Plan Review Details - Permit 18030096
Plan Review Stops For Permit 18030096
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2018-04-20 Cont ID  
Sent By shill Date 2018-04-20 Time 13:59 Rev Time 0.00
Received By shill Date 2018-04-20 Time 13:53 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-03-21 Cont ID  
Sent By jgomez Date 2018-03-21 Time 18:18 Rev Time 0.00
Received By jgomez Date 2018-03-21 Time 17:28 Sent To  
Notes
2018-03-21 17:42:16RESIDENTIAL (R3) ALTERATION, BUILDING REVIEW COMMENTS
 CODE: FBC 6TH EDITION (2017).
  
 1- CLEARLY SPECIFY ALL STRUCTURAL L CONNECTORS FOR ALL
 NEW (2)2X12 STRUCTURAL HEADERS AND 4X4 POSTS SHOWN ON
 SHEET 1.1. ALSO, SPECIFY POSTS CONNECTIONS AT BOTTOM TO
 SHOW COMPLIANCE WITH THE LOAD PATH OF SEC. R601.2
 FBC-RESIDENTIAL.
  
 R601.2 REQUIREMENTS.
 WALL CONSTRUCTION SHALL BE CAPABLE OF ACCOMMODATING ALL
 LOADS IMPOSED IN ACCORDANCE WITH SECTION R301 AND OF
 TRANSMITTING THE RESULTING LOADS TO THE SUPPORTING
 STRUCTURAL ELEMENTS.
  
 2- IT LOOKS LIKE THIS BUILDINGS LOCATED IN EXPOSURE "D"
 NOT "C" AS SPECIFIED ON DESIGN PARAMETERS ON SHEET 1.1.
 REVISE AS REQUIRED.
  
 R301.2.1.4.3 EXPOSURE CATEGORIES.
 AN EXPOSURE CATEGORY SHALL BE DETERMINED IN ACCORDANCE
 WITH THE FOLLOWING:
 EXPOSURE D. EXPOSURE D SHALL APPLY WHERE THE GROUND
 SURFACE ROUGHNESS, AS DEFINED BY SURFACE ROUGHNESS D,
 PREVAILS IN THE UPWIND DIRECTION FOR A DISTANCE OF AT
 LEAST 5,000 FEET (1524 M) OR 20 TIMES THE HEIGHT OF THE
 BUILDING, WHICHEVER IS GREATER. EXPOSURE D SHALL ALSO
 APPLY WHERE THE GROUND SURFACE ROUGHNESS IMMEDIATELY
 UPWIND OF THE SITE IS B OR C, AND THE SITE IS WITHIN A
 DISTANCE OF 600 FEET (183 M) OR 20 TIMES THE BUILDING
 HEIGHT, WHICHEVER IS GREATER, FROM AN EXPOSURE D
 CONDITION AS DEFINED IN THE PREVIOUS SENTENCE.
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date   Cont ID  
Sent By   Date 2018-03-12 Time   Rev Time 0.00
Received By jleahy Date 2018-03-12 Time 09:07 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status P Date 2018-03-21 Cont ID  
Sent By jgomez Date 2018-03-21 Time 17:42 Rev Time 0.00
Received By jgomez Date 2018-03-21 Time 17:42 Sent To  
Notes
2018-03-21 17:42:55GAS RANGE RELOCATION. SEPARATE PERMIT REQUIRED.

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2018-04-25 Cont ID  
Sent By shill Date 2018-04-25 Time 06:10 Rev Time 0.00
Received By shill Date 2018-04-23 Time 12:51 Sent To  
Notes
2018-04-24 12:51:58HARD COPIES FOR SIGNATURE ROUTED TO SHILL

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-04-20 Cont ID  
Sent By shill Date 2018-04-20 Time 13:59 Rev Time 0.00
Received By shill Date 2018-04-06 Time 14:40 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-03-21 Cont ID  
Sent By jgomez Date 2018-03-21 Time 19:02 Rev Time 0.00
Received By jgomez Date 2018-03-05 Time 15:34 Sent To I
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2018-03-21 Cont ID  
Sent By jgomez Date 2018-03-21 Time 17:43 Rev Time 0.00
Received By jgomez Date 2018-03-21 Time 17:43 Sent To  
Notes
2018-03-21 17:44:16NO MECHANICAL WORK SHOWN.

Review Stop P PLUMBING
Rev No 1 Status P Date 2018-03-21 Cont ID  
Sent By jgomez Date 2018-03-21 Time 19:02 Rev Time 0.00
Received By jgomez Date 2018-03-21 Time 19:02 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2018-04-25 Cont ID  
Sent By shill Date 2018-04-25 Time 06:10 Rev Time 0.00
Received By shill Date 2018-04-25 Time 06:09 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2018-04-20 Cont ID  
Sent By shill Date 2018-04-20 Time 13:58 Rev Time 0.00
Received By shill Date 2018-04-20 Time 13:58 Sent To  
Notes
2018-04-20 13:59:32****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 PLANS ARE NOT DIGITALLY SIGNED AND SEALED. YOU MAY
 SUBMIT ORIGINAL SIGNED AND SEALED DOCUMENTS AS A
 "SUBMITTAL" AT THE BUILDING DIVISION TO RESOLVE THIS
 COMMENT, FS471, 481.
  
  