Plan Review Details - Permit 18030308
Plan Review Stops For Permit 18030308
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2018-04-20 Cont ID  
Sent By cthroop Date 2018-04-20 Time 16:55 Rev Time 0.00
Received By cthroop Date 2018-04-19 Time 16:47 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-03-19 Cont ID  
Sent By aclange Date 2018-03-19 Time 10:26 Rev Time 0.00
Received By aclange Date 2018-03-19 Time 07:47 Sent To  
Notes
2018-03-19 10:26:24****PLAN REVIEW COMMENTS****
  
 ART LANGE BUILDING PLANS EXAMINER
  
 DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS STREET
 WEST PALM BEACH, FL 33402
  
 561-805-6718 [email protected]
  
 FBC FLORIDA BUILDING CODE 2017 6TH EDITION W/2010 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION / FRC FLORIDA RESIDENTIAL CODE
 2017 6TH EDITION
  
 1. PERMIT APPLICATIONS SUBMITTED AFTER 12/31/17 SHALL
 BE DESIGNED UNDER THE FLORIDA BUILDING CODE 2017 6TH
 EDITION INCLUDING MECHANICAL, PLUMBING, ENERGY
 CONSERVATION AND ACCESSIBILITY. CHANGE ALL CODE
 REFERENCES ON PAGE G2.01 CODE ANALYSIS.
  
 2. PROVIDE SHOP DRAWINGS FOR STOREFRONT FRAMING.
  
 ALTERNATIVELY YOU CAN SUBMIT THESE LATER AS A DEFERRED
 SUBMITTAL BY LISTING THEM ON THE COVER SHEET.
  
 FBC107.3.4.2 DEFERRED SUBMITTALS. FOR THE PURPOSES OF
 THIS SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE
 PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE
 TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO
 THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD.
 DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR
 APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED
 DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST
 THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS
 FOR REVIEW BY THE BUILDING OFFICIAL.
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD
 THEM TO THE BUILDING OFFICIAL WITH A NOTATION
 INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL
 ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING
 OFFICIAL.
  
 3. NOTE: SEPERATE PERMITS REQUIRED FOR SIGNS AND
 LANDSCAPING.
  
  
  
  
 WHEN RESUBMITTING, PLEASE COMPLETE A RESUBMITTAL FORM:
  
 HTTP://WPB.ORG/DEVELOPMENT/WPCONTENT/UPLOADS/SITES/33/2
 013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 THIS FORM IS ALSO AVAILABLE AT THE BUILDING DIVISION.
 WHEN RESUBMITTING, SWAP OUT SHEETS WHICH HAVE CHANGED
 SO THAT THERE ARE TWO COMPLETE, COLLATED SETS OF PLANS
 READY FOR PERMIT ISSUANCE. OLD SHEETS ARE TO BE
 RETAINED IN THE PERMIT APPLICATION PACKAGE (SEPARATE
 FROM THE PERMIT SETS) AND MARKED *OLD SHEETS* OR
 *VOID*. PLEASE KEEP BOTH SETS OF OLD VOIDED SHEETS IN
 THE PERMIT PACKAGE.
  
 A RESPONSE LETTER INDICATING HOW EACH ITEM WAS
 ADDRESSED WILL HELP TO EXPEDITE PLAN REVIEW.
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2018-03-26 Cont ID  
Sent By jleahy Date 2018-03-26 Time 11:37 Rev Time 0.00
Received By jleahy Date 2018-03-26 Time 11:37 Sent To  
Notes
***NONE***

Review Stop E-LOWVOLT ELECTRICAL LOW VOLTAGE
Rev No 1 Status P Date 2018-07-03 Cont ID  
Sent By jpearson Date 2018-07-03 Time 10:02 Rev Time 0.00
Received By jpearson Date 2018-07-03 Time 10:02 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2018-03-16 Cont ID  
Sent By scaldero Date 2018-03-16 Time 14:52 Rev Time 0.00
Received By scaldero Date 2018-03-16 Time 14:27 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-04-20 Cont ID  
Sent By cthroop Date 2018-04-20 Time 16:55 Rev Time 0.00
Received By cthroop Date 2018-04-06 Time 08:42 Sent To  
Notes
2018-04-20 16:56:01E-MAIL SENT TO LM. CT

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-03-26 Cont ID  
Sent By jleahy Date 2018-03-26 Time 11:37 Rev Time 0.00
Received By jleahy Date 2018-03-12 Time 16:54 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2018-03-19 Cont ID  
Sent By aclange Date 2018-03-19 Time 10:26 Rev Time 0.00
Received By aclange Date 2018-03-19 Time 10:26 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2018-04-17 Cont ID  
Sent By ccole Date 2018-04-17 Time 15:28 Rev Time 0.00
Received By ccole Date 2018-04-17 Time 14:39 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2018-03-21 Cont ID  
Sent By ccole Date 2018-03-21 Time 16:32 Rev Time 0.00
Received By ccole Date 2018-03-21 Time 16:32 Sent To  
Notes
2018-03-21 16:47:011ST REVIEW FBC-2017 MECHANICAL, ENERGY CONSERVATION
 CODES
 PERMIT #18030308
 3/21/18
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET M1.001: KEYED NOTE #2 REFERENCES SHEET M.001
 WHICH IS NOT UPLOADED FOR REVIEW- PLEASE UPLOAD THE
 SHEET.
  
