Plan Review Details - Permit 18030077
Plan Review Stops For Permit 18030077
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-03-16 Cont ID  
Sent By jwitmer Date 2018-03-16 Time 08:17 Rev Time 0.00
Received By jwitmer Date 2018-03-15 Time 16:31 Sent To  
Notes
2018-03-16 08:17:352017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 18030077
 ADD: 4106 BROADWAY SUITE: 4104
 CONT: ACTION MECHANICAL CONTRACTORS INC.
 TEL: 561-642-4730
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: THURS. MARCH 15/ 2018
 ACTION: DENIED
  
 1)SHEET A1. PLEASE UPDATE THE CODE FROM THE 2014 FBC TO
 THE 2017 FBC. PLEASE NOTE ON DEC. 31 / 2017 THE 2017
 FLORIDA BUILDING CODE WERE ADOPTED STATEWIDE.
  
 2) SHEET A1. PLEASE CORRECT THE OCCUPANCY TYPE THIS IS
 NOT A A2 OCCUPANCY, THERE WOULD NEED TO BE A MINIMUM OF
 50 OCCUPANTS IN A RESTAURANT. THE TENANT SPACE IS A
 CHANGE IN USE BUT STILL A MERCANTILE OCCUPANCY. FBC-B
 309.1 MERCANTILE GROUP M OCCUPANCY INCLUDES, AMONG
 OTHERS, THE USE OF A BUILDING OR STRUCTURE OR A PORTION
 THEREOF FOR THE DISPLAY AND SALE OF MERCHANDISE, AND
 INVOLVES STOCKS OF GOODS, WARES OR MERCHANDISE
 INCIDENTAL TO SUCH PURPOSES AND ACCESSIBLE TO THE
 PUBLIC.
  
 3) THE WORK INVOLVED IN THIS CHANGE IN USE WILL REQUIRE
 A BUILDING PERMIT AS WELL AS THE MECHANICAL PERMIT.
 EITHER A BUILDING CONTRACTOR OR GENERAL CONTRACTOR WILL
 BE REQUIRED TO SIGN ONTO A BUILDING PERMIT. F. S.
 489.105 DEFINITIONS, GENERAL CONTRACTOR OR BUILDING
 CONTRACTOR. F. S. 489.113 QUALIFICATIONS FOR PRACTICE;
 RESTRICTIONS.
  
 4) PLEASE NOTE THE WORK BEING COMPLETED UNDER THIS
 PERMIT AND PERMIT 17030415 (GAS) IS CREATING A CHANGE
 IN USE, A COMMERCIAL KITCHEN AND WILL NEED TO SHOW
 COMPLIANCE WITH THE:
  
 2017 FLORIDA EXISTING BUILDING CODE SECTION 1001.2.1
 CHANGE OF USE. ANY WORK UNDERTAKEN IN CONNECTION WITH A
 CHANGE IN USE THAT DOES NOT INVOLVE A CHANGE OF
 OCCUPANCY CLASSIFICATION OR A CHANGE TO ANOTHER GROUP
 WITHIN AN OCCUPANCY CLASSIFICATION SHALL CONFORM TO THE
 APPLICABLE REQUIREMENTS FOR THE WORK AS CLASSIFIED IN
 CHAPTER 5 AND TO THE REQUIREMENTS OF SECTIONS 1002
 THROUGH 1011.
  
 1010.1 EXIST. BLDG CODE. 1010.1. WHERE THE OCCUPANCY OF
 AN EXISTING BUILDING OR PART OF AN EXISTING BUILDING IS
 CHANGED SUCH THAT THE NEW OCCUPANCY IS SUBJECT TO
 DIFFERENT PLUMBING FIXTURE REQUIREMENTS IN ACCORDANCE
 WITH THE FLORIDA BUILDING CODE, PLUMBING, THE NEW
 OCCUPANCY SHALL COMPLY WITH THE INTENT OF THE
 RESPECTIVE FLORIDA BUILDING CODE, PLUMBING PROVISIONS.
  
