| 2018-03-29 16:38:15 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE 2017 6TH ED. |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | 1. THE SUM OF THE INVERTERS AT 125% EQUALS 320 AMPS AT |
| | SECONDARY OF TRANSFORMER. WHEN THE MAIN OF MDP AT 1200 |
| | AMPS IS ADDED TO THIS CURRENT, THE TOTAL IS 1520 AMPS, |
| | WHICH EXCEEDS THE STATED BUSS RATING AT 120% OF PANEL |
| | MDP. PROVIDE CORRECTION. NEC 705.12(D) |
| | 2. PROVIDE MANUFACTURERS SPECIFICATION SHEET FOR PANEL |
| | MDP SHOWING THE BUSS RATING OF 1250 AMPS AS STATED ON |
| | PLAN. NEC 110.3 |
| | 3. PROVIDE MANUFACTURERS SPECIFICATION SHEET FOR ?PV |
| | SOLAR LOAD CENTER? SHOWING THIS PANEL IS LISTED FOR PV |
| | USE AS A COMBINER. NEC 110.3, 690.4 |
| | 4. RISER DIAGRAM SHOWS ?REVENUE GRADE MONITORING IF |
| | REQUIRED?. CONFIRM WITH POWER COMPANY IF THIS |
| | INSTALLATION WILL BE REQUIRED AND UPDATE PLAN |
| | ACCORDINGLY. PROVIDE SPEC SHEET FOR EQUIPMENT IF |
| | REQUIRED. NEC110.3; FBC 107.2.1 |
| | 5. THE 112.5 KVA TRANSFORMER IS SHOWN MOUNTED ON ROOF. |
| | PROVIDE A WEATHER PROOF ENCLOSURE. NEC 450.22 |
| | 6. PROVIDE MEANS OF DISCONNECT FOR TRANSFORMER PRIMARY. |
| | NEC 450.14 |
| | 7. PROVIDE MANUFACTURE SPEC SHEETS FOR ALL PV |
| | COMPONENTS INCLUDING RAPID SHUTDOWN MODULES. NEC 110.3 |
| | 8. PLAN SHOWS THE UTILITY FEED AT 1200 AMPS PLUS THE PV |
| | BACKFEED AT 256 AMPS WITH A TOTAL OF 1440 AMPS. 1200 |
| | PLUS 256 IS 1456 AMPS, NOT 1440. PROVIDE CORRECTION. |
| | FBC 107.2.1 |
| | 9. PLAN STATES THAT THE BREAKER FOR THE PV BACKFEED |
| | SHOULD BE A 300 AMP BREAKER, BUT THE PANEL SHOWS A 350 |
| | AMP BREAKER. PROVIDE CORRECTION. FBC 107.2.1; NEC |
| | 705.12(D) |
| | 10. PROVIDE DETAIL OF GROUNDING ELECTRODE SYSTEM FOR |
| | THE PV SYSTEM. NEC 690.47 |
| | 11. SHEET E-02 SHOWS THE AMBIENT TEMPERATURE SPECS |
| | BASED ON ?WHITE PLAINS WESTCHESTER CO A?. PROVIDE |
| | CORRECTION. FBC 107.2.1 |
| | 12. PROVIDE LABEL PER NEC 690.5. |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | |
| | SINCERELY, |
| | |
| | JOHN PEARSON |
| | ELECTRICAL PLANS EXAMINER |
| | 561-805-6746 |
| | [email protected] |
| | |
| | |