Plan Review Details - Permit 18030329
Plan Review Stops For Permit 18030329
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2018-04-03 Cont ID  
Sent By jleahy Date 2018-04-03 Time 16:49 Rev Time 0.00
Received By jleahy Date 2018-04-03 Time 16:48 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-03-13 Cont ID  
Sent By jleahy Date 2018-03-13 Time 15:40 Rev Time 0.00
Received By jleahy Date 2018-03-13 Time 15:34 Sent To  
Notes
2018-03-13 15:43:49FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 PANEL SCHEDULE AND RISER DIAGRAM DOES NOT MATCH.
  
 PROVIDE CUT SHEETS FOR OUTLETS TO BE SUPPLIED.
  
 100A CIRCUIT REQUIRES A #8 EQUIPMENT GROUND
  
 40A CIRCUIT REQUIRESE A #10 EQUIPMENT GROUND

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-03-13 Cont ID  
Sent By jleahy Date 2018-03-13 Time 15:43 Rev Time 0.00
Received By jleahy Date 2018-03-09 Time 13:12 Sent To  
Notes
2018-03-12 13:12:30ROUTED TO ELECTRICAL INBOX