 2017 FBC-B 2902.3.6 PROHIBITED TOILET ROOM LOCATION.
 TOILET ROOMS SHALL NOT OPEN DIRECTLY INTO A ROOM USED
 FOR THE PREPARATION OF FOOD FOR SERVICE TO THE PUBLIC.
  
 5) THE 2ND PROBLEM WITH THE LOCATION WITH THE EXISTING
 LOCATION OF THE RESTROOM IN A COMMERCIAL KITCHEN IS THE
 OCCUPANTS CANNOT GO THROUGH THE KITCHEN TO GAIN ENTRY
 OF THE RESTROOM. 2017 FBC-B 1016.2 EGRESS THROUGH
 INTERVENING SPACES. EGRESS THROUGH INTERVENING SPACES
 SHALL COMPLY WITH THIS SECTION. (5.) EGRESS SHALL NOT
 PASS THROUGH KITCHENS, STORAGE ROOMS, CLOSETS OR SPACES
 USED FOR SIMILAR PURPOSES.
  
 6) SHEET M2 SHOWS A NEW ROOF TOP 3 TON A/C UNIT AND A
 NEW ROOF EXHAUST FAN. THE ARCHITECTURAL SHEET NOR THE
 MECHANICAL SHEETS SHOW THE TYPE OF ROOF FRAMING SYSTEM
 IS WITHIN THIS TENANT SPACE NOR HOW THE PENETRATION
 THROUGH THE ROOF DECK WILL BE MADE NOR THE REQUIRED
 EXTRA FRAMING AROUND THE NEW PENETRATION, IF EXTRA
 FRAMING MEMBERS WILL BE REQUIRED, NOR THE TYPE OF ROOF
 CURB, AND THE ANCHORING OF THE ROOF CURB TO THE ROOF
 FRAMING MEMBERS.
  
 LATERAL FORCE-RESISTING SYSTEM. FOR ALL ROOF TOP
 EQUIPMENT, CURBS, FANS OR A/C STANDS, AND OR VENTS,
 DETAILED ATTACHMENT TO THE ROOF FRAMING & DECK AS WELL
 AS FROM THE CURB OR ROOF STAND TO THE EQUIPMENT ABOVE.
  
 2017 FBC-B 1604.4 ANALYSIS. LOAD EFFECTS ON STRUCTURAL
 MEMBERS AND THEIR CONNECTIONS SHALL BE DETERMINED BY
 METHODS OF STRUCTURAL ANALYSIS THAT TAKE INTO ACCOUNT
 EQUILIBRIUM, GENERAL STABILITY, GEOMETRIC COMPATIBILITY
 AND BOTH SHORT- AND LONG-TERM MATERIAL PROPERTIES.
 EVERY STRUCTURE SHALL BE DESIGNED TO RESIST THE
 OVERTURNING EFFECTS CAUSED BY THE LATERAL FORCES
 SPECIFIED IN THIS CHAPTER. SEE SECTION 1609 FOR WIND
 LOADS.
  
 7) PLEASE PROVIDE THE WIND DESIGN CRITERIA FOR THE ROOF
 TOP UNIT.
  
 2017 FBC-B 1603.1.4 WIND DESIGN DATA.
 THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL
 BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE
 DESIGN OF THE LATERAL FORCE-RESISTING SYSTEM OF THE
 STRUCTURE:
  
 7.1. ULTIMATE DESIGN WIND SPEED, VULT, (3-SECOND GUST),
 MILES PER HOUR (KM/HR) AND NOMINAL DESIGN WIND SPEED,
 VASD, AS DETERMINED IN ACCORDANCE WITH SECTION
 1609.3.1.
  
 7.2. RISK CATEGORY.
  
 7.HEIGHT AND EXPOSURE.
  
