Plan Review Details - Permit 18030247
Plan Review Stops For Permit 18030247
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2018-06-29 Cont ID  
Sent By rmcdouga Date 2018-06-29 Time 10:40 Rev Time 0.00
Received By rmcdouga Date 2018-06-29 Time 10:40 Sent To I
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2018-06-01 Cont ID  
Sent By rmcdouga Date 2018-06-01 Time 17:30 Rev Time 0.00
Received By rmcdouga Date 2018-06-01 Time 16:49 Sent To I
Notes
2018-06-01 17:29:58PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) SOME OF THE PLAN SHEETS ARE MISSING FROM THE TWO
 SETS OF PLANS THAT WERE RESUBMITTED. IT APPEARS THAT
 THE PERSON THAT DID THE RESUB DID NOT REMOVE THE PLAN
 SHEETS THAT WERE NOT REVISED FROM THE OLD PLAN SETS AND
 INSERT THEM INTO THE NEW ONES. ONLY ONE SET OF THE OLD
 PLANS WAS WITH THE RESUBMITTAL. SUBMIT TWO COMPLETE
 SETS OF PLANS. FBC 107.2.1
  
 2) THE PLANS DO NOT HAVE THE TITLE BLOCK OF THE
 ENGINEER THAT IS SIGNING AND SEALING THEM AS REQUIRED
 BY FAC 61G15-23.001 AND FS471.
  
 3) SUBMIT PROOF THAT THE METL-SPAN CFR INSULATED ROOF
 PANELS THAT ARE SHOWN ON SHEET DS-02 ARE THE ONES THAT
 WERE INSTALLED ON THIS COMMERCIAL BUILDING. FBC 107.2.1
  
 4) THE WINDLOAD DATA ON SHEET S-03 LISTS THIS PROJECT
 AS A RISK CATEGORY II WITH A 170 MPH VULT WINDSPEED.
 THIS BUILDING IS A SCHOOL AND IS CLASSIFIED AS RISK
 CATEGORY III WITH A 180MPH WIND SPEED PER FBC 1609.3.
 PLEASE REVISE THE WINDLOAD DATA.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-03-27 Cont ID  
Sent By aclange Date 2018-03-27 Time 14:35 Rev Time 0.00
Received By aclange Date 2018-03-27 Time 13:08 Sent To E
Notes
2018-03-27 14:36:16****PLAN REVIEW COMMENTS****
  
 ART LANGE BUILDING PLANS EXAMINER
  
 DEVELOPMENT SERVICES DEPARTMENT
  
 401 CLEMATIS STREET
 WEST PALM BEACH, FL 33402
 561-805-6718 [email protected]
  
 FBC FLORIDA BUILDING CODE 2017 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 1. ON PAGE S-3 THE ROOF SLOPE IS SHOWN AS 0 / 12. THIS
 ROOF PRODUCT CANNOT BE INSTALLED ON THIS SLOPE
 ACCORDING TO THE MANUFACTURER?S RECOMMENDATIONS. PLEASE
 VERIFY SLOPE.
  
 FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 2. PROVIDE THE SEAM SPECIFIC TEST REPORTS FOR THE S 5
 H90 ATTACHMENT CLAMP.
  
 FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
  
 WHEN RESUBMITTING, PLEASE COMPLETE A RESUBMITTAL FORM:
  
 HTTP://WPB.ORG/DEVELOPMENT/WPCONTENT/UPLOADS/SITES/33/2
 013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 THIS FORM IS ALSO AVAILABLE AT THE BUILDING DIVISION.
 WHEN RESUBMITTING, SWAP OUT SHEETS WHICH HAVE CHANGED
 SO THAT THERE ARE TWO COMPLETE, COLLATED SETS OF PLANS
 READY FOR PERMIT ISSUANCE. OLD SHEETS ARE TO BE
 RETAINED IN THE PERMIT APPLICATION PACKAGE (SEPARATE
 FROM THE PERMIT SETS) AND MARKED *OLD SHEETS* OR
 *VOID*. PLEASE KEEP BOTH SETS OF OLD VOIDED SHEETS IN
 THE PERMIT PACKAGE.
  
 A RESPONSE LETTER INDICATING HOW EACH ITEM WAS
 ADDRESSED WILL HELP TO EXPEDITE PLAN REVIEW.
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2018-06-26 Cont ID  
Sent By ppetty Date 2018-06-26 Time 11:00 Rev Time 0.00
Received By ppetty Date 2018-06-26 Time 11:00 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2018-05-18 Cont ID  
Sent By ppetty Date 2018-05-18 Time 12:48 Rev Time 0.00
Received By ppetty Date 2018-05-18 Time 12:48 Sent To  
Notes
2018-05-18 12:48:18CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS PASS, SEE COMMENTS BELOW.
  