 2) PROVIDE COOLING AND HEATING CALCULATIONS FOR THE NEW
 HP SYSTEMS - SECTION C403.2.1 FBC-17 ENERGY
 CONSERVATION.
  
 3) M1.001: SMOKE DETECTORS ARE REQUIRED IN THE SUPPLY
 AIR SYSTEMS OF HP 1 & 2- SECTION 606.2.1.
  
 4) M1.001: THE OG-1 OUTDOOR AIR INTAKE SHALL BE IN
 COMPLIANCE WITH SECTION 401.4 FOR REQUIRED CLEARANCES,
 AND SECTION 401.5 FOR INTAKE OPENING PROTECTION.
  
 5) M1.001: SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE
 STEALTH ACCESS PANEL.
  
 6) PLEASE UPDATE ALL CODE REFERENCES TO THE FLORIDA
 BUILDING CODES SIXTH EDITION 2017.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2018-04-19 Cont ID  
Sent By gjohnson Date 2018-04-19 Time 11:38 Rev Time 0.00
Received By gjohnson Date 2018-04-19 Time 11:38 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2018-03-26 Cont ID  
Sent By gjohnson Date 2018-03-26 Time 09:33 Rev Time 0.00
Received By gjohnson Date 2018-03-26 Time 09:04 Sent To  
Notes
2018-03-26 09:56:051ST REVIEW: FBC 2017 6TH EDITION
  
 PLUMBING COMMENTS:
  
 1. SHT. G1.03 PLEASE SHOW COMPLIANCE WITH THE
 FOLLOWING: FBC ACC
 A) 604.7 DISPENSERS. TOILET PAPER DISPENSERS SHALL
 COMPLY WITH 309.4 AND SHALL BE 7 INCHES (180 MM)
 MINIMUM AND 9 INCHES (230 MM) MAXIMUM IN FRONT OF THE
 WATER CLOSET MEASURED TO THE CENTERLINE OF THE
 DISPENSER.
 B) 604.5.2 REAR WALL. THE REAR WALL GRAB BAR SHALL BE
 36 INCHES (915 MM) LONG MINIMUM AND EXTEND FROM THE
 CENTERLINE OF THE WATER CLOSET 12 INCHES (305 MM)
 MINIMUM ON ONE SIDE AND 24 INCHES (610 MM) MINIMUM ON
 THE OTHER SIDE.
 C) 609.4 POSITION OF GRAB BARS. 33 INCHES MINIMUM AND
 36 INCHES MAXIMUM ABOVE THE FINISH FLOOR MEASURED TO
 THE TOP OF THE GRIPPING SURFACE,
  
 2. SHT. 14.101 DETAIL #01 PROVIDE DIMENSIONS FOR KNEE
 AND TOE CLEARANCE. PER FBC ACC 306
  
 3. PLEASE SHOW THE CLEAR FLOOR SPACE WITH THE
 DIMENSIONS SHOWN, FOR THE TOILETS, LAVATORY'S AND WATER
 FOUNTAIN. PER FBC ACC 604.3.1 - 606.2 - 602.2
  
 4. THE TOILET PAPER DISPENSER SHALL BE MOUNTED ON THE
 SIDE WALL IN FRONT OF THE TOILET SHT. I1.401 + I1.402
 SHOW IT ON THE REAR WALL IT SHALL COMPLY WITH FBC ACC
 604.7
  
 5. TEMPERED WATER SHALL BE DELIVERED FROM LAVATORIES
 AND GROUP WASH FIXTURES LOCATED IN PUBLIC TOILET
 FACILITIES PROVIDED FOR CUSTOMERS, PATRONS AND
 VISITORS. TEMPERED WATER SHALL BE DELIVERED THROUGH AN
 APPROVED WATER-TEMPERATURE LIMITING DEVICE THAT
 CONFORMS TO ASSE 1070 OR CSA B125.3. PER FBC PL 416.5
  
 6. PLEASE SHOW COMPLIANCE WITH FBC ACC 602.1 + 602.2 +
 602.4 + 602.7
  
 7. PLEASE SHOW ON THE WATER ISOMETRIC THE AIR HAMMER
 ARRESTORS AND SHUT OFF VALVES COMPILING WITH FBC PL
 604.9 + 606.1 (5)
  
 8. THE ISOMETRIC DRAWINGS ARE TO CONGESTED TO VERIFY
 CODE COMPLIANCE PLEASE EXPAND THE WATER AND SANITARY
 ISOMETRIC . PER WPB AMEND TO FBC 107.2.1
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2018-03-19 Cont ID  
Sent By aclange Date 2018-03-19 Time 10:32 Rev Time 0.00
Received By aclange Date 2018-03-19 Time 10:32 Sent To  
Notes
2018-03-21 17:40:33MECH DIG/SIGS GOOD- CCOLE-3/21/18
2018-03-19 10:32:42ALL SIGNATURES VARIFIED.