 7.4. APPLICABLE INTERNAL PRESSURE COEFFICIENT.
  
 7.DESIGNED BY THE REGISTERED DESIGN PROFESSIONAL
 RESPONSIBLE FOR THE DESIGN OF THE STRUCTURE, PSF.
 TABLE 1609.7(2) ADJUSTMENT FACTORS FOR HEIGHT &
 EXPOSURE. PROVIDE THE MEAN ROOF HEIGHT FOR THE
 BUILDING.
 1609.3.1 WIND SPEED CONVERSION VULT TO VASD.
  
 8) 2014 / 2017 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005,
 RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS
 OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS:
 (31(D) ROOFING PRODUCTS AND ASSEMBLIES, ROOF TOP CURBS
 OR VENTILATORS (NOT REVIEWED BY THE DESIGNER OF RECORD,
 SHOP DRAWING STAMP OF APPROVAL).
  
 9) W. P. B. 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 10) PLEASE BE AWARE WITH THE MOVING OF THE RESTROOM
 FROM BEING IN THE KITCHEN PLEASE KEEP IN MIND THE NEW
 RESTROOM WILL NEED TO MEET ALL OF THE RESTROOM
 REQUIREMENTS OF THE 2017 FBC-ACCESSIBILITY CODE IN
 CHAPTER 6.
  
 11) PLEASE ALSO BE AWARE THAT YOU WILL NEED TO DECLARE
 COMPLIANCE WITH DISPROPORTIONATE COST OF THE:
  
 2017 ACCESSIBILITY CODE. 202.4.1 DISPROPORTIONATE COST.
 ALTERATIONS MADE TO PROVIDE AN ACCESSIBLE PATH OF
 TRAVEL TO THE ALTERED AREA WILL BE DEEMED
 DISPROPORTIONATE TO THE OVERALL ALTERATION WHEN THE
 COST EXCEEDS 20% OF THE COST OF THE ALTERATION TO THE
 PRIMARY FUNCTION AREA. COSTS THAT MAY BE COUNTED AS
 EXPENDITURES REQUIRED TO PROVIDE AN ACCESSIBLE PATH OF
 TRAVEL MAY INCLUDE: (I) COSTS ASSOCIATED WITH PROVIDING
 AN ACCESSIBLE ENTRANCE AND AN ACCESSIBLE ROUTE TO THE
 ALTERED AREA; (II) COSTS ASSOCIATED WITH MAKING
 RESTROOMS ACCESSIBLE, SUCH AS INSTALLING GRAB BARS,
 ENLARGING TOILET STALLS, INSULATING PIPES, OR
 INSTALLING ACCESSIBLE FAUCET CONTROLS; (III) COSTS
 ASSOCIATED WITH PROVIDING ACCESSIBLE TELEPHONES, SUCH
 AS RELOCATING THE TELEPHONE TO AN ACCESSIBLE HEIGHT,
 INSTALLING AMPLIFICATION DEVICES, OR INSTALLING A TEXT
 TELEPHONE (TTY); (IV) COSTS ASSOCIATED WITH RELOCATING
 AN INACCESSIBLE DRINKING FOUNTAIN.
  
