| Plan Review Stops For Permit 18030329 |
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2018-04-03 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2018-04-03 |
Time |
16:49 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2018-04-03 |
Time |
16:48 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2018-03-13 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2018-03-13 |
Time |
15:40 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2018-03-13 |
Time |
15:34 |
Sent To |
|
|
| Notes |
| 2018-03-13 15:43:49 | FLORIDA BUILDING CODE 2017 6TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED | | | NFPA 70 2014 EDITION | | | | | | JAKE LEAHY | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6713 | | | [email protected] | | | | | | PANEL SCHEDULE AND RISER DIAGRAM DOES NOT MATCH. | | | | | | PROVIDE CUT SHEETS FOR OUTLETS TO BE SUPPLIED. | | | | | | 100A CIRCUIT REQUIRES A #8 EQUIPMENT GROUND | | | | | | 40A CIRCUIT REQUIRESE A #10 EQUIPMENT GROUND |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2018-03-13 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2018-03-13 |
Time |
15:43 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2018-03-09 |
Time |
13:12 |
Sent To |
|
|
| Notes |
| 2018-03-12 13:12:30 | ROUTED TO ELECTRICAL INBOX |
|
|
|