Plan Review Details - Permit 18030272
Plan Review Stops For Permit 18030272
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2018-03-28 Cont ID  
Sent By jleahy Date 2018-03-28 Time 16:12 Rev Time 0.00
Received By jleahy Date 2018-03-28 Time 16:12 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-03-09 Cont ID  
Sent By jleahy Date 2018-03-09 Time 09:53 Rev Time 0.00
Received By jleahy Date 2018-03-09 Time 09:53 Sent To  
Notes
2018-03-09 10:25:54FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH ED
 NFPA 70 2011 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
  
 PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR EACH
 PANEL INCLUDING INFORMATION FROM THE POWER COMPANY
 STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR
 THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE
 SERVICE EQUIPMENT AND DOWNSTREAM PANELS IS ADEQUATE.
 NEC 110.9, 110.10
 .
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-03-28 Cont ID  
Sent By jleahy Date 2018-03-28 Time 16:13 Rev Time 0.00
Received By jleahy Date 2018-03-15 Time 12:53 Sent To  
Notes
2018-03-16 12:53:39RESUB ROUTED TO JLEAHY

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-03-09 Cont ID  
Sent By jleahy Date 2018-03-09 Time 10:26 Rev Time 0.00
Received By jleahy Date 2018-03-07 Time 10:10 Sent To  
Notes
2018-03-08 10:10:36ROUTED TO ELECTRICAL INBOX