| Plan Review Stops For Permit 18030202 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2018-04-09 |
|
|
Cont ID |
|
| Sent By |
aclange |
Date |
2018-04-09 |
Time |
13:48 |
Rev Time |
0.00 |
| Received By |
aclange |
Date |
2018-04-09 |
Time |
13:43 |
Sent To |
|
|
| Notes |
| 2018-04-09 13:48:53 | PREVIOUSLY REVIEWED. NO OTHER CHANGES OTHER THAN | | | MECHANICAL RESUBMITTAL. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
P |
Date |
2018-03-19 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2018-03-19 |
Time |
07:37 |
Rev Time |
0.00 |
| Received By |
aclange |
Date |
2018-03-13 |
Time |
13:03 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2018-03-21 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2018-03-21 |
Time |
12:10 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2018-03-21 |
Time |
12:10 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
2018-03-20 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2018-03-20 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2018-03-13 |
Time |
11:02 |
Sent To |
|
|
| Notes |
| 2018-03-20 13:36:51 | THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC, | | | FIRE MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | PLEASE CONSIDER THE FOLLOWING AS PROVISO: | | | | | | THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED | | | AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE | | | PROVISO COMMENTS WILL RESULT IN A FAILED FIRE | | | INSPECTION. | | | | | | | | | 1) THERE IS A FIREPLACE INDICATED ON SHEET A6-31 AS | | | HEARTHCABINET MODEL NUMBER HC92000. I COULD NOT FIND | | | SPEC SHEETS WITH THIS SUBMITTAL NOR ONLINE TO VERIFY | | | ITS LISTING OR INSTALL RECOMMENDATIONS. | | | | | | AS TO NOT HOLD UP THIS PROJECT, PLEASE PROVIDE THE | | | SPECS AND LISTING AND ENSURE BOTH ARE COMPLIED WITH FOR | | | THE INSTALLATION. | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
2018-04-23 |
Time |
|
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2018-04-05 |
Time |
07:46 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2018-03-23 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2018-03-23 |
Time |
07:30 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2018-03-07 |
Time |
08:00 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2018-05-07 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2018-05-07 |
Time |
12:21 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2018-04-20 |
Time |
17:07 |
Sent To |
|
|
| Notes |
| 2018-05-07 08:18:59 | MECHANICAL PROVISO | | | 5/7/2018 | | | | | | 1) IN RESPONSE TO COMMENT #2 FROM THE 1ST REVIEW | | | CONCERNING THE INSTALLATION OF THE FIRE/SMOKE DAMPERS | | | IN THE FLAMEBAR DUCTS, THE INSTALLATIONS ARE GRANTED A | | | PROVISO PENDING FIELD APPROVAL BY CHIEF HAROLD MOSER. | | 2018-04-23 12:23:14 | 2ND REVIEW FBC-2010 MECHANICAL | | | THE BRISTOL | | | REVISION #18030202 | | | MASTER #15111020 | | | 4/23/18 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) IN RESPONSE TO COMMENT #2 FROM THE 1ST REVIEW | | | CONCERNING THE INSTALLATION OF THE FIRE/SMOKE DAMPERS | | | IN THE FLAMEBAR DUCTS, THE INSTALLATIONS ARE GRANTED A | | | PROVISO PENDING FIELD APPROVAL BY CHIEF HAROLD MOSER. | | | | | | 3) PLEASE EITHER UPDATE SHEET M2.55B (18-19 TIER 2) TO | | | MATCH THE REVISIONS SHOWN ON M2.55C (19 TIER 2) , OR | | | ELIMINATE M2.55B AND REVISE M2.55C TO INCLUDE THE 18TH | | | FLOOR. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE | | | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND | | | KEEP THEM WITH THE SUBMITTALS. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2018-03-21 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2018-03-21 |