 12) WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES
 AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 DEVELOPMENT SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-03-16 Cont ID  
Sent By jpearson Date 2018-03-16 Time 11:00 Rev Time 0.00
Received By jpearson Date 2018-03-16 Time 09:03 Sent To  
Notes
2018-03-16 11:00:20CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. THE NEC AND FBC SPECIFIED FOR DESIGN IS NOT THE
 CURRENT CODE. PROVIDE CORRECTION. FBC PREFACE (ALSO SEE
 CURRENT CODES ABOVE)
 2. PROVIDE ACCURATE LOAD CALCULATION FOR SERVICE,
 INCLUDE EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF
 SERVICE IS ADEQUATE. CURRENT CALCULATION USES THE
 SMALLER OF THE AC EQUIPMENT LOAD AND SHOULD USE THE
 LARGER OF THE TWO. ADDITIONALLY, SERVICE SHOULD BE
 SIZED FOR 125% OF CONTINUOUS LOADS PLUS 100% OF THE
 NON-CONTINUOUS LOADS. PROVIDE CORRECTIONS. NEC 215.2,
 220, 220.60, 408.30
 3. BASED ON COMMENT NUMBER 2, IT APPEARS THAT THE
 CURRENT SERVICE IS NOT ADEQUATE FOR THE ADDITIONAL
 LOAD. PROVIDE CORRECT SIZE SERVICE FOR LOAD IF
 CALCULATION DEMANDS. NEC 230.79
 4. IF SERVICE IS TO BE REPLACED, PROVIDE AVAILABLE
 SHORT CIRCUIT CALCULATION FOR EACH PANEL INCLUDING
 INFORMATION FROM THE POWER COMPANY STATING WHAT THE
 AVAILABLE SHORT CIRCUIT CURRENT IS FOR THE SERVICE TO
 CONFIRM THE STATED AIC RATING OF THE SERVICE EQUIPMENT
 AND DOWNSTREAM PANELS IS ADEQUATE. NEC 110.9, 110.10
 5. PROVIDE THE REQUIRED SERVICE AREA RECEPTACLE PER
 CODE. NEC 210.64
 6. PROVIDE GFCI PROTECTED OUTLET FOR SERVICING OF A/C
 EQUIPMENT PER CODE. NEC 210.63
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2018-03-19 Cont ID  
Sent By pleduc Date 2018-03-19 Time   Rev Time 0.00
Received By pleduc Date 2018-03-19 Time 11:21 Sent To  
Notes
2018-03-19 12:55:31THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) SHEET A 1 - THIS PROJECT APPEARS TO BE AN OCCUPANCY
 CHANGE. PLEASE INDICATE THE EXISTING OCCUPACNY AND
 PROPOSED OCCUPANCY. THE PROPOSED APPEARS TO BE
 MERCANTILE
  
 PER NFPA 101, CHAPTER 6, OCCUPANCY CLASSIFICATION
  
 6.1 CLASSIFICATION OF OCCUPANCY.
 6.1.1 GENERAL.
 6.1.1.1 OCCUPANCY CLASSIFICATION. THE OCCUPANCY OF A
 BUILDING OR
 STRUCTURE, OR PORTION OF A BUILDING OR STRUCTURE, SHALL
 BE CLASSIFIED IN
 ACCORDANCE WITH 6.1.2 THROUGH 6.1.13. OCCUPANCY
 CLASSIFICATION SHALL BE
 SUBJECT TO THE RULING OF THE AUTHORITY HAVING
 JURISDICTION WHERE THERE IS A
 QUESTION OF PROPER CLASSIFICATION IN ANY INDIVIDUAL
 CASE.
  
 PLEASE PROVIDE THE ACCURATE OCCUPANCY.
  
  
 2) SHEET A 1 - THE INDICATED OCCUPACNY LOAD APPEARS TO
 BE LOW AND INCORRECT.
  
 PER # 1 ABOVE PROVIDE AN ACCURATE OCCUPANCY LOAD PER
 NFPA 101. CHAPTER 7, MEANS OF EGRESS
  
 7.3.1.2* OCCUPANT LOAD FACTOR. THE OCCUPANT LOAD IN ANY
 BUILDING OR PORTION THEREOF SHALL BE NOT LESS THAN THE
 NUMBER OF
 PERSONS DETERMINED BY DIVIDING THE FLOOR AREA ASSIGNED
 TO THAT USE
 BY THE OCCUPANT LOAD FACTOR FOR THAT USE AS SPECIFIED
 IN TABLE
 7.3.1.2, FIGURE 7.3.1.2 (A), AND FIGURE 7.3.1.2(B).
 WHERE BOTH
 GROSS AND NET AREA FIGURES ARE GIVEN FOR THE SAME
 OCCUPANCY,
 CALCULATIONS SHALL BE MADE BY APPLYING THE GROSS AREA
 FIGURE TO THE
 GROSS AREA OF THE PORTION OF THE BUILDING DEVOTED TO
 THE USE FOR
 WHICH THE GROSS AREA FIGURE IS SPECIFIED AND BY
 APPLYING THE NET
 AREA FIGURE TO THE NET AREA OF THE PORTION OF THE
 BUILDING DEVOTED TO
 THE USE FOR WHICH THE NET AREA FIGURE IS SPECIFIED.
  
