Plan Review Details - Permit 18030017
| Plan Review Stops For Permit 18030017 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2018-06-30 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2018-06-30 |
Time |
11:03 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2018-06-29 |
Time |
16:29 |
Sent To |
Z |
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2018-03-23 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2018-03-23 |
Time |
11:18 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2018-03-17 |
Time |
07:13 |
Sent To |
|
|
| Notes |
| 2018-03-23 11:19:36 | BUILDING PLAN REVIEW | | | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST | | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | | CHAPTER 1 ADMINISTRATION | | | | | | CHRISTOPHER S. THROOP, C.B.O. | | | PLANS EXAMINER, PX3169 | | | CONSTRUCTION SERVICES DIVISION | | | TEL: 561-805-6726 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | | | | 1ST REVIEW | | | RESULTS: DENIED | | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | | | | 1. APPLICATION FOR THE RESIDENTIAL STRUCTURE MUST BE | | | MADE PRIOR TO THE ISSUANCE OF A FOUNDATION PERMIT. | | | 2. SEPERATE PERMIT REQUIRED FOR CABANA. | | | 3. PROPOSED STRUCTURES ARE IN FLOOD ZONE A WITH A BASE | | | FLOOD ELEVATION (BFE) OF 7'0". BASE FLOOD ELEVATIONS | | | ARE ESTABLISHED BY THE FLOOD INSURANCE STUDY (FIS) OF | | | THE PROPERTY. THE CITY OF WEST PALM BEACH, BY | | | ORDINANCE, REQUIRES AND ADDITIONAL TWO FEET OF | | | FREEBOARD. THE DESIGN FLOOD ELEVATION (DFE) SHALL BE NO | | | LOWER THAN 9' 0". | | | 4. PROVIDE AN ELEVATION CERTIFICATE FOR BOTH | | | STRUCTURES. | | | 5. VALUE APPEARS LOW FOR THE SCOPE OF WORK. | | | 6. PLAN PAGE A000 STATES GOVERNING CODE AS 2014 FBC 5TH | | | ED. DESIGN SHALL BE BASED ON THE 2017 FBC 6TH ED. | | | 7. SITE RETAINING WALLS REQUIRED TO RETAIN SITE | | | DRAINAGE FROM ADJOINING PROPERTIES. PROVIDE DETAIL OF | | | WALLS WITH APPLICATION FOR STRUCUTRE. | | | | | | A CONSTRUCTION DRAWING ELEVATION CERTIFICATE IS | | | REQUIRED AT TIME OF PERMIT APPLICATION. | | | NOTE: ALL EQUIPMENT SERVICING THE BUILDINGS ON THIS | | | SITE ARE REQUIRED TO BE AT OR ABOVE 9.0 FEET NGVD. | | | | | | AN UNDER CONSTRUCTION (FORMBOARD) SURVEY WITH FINISHED | | | FLOOR ELEVATION IS RECOMMENDED. | | | | | | A FINISHED CONSTRUCTION ELEVATION CERTIFICATE IS | | | REQUIRED AND SHALL BE SUBMITTED FOR REVIEW AND APPROVAL | | | PRIOR TO THE ISSUANCE OF THE CERTIFICATE OF OCCUPANCY. | | | | | | THE STATED VALUE APPEARS LOW FOR THE PROPOSED SCOPE OF | | | WORK. | | | | | | YOU MAY PROVIDE A COPY OF THE CONTRACT SIGNED BY THE | | | OWNER OR A LIST OF LABOR, MATERIALS AND EQUIPMENT | | | RENTAL TO VERIFY VALUE. | | | | | | CITY OF WPB CHPT. 1 ? VALUE | | | 109.3 BUILDING PERMIT VALUATIONS. IF, IN THE OPINION OF | | | THE BUILDING OFFICIAL, THE CLAIMED VALUATION OF | | | BUILDING, ALTERATION, STRUCTURE, ELECTRICAL, GAS, | | | MECHANICAL OR PLUMBING SYSTEMS APPEARS TO BE | | | UNDERESTIMATED ON THE APPLICATION, THE PERMIT SHALL BE | | | DENIED, UNLESS THE APPLICANT CAN SHOW DETAILED, | | | QUANTITY ESTIMATES, AND/OR BONA FIDE SIGNED CONTRACTS | | | (EXCLUDING LAND VALUE) TO MEET THE APPROVAL OF THE | | | BUILDING