Time |
15:28 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2018-03-19 |
Time |
18:00 |
Sent To |
|
|
| Notes |
| 2018-03-21 16:00:51 | 1ST REVIEW FBC-2010 MECHANICAL | | | THE BRISTOL | | | REVISION #18030202 | | | MASTER #15111020 | | | 3/21/18 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) SHEETS M2.05- M2.25: PLEASE CLARIFY THE PURPOSE OF | | | THE NEW SMOKE DAMPERS SHOWN ON THE O/A DUCT DROPS IN | | | THE NORTH AND SOUTH CORE CEILINGS. CLARIFY HOW THE | | | DAMPERS ARE TO BE ACTUATED AND IF THEY ARE PART OF THE | | | SMOKE CONTROL SYSTEM. UPDATE ALL CONTROL DETAILS IF | | | APPLICABLE. SUBMIT MANUFACTURER'S SPECIFICATIONS FOR | | | THE DAMPERS AND PROVIDE INSTALLATION DETAILS ON THE | | | PLAN. | | | | | | 2) M2.05- M2.25 PROVIDE MANUFACTURER'S SPECIFICATIONS | | | FOR THE FIRE/SMOKE DAMPERS SHOWN IN THE CORES WHERE THE | | | FLAMEBAR DUCT CONNECTS WITH THE CONVENTIONAL DUCTWORK. | | | THE SPECS MUST INDICATE THAT THE PROPOSED INSTALLATIONS | | | ARE CONSISTENT WITH THE UL 555, UL 555S, AND/OR UL 555C | | | TESTING STANDARDS- SECTION 607.3.1. | | | | | | 3) M2.26: IT APPEARS THAT THE 12X12 AIR INTAKE BY THE | | | NEW EF-R2 IS MISLABELED AND SHOULD BE LABELED AS AN | | | EXHAUST OUTLET. | | | | | | 4) M.55B: BESIDES THE RELOCATION OF ONE HP, THE PLAN IS | | | ALSO INDICATING OTHER HP CHANGES THROUGHOUT THE SPACE. | | | PLEASE PROVIDE A MORE DESCRIPTIVE NARRATIVE THAT | | | ITEMIZES ALL THE CHANGES, AND UPDATED ENERGY AND AC | | | CALCULATIONS IF APPLICABLE. | | | | | | 5) M.55C: TO HELP EXPEDITE THE REVIEW, PLEASE UPLOAD | | | THE ORIGINAL PLAN SHEET FOR COMPARISON. | | | | | | 6) M2.57B & M2.58B: THE DETAIL OF THE REROUTED DUCTS IN | | | THE UTILITY ROOM IS INCOMPLETE- THE RETURN GRILLS AND | | | FSD'S ARE NOT SHOWN. | | | | | | 7) M61.A: NO DUCTS ARE SHOWN ON THE PLAN- PLEASE | | | CLARIFY. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE | | | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND | | | KEEP THEM WITH THE SUBMITTALS. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
P |
Date |
2018-03-23 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2018-03-23 |
Time |
07:25 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2018-03-23 |
Time |
05:03 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
1 |
Status |
P |
Date |
2018-03-19 |
|
|
Cont ID |
|
| Sent By |
aclange |
Date |
2018-03-19 |
Time |
07:37 |
Rev Time |
0.00 |
| Received By |
aclange |
Date |
2018-03-19 |
Time |
07:37 |
Sent To |
|
|
| Notes |
| 2018-04-23 13:12:53 | MECH SIGS GOOD- CCOLE-4/23/18 | | 2018-03-23 07:29:41 | 3/23/18 DIG SIG OK ON PLUMB/GPJ | | 2018-03-21 17:40:04 | MECH DIG/SIGS GOOD- CCOLE-3/21/18 | | 2018-03-19 07:37:33 | SIGNATURES OK |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2018-03-21 |
|
|
Cont ID |
|
| Sent By |
jroach |
Date |
2018-03-21 |
Time |
16:23 |
Rev Time |
0.00 |
| Received By |
jroach |
Date |
2018-03-21 |
Time |
16:23 |
Sent To |
|
|
| Notes |
| 2018-03-21 16:24:41 | PLEASE NOTE THAT ALL PROVISOS LISTED ON THE ORIGINAL | | | APPROVED PERMIT REVIEW REMAIN ACTIVE AND SHALL BE | | | ADDRESSED ACCORDINGLY. | | | | | | QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING: | | | | | | JOHN P. ROACH, AICP, PRINCIPAL PLANNER | | | CITY OF WEST PALM BEACH | | | DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION | | | 401 CLEMATIS STREET - P.O. BOX 3147 | | | WEST PALM BEACH, FLORIDA 33402 | | | | | | P: 561.822.1448 | | | F: 561.822.1460 | | | | | | E: [email protected] | | | | | | W: WPB.ORG | | | |
|
|