  
  
 3) SHEET A 1 - SHELVING AND AISLES ARE INDICATED. THE
 TOTAL WIDTH OF THE PROPOSED IS INDICATED A 15'. THERE
 ARE THRESS AISLES INDICATED AS 37 1/4" - 37" - 37 1/2"
 WHICH LEAVES ABOUT 33" FOR SHELVING.
  
 THOUGH THE DRAWING IS NOT TO SCALE, IT DOES APPEAR
 APPEAR TO BE ENOUGH ROOM FOR THE AMOUNT OF SHELVING.
  
 PLEASE REVIEW AND CORRECT OR JUSTIFY.
  
  
  
  
 4) SHEET M 1 - THERE IS NO HOOD DUCT WORK INDICATED.
  
 36.3.2.3* COMMERCIAL COOKING OPERATIONS. COMMERCIAL
 COOKING OPERATIONS SHALL BE PROTECTED IN ACCORDANCE
 WITH 9.2.3,
 UNLESS THE COOKING EQUIPMENT IS ONE OF THE FOLLOWING
 TYPES:
 (1) OUTDOOR EQUIPMENT
 (2) EQUIPMENT USED ONLY FOR FOOD WARMING
  
 NFPA 101, CHAPTER 9
  
 9.2.3 COMMERCIAL COOKING OPERATIONS. WHERE REQUIRED BY
 ANOTHER
 SECTION OF THIS CODE, COMMERCIAL COOKING OPERATIONS
 SHALL BE PROTECTED
 IN ACCORDANCE WITH NFPA 96, STANDARD FOR VENTILATION
 CONTROL AND
 FIRE PROTECTION OF COMMERCIAL COOKING OPERATIONS,
 UNLESS SUCH
 INSTALLATIONS ARE APPROVED EXISTING INSTALLATIONS,
 WHICH SHALL BE
 PERMITTED TO BE CONTINUED IN SERVICE.
  
 NFPA 96,
  
 CHAPTER 4 GENERAL REQUIREMENTS
 4.1 GENERAL.
 4.1.1 COOKING EQUIPMENT USED IN PROCESSES PRODUCING
 SMOKE OR GREASE-LADEN VAPORS SHALL BE EQUIPPED WITH AN
 EXHAUST
 SYSTEM THAT COMPLIES WITH ALL THE EQUIPMENT AND
 PERFORMANCE
 REQUIREMENTS OF THIS STANDARD.
  
 PLEASE PRVIDE DUCT DETAILS PER THE REQUIREMENTS.
  
  
  
  
 5) A HOOD FIRE SUPPRESSION SYSTEM IS REQUIRED AND SHALL
 BE SUBMITTED UNDER SEPARATE PERMIT IN COMPLIANCE WITH
 THE APPLICABLE FIRE CODES
  
  
  
 6) SHEET GAS - THERE IS NO INDICATION WITH COMPLAINCE
 WITH NFPA CODES.
  
 36.5 BUILDING SERVICES.
 36.5.1 UTILITIES. UTILITIES SHALL COMPLY WITH THE
 PROVISIONS OF SECTION
 9.1.
  
  
 9.1 UTILITIES.
 9.1.1 GAS. EQUIPMENT USING GAS AND RELATED GAS PIPING
 SHALL BE IN
 ACCORDANCE WITH NFPA 54, NATIONAL FUEL GAS CODE, OR
 NFPA 58,
 LIQUEFIED PETROLEUM GAS CODE, UNLESS SUCH INSTALLATIONS
 ARE APPROVED
 EXISTING INSTALLATIONS, WHICH SHALL BE PERMITTED TO BE
 CONTINUED IN
 SERVICE.
  