OFFICIAL. FOR PERMITTING PURPOSES, VALUATION | | | OF BUILDINGS AND SYSTEMS SHALL BE TOTAL REPLACEMENT | | | VALUE TO INCLUDE STRUCTURAL, ELECTRIC, PLUMBING, | | | MECHANICAL, INTERIOR FINISH, RELATIVE SITE WORK, | | | ARCHITECTURAL AND DESIGN FEES, MARKETING COSTS, | | | OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE. | | | VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED | | | DATA OF NATIONAL CONSTRUCTION | | | COST ANALYSIS SERVICES (MARSHALL-SWIFT, MEANS, ETC.), | | | AS PUBLISHED BY INTERNATIONAL CODE CONGRESS. | | | FINAL BUILDING PERMIT VALUATION SHALL BE SET BY THE | | | BUILDING OFFICIAL. | | | | | | ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS AND | | | SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE 2017 | | | FLORIDA BUILDING CODE, 6TH EDITION. | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | | CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY | | | REVIEWED SHEETS DETACHED AND MARK VOID. | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2018-06-29 |
|
|
Cont ID |
|
| Sent By |
jpearson |
Date |
2018-06-29 |
Time |
13:04 |
Rev Time |
0.00 |
| Received By |
jpearson |
Date |
2018-06-29 |
Time |
12:43 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2018-03-09 |
|
|
Cont ID |
|
| Sent By |
jpearson |
Date |
2018-03-09 |
Time |
13:48 |
Rev Time |
0.00 |
| Received By |
jpearson |
Date |
2018-03-09 |
Time |
07:41 |
Sent To |
|
|
| Notes |
| 2018-03-09 13:48:24 | NO NOTES. |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
N |
Date |
2018-03-08 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2018-03-08 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2018-03-07 |
Time |
16:45 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2018-07-06 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2018-07-06 |
Time |
13:25 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2018-07-05 |
Time |
13:06 |
Sent To |
I |
|
| Notes |
| 2018-07-06 13:07:11 | IMPACT FEES ROUTED TO CTHROOP |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2018-07-03 |
|
|
Cont ID |
|
| Sent By |
lmarchan |
Date |
2018-07-03 |
Time |
16:14 |
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2018-06-20 |
Time |
13:13 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2018-03-30 |
|
|
Cont ID |
|
| Sent By |
cpuell |
Date |
2018-03-30 |
Time |
13:52 |
Rev Time |
0.00 |
| Received By |
cpuell |
Date |
2018-03-01 |
Time |
13:46 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
2 |
Status |
P |
Date |
2018-07-06 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2018-07-06 |
Time |
13:25 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2018-07-06 |
Time |
13:24 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
1 |
Status |
F |
Date |
2018-03-23 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2018-03-23 |
Time |
11:19 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2018-03-17 |
Time |
07:14 |
Sent To |
|
|
| Notes |
