Plan Review Details - Permit 18030309
Plan Review Stops For Permit 18030309
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2018-04-24 Cont ID  
Sent By cthroop Date 2018-04-24 Time 07:35 Rev Time 0.00
Received By cthroop Date 2018-04-19 Time 16:48 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-03-19 Cont ID  
Sent By aclange Date 2018-03-19 Time 13:05 Rev Time 0.00
Received By aclange Date 2018-03-19 Time 10:46 Sent To  
Notes
2018-03-19 13:05:36****PLAN REVIEW COMMENTS****
  
 ART LANGE BUILDING PLANS EXAMINER
  
 DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS STREET
 WEST PALM BEACH, FL 33402
  
 561-805-6718 [email protected]
  
 FBC FLORIDA BUILDING CODE 2017 6TH EDITION W/2010 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION / FRC FLORIDA RESIDENTIAL CODE
 2017 6TH EDITION
  
 1. PERMIT APPLICATIONS SUBMITTED AFTER 12/31/17 SHALL
 BE DESIGNED UNDER THE FLORIDA BUILDING CODE 2017 6TH
 EDITION INCLUDING MECHANICAL, PLUMBING, ENERGY
 CONSERVATION AND ACCESSIBILITY. CHANGE ALL CODE
 REFERENCES ON PAGE G2.01 CODE ANALYSIS.
  
 2. PROVIDE SHOP DRAWINGS FOR STOREFRONT FRAMING.
  
 ALTERNATIVELY YOU CAN SUBMIT THESE LATER AS A DEFERRED
 SUBMITTAL BY LISTING THEM ON THE COVER SHEET.
  
 FBC107.3.4.2 DEFERRED SUBMITTALS. FOR THE PURPOSES OF
 THIS SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE
 PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE
 TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO
 THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD.
 DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR
 APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED
 DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST
 THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS
 FOR REVIEW BY THE BUILDING OFFICIAL.
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD
 THEM TO THE BUILDING OFFICIAL WITH A NOTATION
 INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL
 ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING
 OFFICIAL.
  
 3. NOTE: SEPERATE PERMITS REQUIRED FOR SIGNS AND
 LANDSCAPING.
  
  
  
  
 WHEN RESUBMITTING, PLEASE COMPLETE A RESUBMITTAL FORM:
  
 HTTP://WPB.ORG/DEVELOPMENT/WPCONTENT/UPLOADS/SITES/33/2
 013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 THIS FORM IS ALSO AVAILABLE AT THE BUILDING DIVISION.
 WHEN RESUBMITTING, SWAP OUT SHEETS WHICH HAVE CHANGED
 SO THAT THERE ARE TWO COMPLETE, COLLATED SETS OF PLANS
 READY FOR PERMIT ISSUANCE. OLD SHEETS ARE TO BE
 RETAINED IN THE PERMIT APPLICATION PACKAGE (SEPARATE
 FROM THE PERMIT SETS) AND MARKED *OLD SHEETS* OR
 *VOID*. PLEASE KEEP BOTH SETS OF OLD VOIDED SHEETS IN
 THE PERMIT PACKAGE.
  
 A RESPONSE LETTER INDICATING HOW EACH ITEM WAS
 ADDRESSED WILL HELP TO EXPEDITE PLAN REVIEW.
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2018-03-26 Cont ID  
Sent By jleahy Date 2018-03-26 Time 11:38 Rev Time 0.00
Received By jleahy Date 2018-03-26 Time 11:38 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2018-03-16 Cont ID  
Sent By scaldero Date 2018-03-16 Time 14:55 Rev Time 0.00
Received By scaldero Date 2018-03-16 Time 14:52 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date   Cont ID  
Sent By   Date 2018-07-10 Time   Rev Time 0.00
Received By lmarchan Date 2018-06-27 Time 15:48 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date   Cont ID  
Sent By   Date 2018-05-24 Time   Rev Time 0.00
Received By lmarchan Date 2018-05-15 Time 12:34 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-04-24 Cont ID  
Sent By cthroop Date 2018-04-24 Time 07:35 Rev Time 0.00
Received By cthroop Date 2018-04-06 Time 08:17 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-03-26 Cont ID  
Sent By jleahy Date 2018-03-26 Time 11:38 Rev Time 0.00
Received By jleahy Date 2018-03-12 Time 16:55 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2018-03-19 Cont ID  
Sent By aclange Date 2018-03-19 Time 12:35 Rev Time 0.00
Received By aclange Date 2018-03-19 Time 12:35 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2018-07-10 Cont ID  
Sent By ccole Date 2018-07-10 Time 09:17 Rev Time 0.00
Received By ccole Date 2018-07-10 Time 07:14 Sent To I
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2018-05-24 Cont ID  
Sent By ccole Date 2018-05-24 Time 13:03 Rev Time 0.00
Received By ccole Date 2018-05-23 Time 17:30 Sent To  
Notes
2018-05-24 13:42:053RD REVIEW FBC-2017 MECHANICAL, ENERGY CONSERVATION
 CODES
 PERMIT #18030309
 5/24/18
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) IN RESPONSE TO THE ISSUE OF THE O/A DUCT LOCATED IN
 THE INTERIOR EXIT STAIRWAY EXTENSION THE EOR IS
 PROPOSING THAT THE EXISTING FIRE-RATED CEILING IN THE
 EXTENSION BE REMOVED AND A 2HR. RATED FIRE WRAP TO BE
 APPLIED TO THE DUCT. REMOVAL OF THE CEILING HOWEVER
 DOES NOT SOLVE THE PROBLEM OF THE DUCT AND POSSIBLY
 OTHER PROHIBITED ELECTRICAL CONDUITS, PLUMBING OR FIRE
 SPRINKLER PIPINGS,
  