  
 PLEASE REVIEW TO ENSURE COMPLAINCE AND PROVIDE A
 APPLICABLE NOTE OF ACKNOWLEDGEMENT.
  
  
  
  
 7) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 8) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2018-03-17 Cont ID  
Sent By gjohnson Date 2018-03-17 Time 09:47 Rev Time 0.00
Received By gjohnson Date 2018-03-17 Time 09:47 Sent To  
Notes
2018-03-17 09:50:341ST REVIEW: FBC 2017 6TH EDITION
  
 PLUMBING COMMENTS:
  
 1. PERMIT RECORDS SHOW EXISTING GAS SYSTEM PLEASE SHOW
 EXISTING GAS LOADS AND PIPING ON RISER DIAGRAM. PER WPB
 AMEND TO FBC 107.2.1
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-04-02 Cont ID  
Sent By eschneid Date 2018-04-02 Time 13:48 Rev Time 0.00
Received By eschneid Date 2018-03-02 Time 09:59 Sent To  
Notes
2018-03-13 09:59:253.13.18 - B11
2018-03-06 09:59:56ROUTED TO MECHANICAL INBOX

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2018-03-13 Cont ID  
Sent By ccole Date 2018-03-13 Time 10:02 Rev Time 0.00
Received By ccole Date 2018-03-06 Time 11:10 Sent To  
Notes
2018-03-13 10:08:241ST REVIEW FBC-2017 MECHANICAL & ENERGY CONSERVATION
 CODES, WEST PALM BEACH AMENDMENTS TO THE FBC.
 PERMIT #18030077
 3/13/18
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE PERMIT APPLICATION AND VALUE ARE INDICATING ONLY
 THE INSTALLATION OF A KITCHEN HOOD, HOWEVER THE PLANS
 ARE INDICATING A TENANT BUILD-OUT WHICH WILL REQUIRE A
 GENERAL CONTRACTOR TO SUBMIT AN APPLICATION WITH AN
 ACCURATE WORK DESCRIPTION, AND A VALUE THAT WILL
 INCLUDE ALL PHASES OF THE PROJECT- BUILDING,
 MECHANICAL, ELECTRICAL, AND PLUMBING/GAS- SEE SECTIONS
 107 AND 109.3 WPB AMENDMENTS TO THE FBC. THE SUBMITTED
 PLANS AS THEY ARE NOW RECEIVING A FULL REVIEW BY THE
 BUILDING, FIRE, AND PLANNING AND ZONING DEPARTMENTS.
  
 2) PROVIDE AIR BALANCE CALCULATIONS ON THE PLAN IN THE
 FORM OF A SCHEDULE THAT INDICATES ALL EXHAUST AND
 REPLACEMENT AIR FOR THE FACILITY, PLUS THE NET
 EXFILTRATION IF APPLICABLE. THE TOTAL REPLACEMENT
 AIRFLOW RATE SHALL EQUAL THE TOTAL EXHAUST AIRFLOW RATE
 PLUS THE NET EXFILTRATION- SECTION 508.1.2.
  
 3) VERIFY THAT THE TEMPERATURE DIFFERENTIAL BETWEEN THE
 EXHAUST HOOD MAKEUP AIR AND THE AIR IN THE CONDITIONED
 SPACE DOES NOT EXCEED 10 DEGREES F- SECTION 508.1.1.
  
 4) VERIFY COMPLIANCE WITH SECTION C403.2.8 FLORIDA
 ENERGY CONSERVATION CODE PERTAINING TO THE KITCHEN
 EXHAUST SYSTEM:
  
 C403.2.8: REPLACEMENT AIR INTRODUCED DIRECTLY INTO THE
 EXHAUST HOOD CAVITY SHALL NOT BE GREATER THAN 10
 PERCENT OF THE HOOD EXHAUST AIRFLOW RATE. CONDITIONED
 SUPPLY AIR DELIVERED TO ANY SPACE SHALL NOT EXCEED THE
 GREATER OF THE FOLLOWING:
  