| 2018-03-23 11:20:42 | BUILDING PLAN REVIEW | | | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST | | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | | CHAPTER 1 ADMINISTRATION | | | | | | CHRISTOPHER S. THROOP, C.B.O. | | | PLANS EXAMINER, PX3169 | | | CONSTRUCTION SERVICES DIVISION | | | TEL: 561-805-6726 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | | | | 1ST REVIEW | | | RESULTS: DENIED | | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | | | | BEFORE A PERMIT TO CONSTRUCT CAN BE ISSUED, IMPACT | | | FEES, REQUIRED BY PALM BEACH COUNTY, SHALL BE PAID. | | | UPON FINAL APPROVAL OF PLANS, ONE SET OF PLANS SHALL BE | | | SIGNED OUT AND SUBMITTED TO PALM BEACH COUNTY FOR AN | | | IMPACT FEE REVIEW. THE PLANS WITH THE IMPACT FEE STAMP | | | AND A COPY OF THE PAID RECEIPT MUST BE RETURNED TO THE | | | CITY BUILDING DEPARTMENT BEFORE THE BUILDING PERMIT CAN | | | BE ISSUED. FOR INFORMATION CALL PALM BEACH COUNTY | | | IMPACT FEES AT (561) 233-5025. | | | | | | |
|
|
| Review Stop |
NFIP |
NFIP REVIEW ACTIVITY |
| Rev No |
2 |
Status |
P |
Date |
2018-06-30 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2018-06-30 |
Time |
11:03 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2018-06-29 |
Time |
16:29 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
NFIP |
NFIP REVIEW ACTIVITY |
| Rev No |
1 |
Status |
F |
Date |
2018-03-19 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2018-03-19 |
Time |
17:14 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2018-03-19 |
Time |
17:08 |
Sent To |
|
|
| Notes |
| 2018-03-19 17:24:12 | BUILDING PLAN REVIEW | | | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST | | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | | CHAPTER 1 ADMINISTRATION | | | | | | CHRISTOPHER S. THROOP, C.B.O. | | | PLANS EXAMINER, PX3169 | | | CONSTRUCTION SERVICES DIVISION | | | TEL: 561-805-6726 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | | | | 1ST REVIEW | | | RESULTS: DENIED | | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | | | | 1. APPLICATION FOR THE RESIDENTIAL STRUCTURE MUST BE | | | MADE PRIOR TO THE ISSUANCE OF A FOUNDATION PERMIT. | | | 2. SEPERATE PERMIT REQUIRED FOR CABANA. | | | 3. PROPOSED STRUCTURES ARE IN FLOOD ZONE A WITH A BASE | | | FLOOD ELEVATION (BFE) OF 7'0". BASE FLOOD ELEVATIONS | | | ARE ESTABLISHED BY THE FLOOD INSURANCE STUDY (FIS) OF | | | THE PROPERTY. THE CITY OF WEST PALM BEACH, BY | | | ORDINANCE, REQUIRES AND ADDITIONAL TWO FEET OF | | | FREEBOARD. THE DESIGN FLOOD ELEVATION (DFE) SHALL BE NO | | | LOWER THAN 9' 0". | | | 4. PROVIDE AN ELEVATION CERTIFICATE FOR BOTH | | | STRUCTURES. | | | 5. VALUE APPEARS LOW FOR THE SCOPE OF WORK. | | | 6. PLAN PAGE A000 STATES GOVERNING CODE AS 2014 FBC 5TH | | | ED. DESIGN SHALL BE BASED ON THE 2017 FBC 6TH ED. | | | 7. SITE RETAINING WALLS REQUIRED TO RETAIN SITE | | | DRAINAGE FROM ADJOINING PROPERTIES. PROVIDE DETAIL OF | | | WALLS WITH APPLICATION FOR STRUCUTRE. | | | | | | A CONSTRUCTION DRAWING ELEVATION CERTIFICATE IS | | | REQUIRED AT TIME OF PERMIT APPLICATION. | | | NOTE: ALL EQUIPMENT SERVICING THE BUILDINGS ON THIS | | | SITE ARE REQUIRED TO BE AT OR ABOVE 9.0 FEET NGVD. | | | | | | AN UNDER CONSTRUCTION (FORMBOARD) SURVEY WITH FINISHED | | | FLOOR ELEVATION IS RECOMMENDED. | | | | | | A FINISHED CONSTRUCTION ELEVATION CERTIFICATE IS | | | REQUIRED AND SHALL BE SUBMITTED FOR REVIEW AND APPROVAL | | | PRIOR TO THE ISSUANCE OF THE CERTIFICATE OF