 1. CORRECTED
 2. CORRECTED
 3. CORRECTED
 4. CORRECTED
 5. CORRECTED
 6. CORRECTED
 7. CORRECTED
 8. CORRECTED
 9. CORRECTED
 10. CORRECTED
 11. CORRECTED
 12. CORRECTED
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 PHIL PETTY
 ELECTRICAL PLANS EXAMINER,CHIEF ELECTRICAL INSPECTOR
 561-805-6742
 [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-03-29 Cont ID  
Sent By jpearson Date 2018-03-29 Time 16:38 Rev Time 0.00
Received By jpearson Date 2018-03-29 Time 16:13 Sent To  
Notes
2018-03-29 16:38:15CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. THE SUM OF THE INVERTERS AT 125% EQUALS 320 AMPS AT
 SECONDARY OF TRANSFORMER. WHEN THE MAIN OF MDP AT 1200
 AMPS IS ADDED TO THIS CURRENT, THE TOTAL IS 1520 AMPS,
 WHICH EXCEEDS THE STATED BUSS RATING AT 120% OF PANEL
 MDP. PROVIDE CORRECTION. NEC 705.12(D)
 2. PROVIDE MANUFACTURERS SPECIFICATION SHEET FOR PANEL
 MDP SHOWING THE BUSS RATING OF 1250 AMPS AS STATED ON
 PLAN. NEC 110.3
 3. PROVIDE MANUFACTURERS SPECIFICATION SHEET FOR ?PV
 SOLAR LOAD CENTER? SHOWING THIS PANEL IS LISTED FOR PV
 USE AS A COMBINER. NEC 110.3, 690.4
 4. RISER DIAGRAM SHOWS ?REVENUE GRADE MONITORING IF
 REQUIRED?. CONFIRM WITH POWER COMPANY IF THIS
 INSTALLATION WILL BE REQUIRED AND UPDATE PLAN
 ACCORDINGLY. PROVIDE SPEC SHEET FOR EQUIPMENT IF
 REQUIRED. NEC110.3; FBC 107.2.1
 5. THE 112.5 KVA TRANSFORMER IS SHOWN MOUNTED ON ROOF.
 PROVIDE A WEATHER PROOF ENCLOSURE. NEC 450.22
 6. PROVIDE MEANS OF DISCONNECT FOR TRANSFORMER PRIMARY.
 NEC 450.14
 7. PROVIDE MANUFACTURE SPEC SHEETS FOR ALL PV
 COMPONENTS INCLUDING RAPID SHUTDOWN MODULES. NEC 110.3
 8. PLAN SHOWS THE UTILITY FEED AT 1200 AMPS PLUS THE PV
 BACKFEED AT 256 AMPS WITH A TOTAL OF 1440 AMPS. 1200
 PLUS 256 IS 1456 AMPS, NOT 1440. PROVIDE CORRECTION.
 FBC 107.2.1
 9. PLAN STATES THAT THE BREAKER FOR THE PV BACKFEED
 SHOULD BE A 300 AMP BREAKER, BUT THE PANEL SHOWS A 350
 AMP BREAKER. PROVIDE CORRECTION. FBC 107.2.1; NEC
 705.12(D)
 10. PROVIDE DETAIL OF GROUNDING ELECTRODE SYSTEM FOR
 THE PV SYSTEM. NEC 690.47
 11. SHEET E-02 SHOWS THE AMBIENT TEMPERATURE SPECS
 BASED ON ?WHITE PLAINS WESTCHESTER CO A?. PROVIDE
 CORRECTION. FBC 107.2.1
 12. PROVIDE LABEL PER NEC 690.5.
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2018-06-14 Cont ID  
Sent By pleduc Date 2018-06-14 Time   Rev Time 0.00
Received By pleduc Date 2018-06-13 Time 15:55 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2018-05-15 Cont ID  
Sent By pleduc Date 2018-05-15 Time   Rev Time 0.00
Received By pleduc Date 2018-05-15 Time 09:48 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2018-04-04 Cont ID  
Sent By pleduc Date 2018-04-04 Time   Rev Time 0.00
Received By pleduc Date 2018-04-02 Time 12:13 Sent To I
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2018-06-29 Cont ID  
Sent By rmcdouga Date 2018-06-29 Time 10:41 Rev Time 0.00
Received By rmcdouga Date 2018-06-08 Time 13:19 Sent To  
Notes
2018-06-11 13:20:07B26

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-06-01 Cont ID  
Sent By rmcdouga Date 2018-06-01 Time 17:30 Rev Time 0.00
Received By rmcdouga Date 2018-05-08 Time 12:41 Sent To  
Notes
2018-05-09 12:41:39B27

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-04-05 Cont ID  
Sent By lmarchan Date 2018-04-05 Time 13:47 Rev Time 0.00
Received By lmarchan Date 2018-03-06 Time 14:48 Sent To  
Notes
2018-03-23 10:42:45B28
2018-03-07 14:48:35ROUTED TO JLEAHY

Review Stop P PLUMBING
Rev No 1 Status N Date 2018-03-26 Cont ID  
Sent By gjohnson Date 2018-03-26 Time 10:40 Rev Time 0.00
Received By gjohnson Date 2018-03-26 Time 10:15 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status P Date 2018-06-28 Cont ID  
Sent By hmtribou Date 2018-06-28 Time 08:25 Rev Time 0.00
Received By hmtribou Date 2018-06-28 Time 08:25 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2018-05-23 Cont ID  
Sent By hmtribou Date 2018-05-23 Time 08:35 Rev Time 0.00
Received By hmtribou Date 2018-05-23 Time 08:35 Sent To I
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2018-03-14 Cont ID  
Sent By HT Date 2018-03-14 Time 15:20 Rev Time 0.00
Received By hmtribou Date 2018-03-14 Time 15:20 Sent To P
Notes
***NONE***