 1.THE VENTILATION RATE REQUIRED TO MEET THE SPACE
 HEATING OR COOLING LOAD.
 2.THE HOOD EXHAUST FLOW MINUS THE AVAILABLE TRANSFER
 AIR FROM ADJACENT SPACE WHERE AVAILABLE TRANSFER AIR IS
 CONSIDERED THAT PORTION OF OUTDOOR VENTILATION AIR NOT
 REQUIRED TO SATISFY OTHER EXHAUST NEEDS, SUCH AS
 RESTROOMS, AND NOT REQUIRED TO MAINTAIN PRESSURIZATION
 OF ADJACENT SPACES.
 WHERE TOTAL KITCHEN HOOD EXHAUST AIRFLOW RATE IS
 GREATER THAN 5,000 CFM (2360 L/S), EACH HOOD SHALL BE A
 FACTORY BUILT COMMERCIAL EXHAUST HOOD LISTED BY A
 NATIONALLY RECOGNIZED TESTING LABORATORY IN COMPLIANCE
 WITH UL 710. EACH HOOD SHALL HAVE A MAXIMUM EXHAUST
 RATE AS SPECIFIED IN TABLE C403.2.8 AND SHALL COMPLY
 WITH ONE OF THE FOLLOWING:
 1.NOT LESS THAN 50 PERCENT OF ALL REPLACEMENT AIR SHALL
 BE TRANSFER AIR THAT WOULD OTHERWISE BE EXHAUSTED.
 2.DEMAND VENTILATION SYSTEMS ON NOT LESS THAN 75
 PERCENT OF THE EXHAUST AIR THAT ARE CAPABLE OF NOT LESS
 THAN A 50-PERCENT REDUCTION IN EXHAUST AND REPLACEMENT
 AIR SYSTEM AIRFLOW RATES, INCLUDING CONTROLS NECESSARY
 TO MODULATE AIRFLOW IN RESPONSE TO APPLIANCE OPERATION
 AND TO MAINTAIN FULL CAPTURE AND CONTAINMENT OF SMOKE,
 EFFLUENT AND COMBUSTION PRODUCTS DURING COOKING AND
 IDLE.
 3.LISTED ENERGY RECOVERY DEVICES WITH A SENSIBLE HEAT
 RECOVERY EFFECTIVENESS OF NOT LESS THAN 40 PERCENT ON
 NOT LESS THAN 50 PERCENT OF THE TOTAL EXHAUST AIRFLOW.
  
 5) PROVIDE AN ELEVATION VIEW OF THE NEW HOOD AND THAT
 SHOWS THE FOLLOWING: A)THE VERTICAL DISTANCE BETWEEN
 THE FRONT LOWER LIP OF THE HOOD AND THE TOP HORIZONTAL
 SURFACE OF THE COOKING APPLIANCES ON ALL OPEN SIDES-
 SECTION 507.4.1. B) THE EXHAUST AND MAKEUP AIR SUPPLY
 DUCT RUNS AND CONNECTIONS TO THE HOOD, INCLUDING THE
 DIMENSIONS OF THE DUCTS AND THE REQUIRED MINIMUM 18"
 CLEARANCE TO COMBUSTIBLES FOR THE GREASE DUCT. PLEASE
 NOTE IF FIREWRAPPING IS TO BE USED, THE DRAWING SHALL
 SHOW THE WRAPPING IN PLACE FROM OUTLET TO TERMINATION-
 SECTION 506.3.6. C) THE EXHAUST FAN AND EXHAUST OUTLET
 HEIGHT ABOVE THE FINISHED ROOF SURFACE- SECTION
 506.3.13.1
  
 6) THE HOOD SHALL BE INSTALLED WITH NOT LESS THAN 18"
 CLEARANCE TO COMBUSTIBLES. BECAUSE THE HOOD IS ADJACENT
 TO THE WALL, IT IS REQUIRED THAT THE WALL BE OF
 NON-COMBUSTIBLE CONSTRUCTION WITH WITH MINIMUM 1/2"
 THICK GYPSUM WALLBOARD OR CEMENTITIOUS WALL BOARD. IN
 ADDITION IT IS REQUIRED THAT A SMOOTH, CLEANABLE,
 NONABSORBENT AND NONCOMBUSTIBLE MATERIAL IS INSTALLED
 BETWEEN THE HOOD AND THE GYPSUM BOARD OVER AN AREA
 EXTENDING NOT LESS THAN 18 INCHES IN ALL DIRECTIONS
 FROM THE HOOD- SECTION 507.2.6. PLEASE REVISE THE PLANS
 TO SHOW COMPLIANCE.
  