OCCUPANCY. | | | | | | THE STATED VALUE APPEARS LOW FOR THE PROPOSED SCOPE OF | | | WORK. | | | | | | YOU MAY PROVIDE A COPY OF THE CONTRACT SIGNED BY THE | | | OWNER OR A LIST OF LABOR, MATERIALS AND EQUIPMENT | | | RENTAL TO VERIFY VALUE. | | | | | | CITY OF WPB CHPT. 1 ? VALUE | | | 109.3 BUILDING PERMIT VALUATIONS. IF, IN THE OPINION OF | | | THE BUILDING OFFICIAL, THE CLAIMED VALUATION OF | | | BUILDING, ALTERATION, STRUCTURE, ELECTRICAL, GAS, | | | MECHANICAL OR PLUMBING SYSTEMS APPEARS TO BE | | | UNDERESTIMATED ON THE APPLICATION, THE PERMIT SHALL BE | | | DENIED, UNLESS THE APPLICANT CAN SHOW DETAILED, | | | QUANTITY ESTIMATES, AND/OR BONA FIDE SIGNED CONTRACTS | | | (EXCLUDING LAND VALUE) TO MEET THE APPROVAL OF THE | | | BUILDING OFFICIAL. FOR PERMITTING PURPOSES, VALUATION | | | OF BUILDINGS AND SYSTEMS SHALL BE TOTAL REPLACEMENT | | | VALUE TO INCLUDE STRUCTURAL, ELECTRIC, PLUMBING, | | | MECHANICAL, INTERIOR FINISH, RELATIVE SITE WORK, | | | ARCHITECTURAL AND DESIGN FEES, MARKETING COSTS, | | | OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE. | | | VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED | | | DATA OF NATIONAL CONSTRUCTION | | | COST ANALYSIS SERVICES (MARSHALL-SWIFT, MEANS, ETC.), | | | AS PUBLISHED BY INTERNATIONAL CODE CONGRESS. | | | FINAL BUILDING PERMIT VALUATION SHALL BE SET BY THE | | | BUILDING OFFICIAL. | | | | | | ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS AND | | | SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE 2017 | | | FLORIDA BUILDING CODE, 6TH EDITION. | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | | CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY | | | REVIEWED SHEETS DETACHED AND MARK VOID. | | | | | | | | | | | | | | | | | | | | | | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2018-06-30 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2018-06-30 |
Time |
08:02 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2018-06-30 |
Time |
07:35 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
P |
Date |
2018-03-22 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2018-03-22 |
Time |
11:45 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2018-03-22 |
Time |
11:13 |
Sent To |
|
|
| Notes |
| 2018-03-22 12:02:00 | 1ST REVIEW: FBC 2017 6TH EDITION | | | | | | PLUMBING COMMENTS: APPROVED WITH PROVISO SHALL BE | | | CORRECTED ON MASTER. | | | | | | 1. THE BATHROOMS 244 + 215 SHOW A TUB ON THE FLOOR PLAN | | | AND A SHOWER ON THE ISOMETRIC DRAWING PLEASE CLARIFY. | | | PER WPB AMEND TO FBC 107.2.1 | | | | | | 2. THE ISOMETRIC DOES NOT MATCH THE FLAT DRAWING AT THE | | | BRANCH FOR THE POWDER ROOM 135. THE FLAT DRAWING SHOWS | | | 1 BRANCH CONNECTING THE POWDER ROOM AND 2 SOIL STACKS | | | THE ISOMETRIC DRAWING SHOWS 2 SEPARATE BRANCHES | | | CONNECTING THE POWDER ROOM AND THE SOIL STACKS. PER WPB | | | AMEND TO FBC 107.2.1 | | | | | | 3. PROVIDE DETAIL FOR DRY WELL FOR OUTSIDE SHOWER. PER | | | WPB AMEND TO FBC 107.2.1.2 | | | | | | GEORGE JOHNSON | | | PLUMBING PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561-805-6711 | | | [email protected] | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
2018-07-02 |
|
|
Cont ID |
|
| Sent By |
awooten |
