| 2018-03-09 05:33:40 | 03/09/2019 1ST GAS REVIEW**DENIED** |
| | |
| | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| | TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS |
| | |
| | MASTER # 17090753 DID NOT HAVE A GAS REVIEW OR SHOW ANY |
| | OF THE APPLIANCES AS BEING GAS |
| | |
| | |
| | 1) PLEASE EXPLAIN HOW YOU CAME UP WITH THE 49' AS THE |
| | MOST REMOTE OUTLET OF THIS SYSTEM. SHOW THE DISTANCE |
| | FROM THE POINT OF DELIVERY, (GAS METER / MP REGULATOR / |
| | LP TANK) TO THE MOST REMOTE OUTLET IN THE BUILDING AND |
| | / OR SYSTEM PER THE 2014 FBC-FUEL GAS SEC.402.4.1 OR |
| | 2014 FBC-RES. SEC. G 2413.3 |
| | |
| | 2) SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE 2014 |
| | FBC-FUEL GAS CODE SEC.304.1, 614.5 (BOTH CLOTHES |
| | DRYERS) OR 2014 FBC-RES. SEC. G 2407.1 AND G2439.4 |
| | (BOTH CLOTHES DRYERS). SUBMIT COMBUSTION AIR |
| | CALCULATIONS FOR THE ADDED GAS APPLIANCES. WHERE |
| | COMBUSTION AIR IS PROVIDED BY THE BUILDING'S MECHANICAL |
| | VENTILATION SYSTEM, THE SYSTEM SHALL PROVIDE THE |
| | SPECIFIED COMBUSTION AIR RATE IN ADDITION TO THE |
| | REQUIRED VENTILATION AIR. FGC SEC.304.9.3 OR FBCR |
| | G2407.9.3. |
| | |
| | 3) SUBMIT MANUFACTURER'S SPECIFICATION SHEETS / |
| | INSTALLATION MANUAL FOR ALL GAS EQUIPMENT TO VERIFY |
| | COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58, AND |
| | FBC-2014 FUEL GAS CODE SEC. 402.2, AND 301.3 OR 2014 |
| | FBC-RES. SEC. G2404.3. GAS APPLIANCES SHALL BE LISTED |
| | AND LABELED. THE INSTALLATION MANUALS FOR ALL GAS |
| | APPLIANCES / EQUIPMENT SHALL BE ONSITE AT THE TIME OF |
| | INSPECTION. FGC SEC.305.1, FBC-RES. SEC.G2408.1 |
| | |
| | 4) SUBMIT TWO COPIES OF A HOUSE PLAN SHOWING THE |
| | LOCATION OF THE TANKLESS WATER HEATER AND THE LOCATION |
| | AND DISTANCE OF ANY OPERABLE DOORS OR WINDOWS IN |
| | RELATION TO THE WATER HEATER. THE LOCATION OF THE WATER |
| | HEATER SHALL COMPLY WITH THE MANUFACTURER'S |
| | INSTALLATION INSTRUCTIONS. THE HOUSE PLAN CAN BE HAND |
| | DRAWN. WPB AMEND. TO FBC SEC. 107.2.1. |
| | |
| | 5) SHOW THE LOCATION OF ALL MP (STEP-DOWN) R. A LISTED |
| | SHUTOFF VALVE SHALL BE INSTALLED IMMEDIATELY AHEAD OF |
| | EACH MP REGULATOR. FBC-FUEL GAS SEC.409.4, |
| | FBC-RESIDENTIAL SEC. G 2420.4. |
| | |
| | 6) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE |
| | PRESSURE REGULATORS. REGULATORS INSTALLED ON THE |
| | EXTERIOR OF THE BUILDING SHALL BE APPROVED FOR OUTDOOR |
| | INSTALLATION. 2014 FGC SEC.410.1. |
| | |
| | 7) SHOW THE DISTANCE FROM THE 2 PSI REGULATOR TO THE |
| | APPLIANCE AND THE TOTAL LOAD ON EACH REGULATOR. COMPLY |
| | WITH 2014 FBC-FUEL GAS TABLE 402.4 (28) FOR THE PROPER |
| | PIPE SIZE AND BTU LOAD. |
| | |
| | 8) VALUE- THE VALUE OF GAS APPLIANCES MUST BE INCLUDED |
| | IN THIS PERMIT AS THEY WERE NOT INCLUDED IN THE MASTER |
| | PERMIT# 17090753. |
| | 109.3 BUILDING PERMIT VALUATIONS. IF, IN THE OPINION OF |
| | THE BUILDING OFFICIAL, THE CLAIMED VALUATION OF |
| | BUILDING, ALTERATION, STRUCTURE, ELECTRICAL, GAS, |
| | MECHANICAL OR PLUMBING SYSTEMS APPEARS TO BE |
| | UNDERESTIMATED ON THE APPLICATION, THE PERMIT SHALL BE |
| | DENIED, UNLESS THE APPLICANT CAN SHOW |
| | DETAILED, QUANTITY ESTIMATES, AND/OR BONA FIDE SIGNED |
| | CONTRACTS (EXCLUDING LAND VALUE) TO MEET THE |
| | APPROVAL OF THE BUILDING OFFICIAL. FOR PERMITTING |
| | PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS SHALL |
| | BE TOTAL REPLACEMENT VALUE TO INCLUDE STRUCTURAL, |
| | ELECTRIC, PLUMBING, MECHANICAL, INTERIOR FINISH, |
| | RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN FEES, |
| | MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING |
| | ONLY LAND VALUE. VALUATION REFERENCES MAY INCLUDE THE |
| | LATEST PUBLISHED DATA OF NATIONAL CONSTRUCTION |
| | COST ANALYSIS SERVICES (MARSHALL-SWIFT, MEANS, ETC.), |
| | AS PUBLISHED BY INTERNATIONAL CODE CONGRESS. |
| | FINAL BUILDING PERMIT VALUATION SHALL BE SET BY THE |
| | BUILDING OFFICIAL. |
| | |
| | 9) YOU INDICATE A TANKLESS WATER HEATER ON YOU |
| | ISOMETRIC BUT IT IS NOT INCLUDED ON YOUR PROPOSAL. FBC |
| | 107.2.1 |
| | |
| | |
| | TIM HUNT |
| | PLUMBING INSPECTOR / PLUMBING PLAN REVIEWER |
| | CITY OF WEST PALM BEACH DEVELOPMENT SERVICES DEPARTMENT |