 7) SUBMIT MANUFACTURER'S SPECIFICTIONS FOR THE GREASE
 EXHAUST FAN- SECTION 506.5.1.
  
 8) PROVIDE WIND LOAD ENGINEERING FOR INSTALLATION OF
 THE EXHASUT FAN AND THE NEW 3-TON ROOFTOP AC UNIT-
 SECTION 301.15.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2018-03-17 Cont ID  
Sent By gjohnson Date 2018-03-17 Time 09:26 Rev Time 0.00
Received By gjohnson Date 2018-03-17 Time 08:56 Sent To  
Notes
2018-03-17 09:47:001ST REVIEW: FBC 2017 6TH EDITION
 PLUMBING COMMENTS:
  
 1. ALL WORK SHALL COMPLY WITH CURRENT CODE 2017 FBC
 PLUMBING , FUEL GAS, ACCESSIBILITY
  
 2. THERE IS NO PERMIT RECORD OF THREE COMPARTMENT SINK
 OR CAN WASH THEY SHALL BE REVIEWED AS NEW WORK AND
 SHALL COMPLY WITH CURRENT CODE. PER WPB AMEND TO FBC
 105.1 AND 107.2.1
  
 3. PLEASE PROVIDE SANITARY AND WATER ISOMETRIC
 DRAWINGS. PER WPB AMEND TO FBC 107.3.5.1.3(13)
  
 4. THE CAN WASH SHALL DISCHARGE TO A GREASE INTERCEPTOR
 ALONG WITH THE 3 COMPARTMENT SINK. FBC PL 1003.3.1
  
 5. A SEPARATE PERMIT IS REQUIRED FOR THE GREASE
 INTERCEPTOR PLACE NOTE OM PLAN. PER WPB AMEND TO FBC
 105.1 AND 107.2.1
  
 6. THE CAN WASH SHALL BE COVERED TO PREVENT STORM WATER
 FROM DISCHARGING TO SANITARY SYSTEM. PER WPB CODE OF
 ORDINANCES SEC. 90-126.(5)
  
 7. SHALL COMPLY WITH BUILDINGS COMMENTS
  
 8. PROVIDE DETAIL FOR GREASE INTERCEPTOR, SIZING
 CALCULATIONS AND MANUFACTURE SPECIFICATIONS AND
 INSTILLATION GUIDE. PER WPB AMEND TO FBC 105.1 AND
 107.2.1
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop Z ZONING
Rev No 1 Status F Date 2018-04-02 Cont ID  
Sent By ES Date 2018-04-02 Time 13:47 Rev Time 0.50
Received By eschneid Date 2018-04-02 Time 11:47 Sent To  
Notes
2018-04-02 13:47:46FAILED
  
 1) THE CITY'S ZONING REGULATIONS REQUIRE THAT
 MECHANICAL SYSTEMS, WHICH INCLUDES THE NEW ROOFTOP
 EXHAUST FAN AND ROOF TOP A/C, BE SCREENED FROM VIEW ON
 ALL SIDES TO THE FULL HEIGHT OF THE STRUCTURE BY BUILT
 ELEMENTS DESIGNED AS AN INTEGRAL PART OF THE BUILDING
 ARCHITECTURE. PLEASE PROVIDE VERIFICATION OF THE
 REQUIREMENT FOR THE NEW EQUIPMENT.
  
 CONTACT ERIC SCHNEIDER @ 9561) 822-1446
 [email protected]