Date |
2018-07-02 |
Time |
|
Rev Time |
0.00 |
| Received By |
awooten |
Date |
2018-07-02 |
Time |
|
Sent To |
|
|
| Notes |
| 2018-07-02 15:15:50 | ******************************************************* | | | ********ZONING REVIEW FOUNDATION PERMIT PASSED ******** | | | ******************************************************* | | | * | | | | | | PROVISO: THE MAXIMUM HEIGHT ALLOWED IS 30 FEET. HEIGHT | | | EXCEPTIONS. EXEMPTIONS TO HEIGHT LIMITS. HEATING, | | | VENTILATION, AND AIR CONDITIONING EQUIPMENT; CHURCH | | | STEEPLES, BELL TOWERS, FLAG POLES, CHIMNEYS, PARAPETS, | | | STAIR ENCLOSURES, TANKS, DECORATIVE FEATURES, ELEVATOR | | | HOISTWAYS OR EQUIPMENT, TELEVISION OR RADIO ANTENNAS, | | | AND RELATED MECHANICAL OR FUNCTIONAL FEATURES MAY | | | EXCEED DISTRICT HEIGHT REQUIREMENTS BY TEN PERCENT (3 | | | FEET). MAXIMUM HEIGHT INCLUDING THE CHIMNEY CANNOT | | | EXCEET 33'. | | | | | | ALANA WOOTEN | | | ASSOCIATE PLANNER | | | PLANNING DIVSION | | | 561-822-1449 | | | [email protected] |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2018-03-29 |
|
|
Cont ID |
|
| Sent By |
AW |
Date |
2018-03-29 |
Time |
13:33 |
Rev Time |
|
| Received By |
awooten |
Date |
2018-03-29 |
Time |
|
Sent To |
|
|
| Notes |
| 2018-03-29 13:39:55 | *****************************************ZONING REVIEW | | | FAILED******************************************** | | | | | | ? DIMENSION THE OVERHANGS. STRUCTURAL INTRUSIONS. | | | STRUCTURAL OVERHANGS, INCLUDING BUT NOT LIMITED TO | | | BALCONIES, CORNICES, GUTTERS, EAVES, AND ROOF OVERHANG | | | PROJECTIONS SHALL NOT EXTEND FARTHER THAN THREE FEET | | | INTO ANY SETBACK. | | | | | | ? THE MAXIMUM HEIGHT ALLOWED IS 30 FEET. HEIGHT | | | EXCEPTIONS. EXEMPTIONS TO HEIGHT LIMITS. HEATING, | | | VENTILATION, AND AIR CONDITIONING EQUIPMENT; CHURCH | | | STEEPLES, BELL TOWERS, FLAG POLES, CHIMNEYS, PARAPETS, | | | STAIR ENCLOSURES, TANKS, DECORATIVE FEATURES, ELEVATOR | | | HOISTWAYS OR EQUIPMENT, TELEVISION OR RADIO ANTENNAS, | | | AND RELATED MECHANICAL OR FUNCTIONAL FEATURES MAY | | | EXCEED DISTRICT HEIGHT REQUIREMENTS BY TEN PERCENT. | | | | | | ? DIMENSION THE SETBACKS FOR ALL MECHANICAL EQUIPMENT. | | | MECHANICAL EQUIPMENT. MECHANICAL EQUIPMENT MAY NOT | | | PROJECT MORE THAN FOUR FEET INTO A SETBACK. WINDOW | | | AIR-CONDITIONING UNITS MAY NOT PROJECT MORE THAN 18 | | | INCHES INTO A REQUIRED SIDE SETBACK. | | | | | | ? WILL THE CABANA BE ATTACHED TO THE HOUSE WITH A SOLID | | | ROOF? | | | | | | ? PLEASE SUBMIT A SEPARATE LANDSCAPE AND IRRIGATION | | | PERMIT. SHOWING THE FOLLOWING: | | | | | | RESIDENTIAL LANDSCAPE REQUIREMENTS CITY OF WEST PALM | | | BEACH | | | SECTION 94-442(C)(2)A. SINGLE FAMILY DWELLING UNITS | | | | | | O GROSS LOT SQUARE FOOTAGE MINUS | | | O BUILDING FOOTPRINT SQUARE FOOTAGE EQUALS | | | O OPEN SPACE SQUARE FOOTAGE (ALL NON-BUILDING AREA) | | | O ONE TREE REQUIRED FOR EACH 1,000 SQ FT OF OPEN SPACE | | | OR PORTION THEREOF | | | O ONE SHRUB REQUIRED FOR EACH 500 SQ FT OF OPEN SPACE | | | OR PORTION THEREOF | | | | | | | | | PLEASE LET ME KNOW WHAT QUESTIONS YOU MAY HAVE. | | | | | | ALANA WOOTEN | | | ASSOCIATE PLANNER | | | PLANNING DIVISION | | | 561-822-1449 | | | [email protected] |
|
|
|