 MECHANCIAL COMPONENTS ETC. FROM BEING LOCATED IN THE
 STAIRWAY EXTENSION, AND NOT FOR THE PURPOSE OF SERVING
 THE STAIRWAY EXTENSION. MORE INFORMATION AS TO WHAT MEP
 SYSTEMS ARE LOCATED IN THE EXTENSION IS REQUIRED.
 PLEASE NOTE THAT THE PROJECT HAS BEEN DETERNINED TO BE
 LEVEL II ALTERATION BY THE ARCHITECT. AND, IN
 ACCORDANCE WITH SECTIONS 701.2 AND 801.2 , THE BUILDING
 SHALL
  
 NOT BE ALTERED SUCH THAT THE BUILDING BECOMES LESS SAFE
 OR ENERGY EFFICIENT THAN IT'S EXISTING CONDITION.
 REMOVAL OF THE CEILING APPARENTLY WOULD MAKE THE
 BUILDING LESS SAFE.
  
 2) M1.002: IT APPEARS A FIRE DAMPER IS MISSING WHERE
 THE O/A DUCT IS PENETRATION THE FIRE-RATED
 LOBBY/STAIRWAY EXTENSION WALL- SECTION 607.5.2.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2018-04-17 Cont ID  
Sent By ccole Date 2018-04-17 Time 16:11 Rev Time 0.00
Received By ccole Date 2018-04-17 Time 16:11 Sent To  
Notes
2018-05-24 13:19:532ND REVIEW FBC-2017 MECHANICAL, ENERGY CONSERVATION
 CODES
 PERMIT #18030309
 4/17/18
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET M1.002: IT APPEARS THAT THE 32"X20" O/A DUCT
 IS LOCATED IN THE INTERIOR EXIT STAIRWAY EXTENSION
 WHICH IS PROHIBITED PER SECTION 1023.5 FBC-17 BUILDING.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2018-03-21 Cont ID  
Sent By ccole Date 2018-03-21 Time 17:17 Rev Time 0.00
Received By ccole Date 2018-03-21 Time 16:47 Sent To  
Notes
2018-03-21 17:22:031ST REVIEW FBC-2017 MECHANICAL, ENERGY CONSERVATION
 CODES
 PERMIT #18030309
 3/21/18
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PROVIDE COOLING AND HEATING CALCULATIONS FOR THE NEW
 HP WEST SYSTEM - SECTION C403.2.1 FBC-17 ENERGY
 CONSERVATION.
  
 2) M1.001: SMOKE DETECTORS ARE REQUIRED IN THE SUPPLY
 AIR SYSTEM OF HP WEST- SECTION 606.2.1.
  
 3) PLEASE UPDATE ALL CODE REFERENCES TO THE FLORIDA
 BUILDING CODES SIXTH EDITION 2017.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status N Date 2018-04-19 Cont ID  
Sent By gjohnson Date 2018-04-19 Time 11:52 Rev Time 0.00
Received By gjohnson Date 2018-04-19 Time 11:52 Sent To  
Notes
2018-04-19 11:52:39NO PLUMBING WORK ON WEST TOWER

Review Stop P PLUMBING
Rev No 1 Status F Date 2018-03-26 Cont ID  
Sent By gjohnson Date 2018-03-26 Time 08:44 Rev Time 0.00
Received By gjohnson Date 2018-03-23 Time 13:47 Sent To  
Notes
2018-03-26 09:03:321ST REVIEW: FBC 2017 6TH EDITION
  
 PLUMBING COMMENTS:
  
 1. SHT. G1.03 PLEASE SHOW COMPLIANCE WITH THE
 FOLLOWING: FBC ACC
 A) 604.7 DISPENSERS. TOILET PAPER DISPENSERS SHALL
 COMPLY WITH 309.4 AND SHALL BE 7 INCHES (180 MM)
 MINIMUM AND 9 INCHES (230 MM) MAXIMUM IN FRONT OF THE
 WATER CLOSET MEASURED TO THE CENTERLINE OF THE
 DISPENSER.
 B) 604.5.2 REAR WALL. THE REAR WALL GRAB BAR SHALL BE
 36 INCHES (915 MM) LONG MINIMUM AND EXTEND FROM THE
 CENTERLINE OF THE WATER CLOSET 12 INCHES (305 MM)
 MINIMUM ON ONE SIDE AND 24 INCHES (610 MM) MINIMUM ON
 THE OTHER SIDE.
 C) 609.4 POSITION OF GRAB BARS. 33 INCHES MINIMUM AND
 36 INCHES MAXIMUM ABOVE THE FINISH FLOOR MEASURED TO
 THE TOP OF THE GRIPPING SURFACE,
  
 2. SHT. 14.101 DETAIL #01 PROVIDE DIMENSIONS FOR KNEE
 AND TOE CLEARANCE. PER FBC ACC 306
  
 3. PLEASE PROVIDE A CLEAR SCOPE OF PLUMBING WORK THIS
 SET OF PLANS HAD SOME DETAILS BUT DO NOT SHOW AND
 PLUMBING ON THE FLOOR PLAN OF THE WEST TOWER AND THERE
 WAS NO PLUMBING SHOWN ON THE DEMO PLAN FOR THE EAST AND
 WEST TOWERS. PER WPB AMEND TO FBC 107.2.1
  
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2018-03-19 Cont ID  
Sent By aclange Date 2018-03-19 Time 12:35 Rev Time 0.00
Received By aclange Date 2018-03-19 Time 12:35 Sent To  
Notes
2018-05-24 13:45:06MECH DIG/SIGS GOOD
 CCOLE-5/24/18
2018-03-21 17:40:55MECH DIG/SIGS GOOD- CCOLE-3/21/18
2018-03-19 12:35:58ALL SIGNATURES VARIFIED.