Plan Review Details - Permit 18030288
Plan Review Stops For Permit 18030288
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-03-26 Cont ID  
Sent By cthroop Date 2018-03-26 Time 13:41 Rev Time 0.00
Received By cthroop Date 2018-03-26 Time 13:40 Sent To  
Notes
2018-03-26 13:42:29BUILDING PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER, PX3169
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. DESIGNED PROFESSIONALS SIGNATURE AND SEAL SHALL BE
 ORIGINAL.
  
 PLANS THAT HAVE BEEN PREPARED BY AN ENGINEER AND
 SUBMITTED FOR PUBLIC RECORD SHALL BEAR THE SIGNATURE,
 DATE AND SEAL OF THE ENGINEER PER FL ADMIN. CODE RULE
 61G15-23.001.
  
  
2018-03-23 10:29:41SEE JAKE FOR REASON TO HAVE BUILDING REVIEW.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-03-23 Cont ID  
Sent By jleahy Date 2018-03-23 Time 10:32 Rev Time 0.00
Received By jleahy Date 2018-03-23 Time 10:29 Sent To B
Notes
2018-03-23 10:32:46FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR EACH
 PANEL INCLUDING INFORMATION FROM THE POWER COMPANY
 STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT
 IS FOR THE SERVICE TO CONFIRM THE STATED AIC RATING OF
 THE SERVICE EQUIPMENT AND DOWNSTREAM PANELS IS
 ADEQUATE. NEC 110.9, 110.10
  
 PROVIDE NOTE THAT THE SERVICE EQUIPMENT SHALL BE MARKED
 WITH THE MAXIMUM AVAILABLE SHORT CIRCUIT CURRENT
 AVAILABLE PER NEC 110.24.
  
 PROVIDE NOTES TO INDICATE THE REQUIRED MARKING OF
 SERVICE EQUIPMENT FOR ARC FLASH HAZARD WARNING AND
 AVAILABLE FAULT CURRENT PER CODE. NEC 110.16, 110.24
  
 210.64 ELECTRICAL SERVICE AREAS AT LEAST ONE 125-VOLT,
 SINGLE-PHASE, 15- OR 20-AMPERE-RATED RECEPTACLE OUTLET
 SHALL BE INSTALLED WIT HIN 15 M (50 FT) OF THE
 ELECTRICAL SERVICE EQUIPMENT.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-03-26 Cont ID  
Sent By cthroop Date 2018-03-26 Time 13:42 Rev Time 0.00
Received By cthroop Date 2018-03-07 Time 10:52 Sent To I
Notes
2018-03-08 10:53:06ROUTED TO ZONING

Review Stop Z ZONING
Rev No 1 Status F Date 2018-03-15 Cont ID  
Sent By eschneid Date 2018-03-15 Time 14:04 Rev Time 0.50
Received By eschneid Date 2018-03-08 Time 16:46 Sent To E
Notes
2018-03-15 14:14:19FAILED
  
 1) PRIOR TO ZONING APPROVAL OF THIS PERMIT A MINOR
 PLANNED DEVELOPMENT IS REQUIRED TO BE SUBMITTED TO, AND
 APPROVED BY, THE PLANNING DIVISION.
  
 2) THE PLANNING DIVISION DOES NOT APPROVE THIS LOCATION
 FOR THE CHARGING STATIONS AND ANCILLARY FACILITIES.
 THEY NEED TO BE LOCATED AT A LOCATION THAT IS NOT
 FRONTING PALM BEACH LAKES BOULEVARD (OR CONGRESS
 AVENUE).
  
 3) FULL COMMENTS WILL BE GENERATED AS PART OF THE MINOR
 PLANNED DEVELOPMENT REVIEW.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446
 [email protected]