POST |
| | INDICATOR |
| | VALVE. |
| | (2) A WALL POST INDICATOR VALVE |
| | (3) AN INDICATING VALVE IN A PIT, INSTALLED IN |
| | ACCORDANCE WITH |
| | SECTION 6.4 |
| | (4)*A BACKFLOW PREVENTER WITH AT LEAST ONE INDICATING |
| | VALVE NOT |
| | LESS THAN 40 FT (12 M) FROM THE BUILDING |
| | (A) FOR BUILDINGS LESS THAN 40 FT (12 M) IN HEIGHT, A |
| | BACKFLOW |
| | PREVENTER WITH AT LEAST ONE INDICATING VALVE SHALL |
| | BE PERMITTED TO BE INSTALLED CLOSER THAN 40 FT (12 M) |
| | BUT AT LEAST AS FAR FROM THE BUILDING AS THE HEIGHT OF |
| | THE WALL FACING THE BACKFLOW PREVENTER. |
| | (5)*A NONINDICATING VALVE, SUCH AS AN UNDERGROUND GATE |
| | VALVE |
| | WITH AN APPROVED ROADWAY BOX, COMPLETE WITH T-WRENCH, |
| | LOCATED NOT LESS THAN 40 FT (12 M) FROM THE BUILDING |
| | (A) FOR BUILDINGS LESS THAN 40 FT (12 M) IN HEIGHT, A |
| | NONINDICATING |
| | VALVE, SUCH AS AN UNDERGROUND GATE VALVE WITH AN |
| | APPROVED ROADWAY BOX, COMPLETE WITH T-WRENCH, SHALL |
| | BE PERMITTED TO BE INSTALLED CLOSER THAN 40 FT (12 M) |
| | BUT |
| | AT LEAST AS FAR FROM THE BUILDING AS THE HEIGHT OF THE |
| | WALL |
| | FACING THE BACKFLOW PREVENTER. |
| | (6) CONTROL VALVES INSTALLED IN A FIRE-RATED ROOM |
| | ACCESSIBLE |
| | FROM THE EXTERIOR |
| | (7) CONTROL VALVES IN A FIRE-RATED STAIR ENCLOSURE |
| | ACCESSIBLE |
| | FROM THE EXTERIOR AS PERMITTED BY THE AUTHORITY HAVING |
| | JURISDICTION |
| | |
| | PLEASE SHOW COMPLIANCE WITH ONE OF THE ABOVE. |
| | |
| | |
| | 2) A LICENSED UNDERGROUND CONTRACTOR IS REQUIRED TO |
| | COMPLETE THIS WORK. ONE IS NOT INDICATED. |
| | |
| | PLEASE ENSURE COMPLIANCE. |
| | |
| | |
| | 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| | ABOVE. |
| | |
| | |
| | 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |
| | |
| | PETER LEDUC |
| | FIRE MARSHAL |
| | 561-804-4709 |
| | [email protected] |
| | |