| 2018-03-08 12:05:14 | FLORIDA BUILDING CODE 2014 5TH EDITION |
| | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH ED |
| | NFPA 70 2011 EDITION |
| | |
| | JAKE LEAHY |
| | ELECTRICAL PLANS EXAMINER II |
| | 561-805-6713 |
| | [email protected] |
| | |
| | SIGN PAGE MISSING FROM PERMIT PLEASE SUPPLY A SHEET |
| | SHOWING THE REQUIRED SIGNAGE AT THIS PV SYSTEM. |
| | |
| | |
| | 690.17 (E) INTERRUPTING RATING. THE BUILDING OR |
| | STRUCTURE DISCONNECTING MEANS SHALL HAVE AN |
| | INTERRUPTING RATING SUFFICIENT FOR THE MAXIMUM CIRCUIT |
| | VOLTAGE AND CURRENT THAT IS AVAILABLE AT THE LINE |
| | TERMINALS OF THE EQUIPMENT. WHERE ALL TERMINALS OF THE |
| | DISCONNECTING MEANS MAY BE ENERGIZED IN THE OPEN |
| | POSITION, A WARNING SIGN SHALL BE MOUNTED ON OR |
| | ADJACENT TO THE DISCONNECTING MEANS. |
| | THE SIGN SHALL BE CLEARLY LEGIBLE AND HAVE THE |
| | FOLLOWING WORDS OR EQUIVALENT: |
| | |
| | WARNING |
| | ELECTRIC SHOCK HAZARD |
| | DO NOT TOUCH TERMINALS. |
| | TERMINALS ON BOTH THE LINE |
| | AND LOAD SIDES MAY BE ENERGIZED |
| | IN THE OPEN POSITION. |
| | |
| | THE WARNING SIGN(S) OR LABEL(S) SHALL COMPLY WITH |
| | 110.21(B). |
| | |
| | |
| | 690.31(G)(3) MARKING AND LABELING REQUIRED. THE |
| | FOLLOWING WIRING METHODS AND ENCLOSURES THAT CONTAIN PV |
| | POWER SOURCE CONDUCTORS SHALL BE MARKED WITH THE |
| | WORDING WARNING: PHOTOVOLTAIC POWER SOURCE BY MEANS OF |
| | PERMANENTLY AFFIXED LABELS OR OTHER APPROVED PERMANENT |
| | MARKING: |
| | |
| | (1) EXPOSED RACEWAYS, CABLE TRAYS, AND OTHER WIRING |
| | METHODS |
| | (2) COVERS OR ENCLOSURES OF PULL BOXES AND JUNCTION |
| | BOXES |
| | (3) CONDUIT BODIES IN WHICH ANY OF THE AVAILABLE |
| | CONDUIT OPENINGS ARE UNUSED |
| | |
| | |
| | |
| | |
| | 690.31(G)(4) MARKING AND LABELING METHODS AND |
| | LOCATIONS. THE LABELS OR MARKINGS SHALL BE VISIBLE |
| | AFTER INSTALLATION. THE LABELS SHALL BE REFLECTIVE, AND |
| | ALL LETTERS SHALL BE CAPITALIZED AND SHALL BE A MINIMUM |
| | HEIGHT OF 9.5 MM (3?8 IN.) IN WHITE ON A RED |
| | BACKGROUND. PV POWER CIRCUIT LABELS SHALL APPEAR ON |
| | EVERY SECTION OF THE WIRING SYSTEM THAT IS SEPARATED BY |
| | ENCLOSURES, WALLS, PARTITIONS, CEILINGS, OR FLOORS. |
| | SPACING BETWEEN LABELS OR MARKINGS, OR BETWEEN A LABEL |
| | AND A MARKING, SHALL NOT BE MORE THAN 3 M (10 FT). |
| | LABELS REQUIRED BY THIS SECTION SHALL BE SUITABLE FOR |
| | THE ENVIRONMENT WHERE THEY ARE INSTALLED. |
| | |
| | |
| | |
| | 690.35(F) MARKING. THE PV POWER SOURCE SHALL BE LABELED |
| | WITH THE FOLLOWING WARNING AT EACH JUNCTION BOX, |
| | COMBINER BOX, DISCONNECT, AND DEVICE WHERE ENERGIZED, |
| | UNGROUNDED CIRCUITS MAY BE EXPOSED DURING SERVICE: |
| | |
| | WARNING |
| | ELECTRIC SHOCK HAZARD. THE DC CONDUCTORS |
| | OF THIS PHOTOVOLTAIC SYSTEM ARE |
| | UNGROUNDED AND MAY BE ENERGIZED. |
| | THE WARNING SIGN(S) OR LABEL(S) SHALL COMPLY WITH |
| | 110.21(B). |
| | |
| | |
| | 690.56(B) FACILITIES WITH UTILITY SERVICES AND PV |
| | SYSTEMS. BUILDINGS OR STRUCTURES WITH BOTH UTILITY |
| | SERVICE AND A PV SYSTEM SHALL HAVE A PERMANENT PLAQUE |
| | OR DIRECTORY PROVIDING THE LOCATION OF THE SERVICE |
| | DISCONNECTING MEANS AND THE PV SYSTEM DISCONNECTING |
| | MEANS IF NOT LOCATED AT THE SAME LOCATION. THE WARNING |
| | SIGN(S) OR LABEL(S) SHALL COMPLY WITH 110.21(B). |
| | |