Plan Review Details - Permit 18030332
Plan Review Stops For Permit 18030332
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2018-04-06 Cont ID  
Sent By skennedy Date 2018-04-06 Time 13:11 Rev Time 0.00
Received By skennedy Date 2018-04-06 Time 13:11 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-03-14 Cont ID  
Sent By shill Date 2018-03-14 Time 17:50 Rev Time 0.00
Received By shill Date 2018-03-14 Time 17:50 Sent To FIRE
Notes
2018-03-14 17:53:07****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 1. FBC 107, REVISE OTHER PAGES WHICH ARE AFFECTED BY
 THE CHANGE IN FLOOR PLAN.
  
 2. PROVIDE A DETAIL FOR THE NEW STAIRS AND HANDRAILS,
 FBC 107.
  
 3. 1- A205 HAS AN ELEVATION MARKER, 10-A801, WHICH I
 WAS UNABLE TO LOCATE. EITHER PROVIDE THE DETAIL OR
 REMOVE. IS THIS THE STAIR DETAIL?
  
 4. PROVIDE VALUE OF ADDITIONAL WORK, FBC 109.
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2018-04-06 Cont ID  
Sent By skennedy Date 2018-04-06 Time 13:12 Rev Time 0.00
Received By skennedy Date 2018-04-06 Time 13:12 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2018-03-19 Cont ID  
Sent By pleduc Date 2018-03-19 Time   Rev Time 0.00
Received By pleduc Date 2018-03-19 Time 11:23 Sent To M
Notes
2018-03-19 13:37:03THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) THERE IS INSUFFICIENT DETAIL OF THE STAIR AND
 RAILING TO DETERMINE COMPLIANCE WITH NFPA 101, CHAPTER
 7, MEANS OF EGRESS.
  
 PLEASE PROVIDE DETAILS IN COMPLIANCE WITH THE
 REQUIREMENTS.
  
  
  
 2) IT IS UNCLEAR IF THE PROPOSED REVISIONS OF THE THE
 BATHROOM OR CLOSET AREAS REQUIRED CHANGES TO THE FIRE
 SPRINKLER OR FIRE ALARM.
  
 PLEASE PROVIDE A NOTE OF COMPLIANCE AND FORTHCOMING
 LIFE SAFETY REVISIONS.
  
  
  
 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-03-21 Cont ID  
Sent By gjohnson Date 2018-03-21 Time 09:30 Rev Time 0.00
Received By gjohnson Date 2018-03-07 Time 11:33 Sent To  
Notes
2018-03-08 11:33:38REVISION ROUTED TO SHILL

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2018-04-06 Cont ID  
Sent By skennedy Date 2018-04-06 Time 13:12 Rev Time 0.00
Received By skennedy Date 2018-04-06 Time 13:12 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2018-03-19 Cont ID  
Sent By ccole Date 2018-03-19 Time 15:01 Rev Time 0.00
Received By ccole Date 2018-03-19 Time 15:01 Sent To P
Notes
2018-03-19 15:03:511ST REVIEW FBC-2017 MECHANICAL
 REVISION #18030332
 MASTER #17060277
 3/19/18
  
 1) SUBMIT REVISED MECHANICAL PLANS FOR UNIT 109.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2018-04-06 Cont ID  
Sent By skennedy Date 2018-04-06 Time 13:13 Rev Time 0.00
Received By skennedy Date 2018-04-06 Time 13:13 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2018-03-21 Cont ID  
Sent By gjohnson Date 2018-03-21 Time 09:12 Rev Time 0.00
Received By gjohnson Date 2018-03-21 Time 08:23 Sent To  
Notes
2018-03-21 09:30:081ST REVIEW: FBC 2017 6TH EDITION
  
 PLUMBING COMMENTS:
  
 1. PLEASE PROVIDE A RESTROOM PLAN DETAIL SHOWING THE
 REQUIRED CLEAR FLOOR SPACE WITH DIMENSIONS INCLUDED.
 PER FBC ACC 604.3.1, 606.2
  
 2. PROVIDE REVISED PLUMBING PLAN TO INCLUDE FLOOR PLAN,
 WATER AND SANITARY ISOMETRIC. PER WPB AMEND TO FBC
 107.3.5.1.3
  
 3. A LINT TRAP IS REQUIRED FOR THE WASHING MACHINE
 DISCHARGE. PER FBC PL 1003.6
  
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711