| 2018-03-22 13:20:22 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE 2017 6TH ED. |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | 1. ONLY ONE SERVICE PER ADDRESS IS PERMITTED. PROVIDE |
| | CORRECTION. WPB FBC 107.2.1; NEC 230.2 |
| | 2. PROVIDE ACCURATE RISER DIAGRAM. RISER PROVIDED ONLY |
| | SHOWS EXISTING SERVICE. NEC 215.5, 230, 250.50, 250.94, |
| | 408.30 |
| | 3. RISER SHOWS THREE 3/0 CONDUCTORS IN A 2 INCH CONDUIT |
| | TO PANEL A. THIS CONDUIT IS REQUIRED TO HAVE AN |
| | EQUIPMENT GROUNDING CONDUCTOR. PROVIDE CORRECTION. NEC |
| | 250.122 |
| | 4. PROVIDE ACCURATE LOAD CALCULATION INCLUDING ALL |
| | LOADS. LOAD CALCULATION PROVIDED IS THE TYPE USED FOR A |
| | DWELLING UNIT AND IS NOT PERMITTED FOR THIS |
| | INSTALLATION. LOAD FOR TANKLESS WATER HEATER IS |
| | MISSING. NEC 220; FBC 107.2.1 |
| | 5. PROVIDE AIC RATING OF SERVICE DISCONNECT AND PANEL. |
| | NEC 110.3, 110.9 |
| | 6. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR EACH |
| | PANEL INCLUDING INFORMATION FROM THE POWER COMPANY |
| | STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR |
| | THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE |
| | SERVICE EQUIPMENT AND DOWNSTREAM PANELS IS ADEQUATE. |
| | NEC 110.9, 110.10 |
| | 7. PROVIDE NOTES TO INDICATE THE REQUIRED MARKING OF |
| | SERVICE EQUIPMENT FOR ARC FLASH HAZARD WARNING AND |
| | AVAILABLE FAULT CURRENT PER CODE. NEC 110.16, 110.24 |
| | 8. PROVIDE THE ADDITIONAL INTERIOR LIGHTING CONTROLS |
| | STIPULATED IN THE FBC ENERGY CODE. MANY AREAS DO NOT |
| | SHOW THE AUTOMATIC CONTROL REQUIRED. FBC EC C405.2 |
| | 9. PROVIDE RECEPTACLE CONTROL REQUIRED BY ASHREA 90.1: |
| | 8.4.2. PER THIS REQUIREMENT, THE FOLLOWING SHALL BE |
| | AUTOMATICALLY CONTROLLED: 1) AT LEAST 50% OF ALL |
| | 125-VOLT, 15 AND 20 AMP RECEPTACLES, IN ALL PRIVATE |
| | OFFICES, CONFERENCE ROOMS, ROOMS USED PRIMARILY FOR |
| | PRINTING AND/OR COPYING FUNCTIONS, BREAK ROOMS, |
| | CLASSROOMS, AND INDIVIDUAL WORKSTATIONS. 2) AT LEASE |
| | 25% OF BRANCH CIRCUIT FEEDERS INSTALLED FOR MODULAR |
| | FURNITURE NOT SHOWN ON THE CONSTRUCTION DOCUMENTS. FBC |
| | EC C405.6.1 |
| | 10. BE ADVISED THAT FIRE ALARM, LOW VOLTAGE SYSTEMS, |
| | DAS, LIGHTNING PROTECTION, GENERATORS, COMMERCIAL HOOD |
| | SYSTEMS, WALK IN COOLERS, SIGNS, SITE LIGHTING, AND |
| | SWIMMING POOLS (WHERE APPLICABLE) ARE NOT INCLUDED IN |
| | THE SCOPE OF THIS PLAN REVIEW. PROVIDE A BLOCK NOTE |
| | INDICATING THE REQUIRED SEPARATE PERMITS AND DATA |
| | SPECIFICATION SHEET SUBMITTALS FOR ANY OF THESE SYSTEMS |
| | PRESENT. WPB FBC 105.1, 107.2.1 |
| | 11. EMERGENCY AND EXIT LIGHTS ARE REQUIRED TO BE FED |
| | FROM THE GENERAL LIGHTING CIRCUIT IN THE AREA. PROVIDE |
| | CORRECTION. NEC 700.12(F) |
| | 12. CIRCUIT NUMBERS ON PLAN DO NOT MATCH WHAT IS LISTED |
| | IN PANEL SCHEDULES. PROVIDE CORRECTION. FBC 107.2.1 |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | |