Plan Review Details - Permit 18030013
Plan Review Stops For Permit 18030013
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2019-01-02 Cont ID  
Sent By cthroop Date 2019-01-02 Time 15:38 Rev Time 0.00
Received By cthroop Date 2018-12-31 Time 17:04 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2018-08-28 Cont ID  
Sent By jgomez Date 2018-08-28 Time 10:48 Rev Time 0.00
Received By jgomez Date 2018-08-27 Time 18:30 Sent To  
Notes
2018-08-28 08:16:49RESIDENTIAL (R3) ALTERATION, ADDITION SECOND BUILDING
 REVIEW CHECKLIST.
 CODE: FBC 6TH EDITION (2017).
  
 ORIGINAL COMMENT:
 1- ACCORDING TO SEC. R301.2.1.4.3 FBC-RESIDENTIAL THIS
 BUILDING IS LOCATED IN EXPOSURE "C" NOT "B". REVISE AS
 REQUIRED INFORMATION IN PLANS AND REQUIRED AND REVISE
 THE DOORS AND WINDOWS DESIGN PRESSURES ACCORDINGLY.
  
 RESPONSE:
 CLARIFY IF WINDOWS/DOORS DESIGN PRESSURES SHOWN ON
 SHEET ED-101 ARE ULTIMATE OR NOMINAL WIND LOADS. DESIGN
 CRITERIA SPECIFIES "DESIGN METHOD: ASD". NEED THIS TO
 VERIFY DESIGN PRESSURES ON PRODUCT APPROVALS SUBMITTED.
 SEC. R301.2.1.3 FBC-RESIDENTIAL.
  
 ORIGINAL COMMENT:
 2- BEDROOM EGRESS WINDOWS DON'T COMPLY WITH SEC. R310.2
 FBC-RESIDENTIAL. REVISE AS REQUIRED. CLEARLY SPECIFY
 SIZE OF WINDOW THATT COMPLIES. SEE WINDOW PRODUCT
 APPROVAL FOR LISTED SIZES.
  
 RESPONSE:
 WINDOW SIZE SPECIFIED (52"W X 57" H) DOESN'T SEEM TO
 COMPLY WITH THE MIN. CLEAR HEIGHT OF 24". PROVIDE
 MANUFACTURER'S CUT SHEETS SHOWING THAT THE SPECIFIED
 WINDOW PROVIDES THE MIN. CLEAR HEIGHT.
  
 ORIGINAL COMMENT:
 3- SPECIFY ROOF VENTILATION AS REQUIRED BY SEC. R806
 FBC-RESIDENTIAL.
  
 RESPONSE:
 SHEET A200 SHOWS ROOF VENT CALCULATIONS USING 1/300
 RATIO. SEC. R806.2 FBC-RESIDENTIAL REQUIRES A RATIO OF
 1/150. IN ORDER TO USE THE 1/300 RATIO NEED TO SHOW
 COMPLIANCE WITH ONE OF THE EXCEPTIONS OF SEC. R806.2
 FBC-RESIDENTIAL. REVISE AS REQUIRED.
  
 ORIGINAL COMMENT:
 4- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.001 FOR:
 A) SINGLE HUNG WINDOWS AS SHOWN ON PLANS.
 NOTE: DESIGN PRESSURES WILL BE REVIEWED ONCE CALCULATED
 DESIGN PRESSURES ON SHEET ED-101 ARE CLARIFIED.
  
 B) WINDOW MULLIONS AS SHOWN ON PLANS. AND, CLEARLY MARK
 MULLION SIZE TO VERIFY COMPLIANCE WITH THE CALCULATED
 DESIGN PRESSURES.
 NOTE: SPECIFY SIZE OF MULLION.
 NOTE: DESIGN PRESSURES WILL BE REVIEWED ONCE CALCULATED
 DESIGN PRESSURES ON SHEET ED-101 ARE CLARIFIED.
  
 C) INSWING ENTRY DOOR WITH SIDELITE AS SHOWN ON PLANS.
 FLORIDA PRODUCT APPROVAL FL4904-R8 IS MISSING THE DOORS
 INSTALLATION INSTRUCTIONS. PROVIDE COMPLETE PRODUCT
 APPROVAL.
 NOTE: DESIGN PRESSURES WILL BE REVIEWED ONCE CALCULATED
 DESIGN PRESSURES ON SHEET ED-101 ARE CLARIFIED.
  
 D) ALL OUTSWING FRENCH DOORS AS SHOWN ON PLANS.
 NOTE: DESIGN PRESSURES WILL BE REVIEWED ONCE CALCULATED
 DESIGN PRESSURES ON SHEET ED-101 ARE CLARIFIED.
  
 E) GABLE END VENTS AS SHOWN ON PLANS.
 REPEAT COMMENT. NO SUBMITTED.
 NOTE: DESIGN PRESSURES WILL BE REVIEWED ONCE CALCULATED
 DESIGN PRESSURES ON SHEET ED-101 ARE CLARIFIED.
  
 F) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON PLANS
 AND DETAILS. NOTE: PROVIDE ONLY THE FLORIDA PRODUCT
 APPROVAL COVER PAGE AND PAGE SHOWING THE SPECIFIED
 CONNECTOR OR DESIGN PROFESSIONAL TO LIST THE FLORIDA
 PRODUCT APPROVAL NUMBER NEXT TO EACH SPECIFIED
 CONNECTOR.
 REPEAT COMMENT. NO SUBMITTED.
  
 G) STORAGE DOUBLE DOORS AS SHOWN ON PLANS. CLARIFY IS
 USING THE SAME DOORS AS ENTRY AND SIDE DOORS.
 NOTE: DESIGN PRESSURES WILL BE REVIEWED ONCE CALCULATED
 DESIGN PRESSURES ON SHEET ED-101 ARE CLARIFIED.
  
 NEW COMMENTS:
 5- DRAWINGS A100 AND A200 ARE NOT LEGIBLE. THEY ARE TOO
 LIGHT. PROVIDE LEGIBLE DRAWINGS. SEC. 107.2.1.3 CITY
 AMENDMENTS.
  
 6- PROVIDE COMPLETE FRAMING DETAILS FOR THE
 INSTALLATION OF THE (2) DOUBLE DOORS AT THE NEW OUTSIDE
 STORAGE. AND, SHOW HOW THE TWO DOUBLE DOORS ARE MULLED
 TOGETHER.T SEC. R301.1 FBC-RESIDENTIAL.
  
 7- PROVIDE LANDING FOR NEW STAIRS STAIRS AS REQUIRED BY
 SEC. R311.3 AND R311.3.2 FBC.-RESIDENTIAL.
  
 8- EXISTING COTTAGE PROPOSED ELEVATION ON SHEET A200
 DOESN'T MATCH EXISTING FLOOR PLAN ON SHEET ED-101. IT
 IS NOT CLEAR IF DOING WORK ON COTTAGE OR NOT. SEC.
 107.2.1 CITY AMENDMENTS.
  
 9- SHEET S-100:
 A) PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE
 VENTILATION OF UNDER FLOOR SPACE FOR THE ADDITION.. SEE
 SEC. R408.1 FBC-RESIDENTIAL FOR REQUIRED LOCATION.
  
 B) ALL EXTERIOR FOOTING NEED TO BE NO LESS THAN 12"
 BELOW GRADE AS REQUIRED BY SEC. R403.1.4
 FBC-RESIDENTIAL. REVISE ALL FOOTING DETAILS AS
 REQUIRED.
  
 10- CROSS SECTION "F" ON SHEET S-102: PROVIDE COMPLETE
 DETAILS AND SPECIFICATIONS FOR CONNECTION OF EXTERIOR
 WALL TO FOUNDATION CLEARLY SHOWING THE LOAD PATH.
 CLEARLY SPECIFY ANCHOR BOLT SIZE. SEC. R401.2
 FBC-RESIDENTIAL.
  
 11- ACCORDING TO SEC. R403.1.2 AND TABLE R403.1.2
 FBC-RESIDENTIAL THE FOOTING SIZE SPECIFIED FOR THE
 ADDITION MAY BE TOO SMALL FOR UPLIFT RESISTANCE. SEE
 TABLE R403.1.2 FOOTING TYPE "F". ENGINEER TO PROVIDE
 ANALYSIS SHOWING THAT SPECIFIED FOOTING SIZE IS
 ADEQUATE. SEC. 107.2.1.2 CITY AMENDMENTS.
  
 ****PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO HELP EXPEDITE THE REVIEW PROCESS.
  
 ****PLEASE INSERT ANY REVISED DRAWING AND REMOVE OLD
 DRAWING. SUBMIT OLD DRAWINGS FOR REFERENCE OF ALREADY
 REVIEWED DRAWINGS. DON'T STAPLE OLD DRAWINGS TO PLANS.
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-03-23 Cont ID  
Sent By jgomez Date 2018-03-23 Time 17:00 Rev Time 0.00
Received By jgomez Date 2018-03-23 Time 11:01 Sent To  
Notes
2018-03-22 18:54:08RESIDENTIAL (R3) ALTERATION, ADDITION BUILDING REVIEW
 COMMENTS
 CODE: FBC 6TH EDITION (2017).
  
 1- ALL PLANS NEED TO HAVE THE ORIGINAL SEAL AND
 SIGNATURE OF THE PROFESSIONAL ARCHITECT OR PROFESSIONAL
 ENGINEER SHOWN ON PLANS AS REQUIRED BY CHAPTER 481 F.S.
 OR CHAPTER 471 F.S. RESPECTIVELY WHEN SUBMITTING
 DOCUMENTS FOR PUBLIC RECORDS.
 NOTE: BASED ON PLANS SUBMITTED, IT LOOKS LIKE THERE IS
 AN ARCHITECT AND AN ENGINEER WORKING IN THIS PROJECT.
 COORDINATE INFORMATION ON PLANS TO AVOID
 CONFLICTS/DELAYS.
  
 2- PLANS SUBMITTED WERE REDUCED IN SIZE. THEY ARE NOT
 LEGIBLE AND THE SCALE THEY WERE DRAWN IS NOT CORRECT
 ANY MORE. PROVIDE 2 COMPLETE SET OF PLANS THAT
 REPRESENT THE CORRECT SCALE. SEC. 107.2.1.3 CITY
 AMENDMENTS.
  
 3- THE CURRENT CODE IS THE FBC 6TH EDITION (2017) NOT
 THE FBC 5TH EDITION (2014). CHAPTER 553 FLORIDA
 STATUTE. UPDATE ALL PLANS AS REQUIRED.
  
 4- ACCORDING TO SEC. R301.2.1.4.3 FBC-RESIDENTIAL THIS
 BUILDING IS LOCATED IN EXPOSURE "C" NOT "B". REVISE AS
 REQUIRED INFORMATION IN PLANS AND REQUIRED AND REVISE
 THE DOORS AND WINDOWS DESIGN PRESSURES ACCORDINGLY.
  
 5- SITE PLAN SUBMITTED SHOWS "EXISTING COTTAGE TO
 REMAIN N.I.C.". ACCORDING TO CITY RECORDS THIS
 STRUCTURE WAS APPROVED AS A COTTAGE WITH GARAGE.
 PROPOSED ELEVATIONS SUBMITTED DON'T MATCH COTTAGE FLOOR
 PLAN. PROVIDE COMPLETE COTTAGE FLOOR PLAN WITH THE
 PROPOSED DESIGN. OTHERWISE REVISE FLOOR PLAN SHOWING
 THE ORIGINAL GARAGE. SEC. 107.2.1 CITY AMENDMENTS.
 NOTE: KITCHEN DRAWING ON SHEET A500 DOESN'T MATCH
 PROPOSED FLOOR PLAN. IS THIS FOR THE COTTAGE?. SAME
 THING APPLIES TO BATHROOM DRAWINGS ON SHEET A601. AND,
 WHAT ARE THE DWGS SHOWN ON SHEET A700 FOR?. ALSO, BUCK
 DETAILS SHOWN ON SHEET A400 DON'T APPLY TO THIS HOUSE.
 THIS IS A WOOD FRAMED HOUSE. REVISE AS REQUIRED.
  
 6- BEDROOM EGRESS WINDOWS DON'T COMPLY WITH SEC. R310.2
 FBC-RESIDENTIAL. REVISE AS REQUIRED. CLEARLY SPECIFY
 SIZE OF WINDOW THAT COMPLIES. SEE WINDOW PRODUCT
 APPROVAL FOR LISTED SIZES.
 R310.1 EMERGENCY ESCAPE AND RESCUE OPENING REQUIRED.
 BASEMENTS, HABITABLE ATTICS AND EVERY SLEEPING ROOM
 SHALL HAVE NOT LESS THAN ONE OPERABLE EMERGENCY ESCAPE
 AND RESCUE OPENING. WHERE BASEMENTS CONTAIN ONE OR MORE
 SLEEPING ROOMS, AN EMERGENCY ESCAPE AND RESCUE OPENING
 SHALL BE REQUIRED IN EACH SLEEPING ROOM. EMERGENCY
 ESCAPE AND RESCUE OPENINGS SHALL OPEN DIRECTLY INTO A
 PUBLIC WAY, OR TO A YARD OR COURT THAT OPENS TO A
 PUBLIC WAY.
  
 7- ENGINEERING PLANS ARE MISSING SHEET 6 OF 9. PROVIDE
 2 COMPLETE SETS. SEC. 107.1 CITY AMENDMENTS.
  
 8- SHEET 3 OF 9 IS MISSING THE FRAMING PLAN AT THE
 PROPOSED REAR PORCH. PROVIDE COMPLETE INFORMATION. SEC.
 R301.1 FBC-RESIDENTIAL.
  
 9- SPECIFY ATTIC ACCESS SIZE AND LOCATION AT NEW
 ADDITION. SEC. R307.1 FBC-RESIDENTIAL.
  
 10- SPECIFY CARBON MONOXIDE ALARM WITHING ALL SLEEPING
 ROOMS AS REQUIRED BY SEC. R315.1 FBC-RESIDENTIAL.
 R315.1 CARBON MONOXIDE PROTECTION.
 EVERY SEPARATE BUILDING OR AN ADDITION TO AN EXISTING
 BUILDING FOR WHICH A PERMIT FOR NEW CONSTRUCTION IS
 ISSUED AND HAVING A FOSSIL-FUEL-BURNING HEATER OR
 APPLIANCE, A FIREPLACE, AN ATTACHED GARAGE, OR OTHER
 FEATURE, FIXTURE, OR ELEMENT THAT EMITS CARBON MONOXIDE
 AS BYPRODUCT OF COMBUSTION SHALL HAVE AN OPERATIONAL
 CARBON MONOXIDE ALARM INSTALLED WITHIN 10 FEET OF EACH
 ROOM USED FOR SLEEPING PURPOSES.
  
 11- BEFORE A PERMIT TO CONSTRUCT CAN BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. UPON APPROVAL,
 ONE SET OF PLANS SHALL BE SIGNED OUT AND SUBMITTED TO
 PALM BEACH COUNTY FOR AN IMPACT FEE REVIEW. THE PLANS
 WITH THE IMPACT FEE STAMP AND A COPY OF THE PAID
 RECEIPT MUST BE RETURNED TO THE CITY BUILDING
 DEPARTMENT BEFORE THE BUILDING PERMIT CAN BE ISSUED.
 FOR INFORMATION CALL PALM BEACH COUNTY IMPACT FEES AT
 (561) 233-5025.
  
 12- SPECIFY ROOF VENTILATION AS REQUIRED BY SEC. R806
 FBC-RESIDENTIAL.
 R806.1 VENTILATION REQUIRED.
 ENCLOSED ATTICS AND ENCLOSED RAFTER SPACES FORMED WHERE
 CEILINGS ARE APPLIED DIRECTLY TO THE UNDERSIDE OF ROOF
 RAFTERS SHALL HAVE CROSS VENTILATION FOR EACH SEPARATE
 SPACE BY VENTILATING OPENINGS PROTECTED AGAINST THE
 ENTRANCE OF RAIN OR SNOW. VENTILATION OPENINGS SHALL
 HAVE A LEAST DIMENSION OF 1/16 INCH (1.6 MM) MINIMUM
 AND 1/4 INCH (6.4 MM) MAXIMUM. VENTILATION OPENINGS
 HAVING A LEAST DIMENSION LARGER THAN 1/4 INCH (6.4 MM)
 SHALL BE PROVIDED WITH CORROSION-RESISTANT WIRE CLOTH
 SCREENING, HARDWARE CLOTH OR SIMILAR MATERIAL WITH
 OPENINGS HAVING A LEAST DIMENSION OF 1/16 INCH (1.6 MM)
 MINIMUM AND 1/4 INCH (6.4 MM) MAXIMUM. OPENINGS IN ROOF
 FRAMING MEMBERS SHALL CONFORM TO THE REQUIREMENTS OF
 SECTION R802.7. REQUIRED VENTILATION OPENINGS SHALL
 OPEN DIRECTLY TO THE OUTSIDE AIR.
  
 13- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO
 LOW. SEC. 109.3 CITY AMENDMENTS.
 FBC 109.3 BUILDING PERMIT VALUATION. FOR PERMITTING
 PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS SHALL BE
 TOTAL REPLACEMENT VALUE TO INCLUDE STRUCTURAL,
 ELECTRIC, PLUMBING, MECHANICAL, INTERIOR FINISH,
 RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN FEES,
 MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING ONLY
 LAND VALUE. VALUATION REFERENCES MAY INCLUDE THE LATEST
 PUBLISHED DATA OF NATIONAL CONSTRUCTION COST ANALYSIS
 SERVICES (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY
 INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT
 VALUATION SHALL BE SET BY THE BUILDING OFFICIAL.
  
 14- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.001 FOR:
 A) SINGLE HUNG WINDOWS AS SHOWN ON PLANS.
  
 B) WINDOW MULLIONS AS SHOWN ON PLANS. AND, CLEARLY MARK
 MULLION SIZE TO VERIFY COMPLIANCE WITH THE CALCULATED
 DESIGN PRESSURES.
  
 C) PEEL & STICK ROOF UNDERLAYMENT FOR SHINGLES AS
 SPECIFIED ON WALL SECTIONS.
  
 D) ROOF SHINGLES AS SHOWN ON PLANS.
  
 E) INSWING ENTRY DOOR WITH SIDELITE AS SHOWN ON PLANS.
  
 F) INSWING MUD ROOM DOOR AS SHOWN ON PLANS.
  
 G) ALL OUTSWING FRENCH DOORS AS SHOWN ON PLANS.
  
 H) GABLE END VENTS AS SHOWN ON PLANS.
  
 I) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON PLANS
 AND DETAILS. NOTE: PROVIDE ONLY THE FLORIDA PRODUCT
 APPROVAL COVER PAGE AND PAGE SHOWING THE SPECIFIED
 CONNECTOR OR DESIGN PROFESSIONAL TO LIST THE FLORIDA
 PRODUCT APPROVAL NUMBER NEXT TO EACH SPECIFIED
 CONNECTOR.
  
 J) STORAGE DOUBLE DOORS AS SHOWN ON PLANS.
  
 K) HURRICANE SHUTTERS IF DOORS AND WINDOWS DON'T HAVE
 IMPACT GLAZING. AND, PROVIDE COMPLETE INSTALLATION
 SCHEDULE. SEE CITY SAMPLE.
  
 15- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
  
  
 ****PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO HELP EXPEDITE THE REVIEW PROCESS.
  
 ****PLEASE INSERT ANY REVISED DRAWING AND REMOVE OLD
 DRAWING. SUBMIT OLD DRAWINGS FOR REFERENCE OF ALREADY
 REVIEWED DRAWINGS. DON?T STAPLE OLD DRAWINGS TO PLANS.
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2018-12-24 Cont ID  
Sent By jpearson Date 2018-12-24 Time 08:12 Rev Time 0.00
Received By jpearson Date 2018-12-24 Time 08:12 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2018-07-30 Cont ID  
Sent By ppetty Date 2018-07-30 Time 10:57 Rev Time 0.00
Received By ppetty Date 2018-07-30 Time 10:57 Sent To  
Notes
2018-07-30 10:57:06FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
 OK
 PHIL PETTY
 ELECTRICAL PLANS EXAMINER
 561-805-6742
 [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-03-27 Cont ID  
Sent By jleahy Date 2018-03-27 Time 07:55 Rev Time 0.00
Received By jleahy Date 2018-03-27 Time 07:54 Sent To  
Notes
2018-03-27 08:20:16FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 KITCHEN COUINTER DOES NOT APPEAR TO MEET THE
 REQUIREMENTS OF THE CODE FOR SPACING
  
 E3901.4.1 WALL COUNTERTOP SPACE.
 A RECEPTACLE OUTLET SHALL BE INSTALLED AT EACH WALL
 COUNTERTOP SPACE 12 INCHES (305 MM) OR WIDER.
 RECEPTACLE OUTLETS SHALL BE INSTALLED SO THAT NO POINT
 ALONG THE WALL LINE IS MORE THAN 24 INCHES (610 MM),
 MEASURED HORIZONTALLY FROM A RECEPTACLE OUTLET IN THAT
 SPACE. [210.52(C)(1)
  
 GENERAL OUTLET SPACING DOES NOT APPEAR TO MEET THE
 CODE.
  
 E3901.2.1 SPACING.
 RECEPTACLES SHALL BE INSTALLED SO THAT NO POINT
 MEASURED HORIZONTALLY ALONG THE FLOOR LINE OF ANY WALL
 SPACE IS MORE THAN 6 FEET (1829 MM), FROM A RECEPTACLE
 OUTLET. [210.52(A)(1)]
  
 AN ADDITIONAL OUTLET IS REQUIRED AT THE REAR OF THE
 BUILDING.
  
 E3901.7 OUTDOOR OUTLETS.
 NOT LESS THAN ONE RECEPTACLE OUTLET THAT IS READILY
 ACCESSIBLE FROM GRADE LEVEL AND LOCATED NOT MORE THAN 6
 FEET, 6 INCHES (1981 MM) ABOVE GRADE, SHALL BE
 INSTALLED OUTDOORS AT THE FRONT AND BACK OF EACH
 DWELLING UNIT HAVING DIRECT ACCESS TO GRADE LEVEL.
 BALCONIES, DECKS, AND PORCHES THAT ARE ACCESSIBLE FROM
 INSIDE OF THE DWELLING UNIT SHALL HAVE AT LEAST ONE
 RECEPTACLE OUTLET INSTALLED WITHIN THE PERIMETER OF THE
 BALCONY, DECK, OR PORCH. THE RECEPTACLE SHALL BE
 LOCATED NOT MORE THAN 6 FEET, 6 INCHES (1981 MM) ABOVE
 THE BALCONY, DECK, OR PORCH SURFACE. [210.52(E)]
  
 SUBMIT A LOAD CALCULATION AND RISER DIAGRAM, SHOWINF
 LOCATION OF SERVICE AND PANEL.
  
 E3602.2SERVICE LOAD.
 THE MINIMUM LOAD FOR UNGROUNDED SERVICE CONDUCTORS AND
 SERVICE DEVICES THAT SERVE 100 PERCENT OF THE DWELLING
 UNIT LOAD SHALL BE COMPUTED IN ACCORDANCE WITH TABLE
 E3602.2. UNGROUNDED SERVICE CONDUCTORS AND SERVICE
 DEVICES THAT SERVE LESS THAN 100 PERCENT OF THE
 DWELLING UNIT LOAD SHALL BE COMPUTED AS REQUIRED FOR
 FEEDERS IN ACCORDANCE WITH CHAPTER 37. [220.82(A)
  
 SUBMIT A PANEL SCHEDULE
  
 E3706.2PANELBOARD CIRCUIT IDENTIFICATION.
 ALL CIRCUITS AND CIRCUIT MODIFICATIONS SHALL BE LEGIBLY
 IDENTIFIED AS TO THEIR CLEAR, EVIDENT, AND SPECIFIC
 PURPOSE OR USE. THE IDENTIFICATION SHALL INCLUDE AN
 APPROVED DEGREE OF DETAIL THAT ALLOWS EACH CIRCUIT TO
 BE DISTINGUISHED FROM ALL OTHERS. SPARE POSITIONS THAT
 CONTAIN UNUSED OVERCURRENT DEVICES OR SWITCHES SHALL BE
 DESCRIBED ACCORDINGLY. THE IDENTIFICATION SHALL BE
 INCLUDED IN A CIRCUIT DIRECTORY LOCATED ON THE FACE OF
 THE PANELBOARD ENCLOSURE OR INSIDE THE PANEL DOOR.
 CIRCUITS SHALL NOT BE DESCRIBED IN A MANNER THAT
 DEPENDS ON TRANSIENT CONDITIONS OF OCCUPANCY.
 [408.4(A)]
  
 SMOKE ALARMS SHALL BE LOCATED AT LEAST 3' FROM BATHROOM
 DOORS
  
 R314.3LOCATION.
 SMOKE ALARMS SHALL BE INSTALLED IN THE FOLLOWING
 LOCATIONS:
  
 4.SMOKE ALARMS SHALL BE INSTALLED NOT LESS THAN 3 FEET
 (914 MM) HORIZONTALLY FROM THE DOOR OR OPENING OF A
 BATHROOM THAT CONTAINS A BATHTUB OR SHOWER UNLESS THIS
 WOULD PREVENT PLACEMENT OF A SMOKE ALARM REQUIRED BY
 SECTION R314.3.

Review Stop HIST HISTORICAL
Rev No 3 Status P Date 2018-12-14 Cont ID  
Sent By fmittner Date 2018-12-14 Time 15:25 Rev Time 0.00
Received By fmittner Date 2018-12-14 Time 15:25 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 2 Status F Date 2018-07-27 Cont ID  
Sent By fmittner Date 2018-07-27 Time 12:06 Rev Time 0.00
Received By fmittner Date 2018-07-27 Time 12:06 Sent To  
Notes
2018-07-27 12:07:57WINDOWS ON FRONT PORCH DO NOT MATCH EXISTING
 CONFIGARATION. PLEASE CONTACT FRIEDERIKE MITTNER, CITY
 HISTORIC PRESERVATION PLANNER AT (561) 822-1457 OR
 [email protected]

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2018-03-08 Cont ID  
Sent By fmittner Date 2018-03-08 Time 09:43 Rev Time 0.00
Received By fmittner Date 2018-03-08 Time 09:43 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2019-06-17 Cont ID  
Sent By cthroop Date 2019-06-17 Time 13:47 Rev Time 0.00
Received By cthroop Date 2019-06-17 Time 13:45 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2019-02-01 Cont ID  
Sent By cthroop Date 2019-02-01 Time 16:44 Rev Time 0.00
Received By cthroop Date 2019-02-01 Time 14:54 Sent To  
Notes
2019-02-01 14:54:18RESUB ROUTED TO CTHROOP

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2019-01-31 Cont ID  
Sent By cthroop Date 2019-01-31 Time 14:43 Rev Time 0.00
Received By cthroop Date 2019-01-22 Time 16:29 Sent To  
Notes
2019-01-23 16:29:57RESUB ROUTED TO ZONING INBOX

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2019-01-02 Cont ID  
Sent By cthroop Date 2019-01-02 Time 15:38 Rev Time 0.00
Received By cthroop Date 2018-12-03 Time 15:58 Sent To  
Notes
2018-12-04 15:58:48R23

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-08-28 Cont ID  
Sent By jgomez Date 2018-08-28 Time 13:23 Rev Time 0.00
Received By jgomez Date 2018-07-18 Time 15:03 Sent To I
Notes
2018-07-19 15:03:18R12

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-03-27 Cont ID  
Sent By jleahy Date 2018-03-27 Time 08:20 Rev Time 0.00
Received By jleahy Date 2018-03-01 Time 13:14 Sent To  
Notes
2018-03-02 13:15:09R29

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 3 Status P Date 2019-06-17 Cont ID  
Sent By cthroop Date 2019-06-17 Time 13:46 Rev Time 0.00
Received By cthroop Date 2019-06-17 Time 13:45 Sent To  
Notes
2019-06-17 13:47:07MU-2019-016484-0000. CT

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status F Date 2018-08-28 Cont ID  
Sent By jgomez Date 2018-08-28 Time 13:03 Rev Time 0.00
Received By jgomez Date 2018-08-28 Time 13:02 Sent To  
Notes
2018-08-28 13:03:40IMPACT FEES - PAPER SUBMITTALS
  
 PLANS REQUIRE REVIEW BY THE PBC IMPACT FEE OFFICE. CALL
 (561) 233-5025. UPON APPROVAL, YOU MAY CHECK OUT ONE
 PLAN SET AND TAKE TO THAT OFFICE FOR REVIEW. PLEASE
 RETURNED STAMPED AND WITH A COPY OF THE RECEIPT AS
 APPLICABLE. PLEASE PROVIDE THE MUNICIPAL IMPACT FEE
 QUESTIONNAIRE FORM TO THE PBC IMPACT FEE OFFICE. THE
 FORM CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/AD
 MINISTRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2018-03-23 Cont ID  
Sent By jgomez Date 2018-03-23 Time 12:45 Rev Time 0.00
Received By jgomez Date 2018-03-23 Time 12:45 Sent To  
Notes
2018-03-23 12:45:19BEFORE A PERMIT TO CONSTRUCT CAN BE ISSUED, IMPACT FEES
 MUST BE PAID TO PALM BEACH COUNTY. UPON APPROVAL, ONE
 SET OF PLANS SHALL BE SIGNED OUT AND SUBMITTED TO PALM
 BEACH COUNTY FOR AN IMPACT FEE REVIEW. THE PLANS WITH
 THE IMPACT FEE STAMP AND A COPY OF THE PAID RECEIPT
 MUST BE RETURNED TO THE CITY BUILDING DEPARTMENT BEFORE
 THE BUILDING PERMIT CAN BE ISSUED. FOR INFORMATION CALL
 PALM BEACH COUNTY IMPACT FEES AT (561) 233-5025.
  
  

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2019-02-01 Cont ID  
Sent By cthroop Date 2019-02-01 Time 16:44 Rev Time 0.00
Received By cthroop Date 2019-02-01 Time 16:44 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 4 Status F Date 2019-01-31 Cont ID  
Sent By cthroop Date 2019-01-31 Time 14:29 Rev Time 0.00
Received By cthroop Date 2019-01-31 Time 14:05 Sent To  
Notes
2019-01-31 14:32:47RESIDENTIAL PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 1&2 FAMILY PLANS EXAMINER, SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 4TH REVIEW
 RESULTS: DENIED
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 ALTHOUGH CORRECTIONS HAVE BEEN MADE CORRECTLY TO
 SUBMITTED MECHANICAL PLAN, ENGINEER'S SIGNATURE IS NOT
 VALID.
  
 DIGITAL SIGNATURE AND SEAL IS NOT ALLOWED ON PAPER
 SUBMITTAL.
  
 FBC 107.1 IF THE DESIGN PROFESSIONAL IS AN ARCHITECT,
 INTERIOR DESIGNER, LANDSCAPE ARCHITECT, OR ENGINEER
 LEGALLY REGISTERED UNDER THE LAWS OF THIS STATE
 REGULATING THE PRACTICE OF ARCHITECTURE OR INTERIOR
 DESIGN AS PROVIDED FOR IN CHAPTER 481, FLORIDA
 STATUTES, PART I, OR LANDSCAPE ARCHITECTURE AS PROVIDED
 FOR IN CHAPTER 481, FLORIDA STATUTES, PART II, OR
 ENGINEERING AS PROVIDED FOR IN CHAPTER 471, FLORIDA
 STATUTES, THEN HE OR SHE SHALL AFFIX HIS OR HER
 OFFICIAL SEAL TO SAID DRAWINGS, SPECIFICATIONS AND
 ACCOMPANYING DATA, AS REQUIRED BY FLORIDA STATUTE.
  
 PLANS THAT HAVE BEEN PREPARED BY AN ENGINEER AND
 SUBMITTED FOR PUBLIC RECORD SHALL BEAR THE SIGNATURE,
 DATE AND SEAL OF THE ENGINEER PER FL ADMIN. CODE RULE
 61G15-23.001.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY
 REVIEWED SHEETS DETACHED.
  
  
  
  
  
  
  

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2019-01-02 Cont ID  
Sent By cthroop Date 2019-01-02 Time 15:38 Rev Time 0.00
Received By cthroop Date 2018-12-31 Time 17:04 Sent To  
Notes
2019-01-02 15:47:45MECHANICAL PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 1&2 FAMILY PLANS EXAMINER, SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 3RD REVIEW
 RESULTS: DENIED
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. COMMENT # 2 FROM 2ND REVIEW HAS NOT BEEN ADDRESSED.
 PROVIDE EQUIPMENT MAKE AND MODEL ON EQUIPMENT SCHEDULE.
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE
 DIMENSIONED AND DRAWN UPON SUITABLE MATERIAL.
 CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY
 TO INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK
 PROPOSED AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE
 PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES,
 RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING
 OFFICIAL.
  
 2. OWNER/AGENT TO SIGN ENERGY SUBMITTAL FORM R405-2014.
 FBCE-101.5.1.1.2 SIMULATED PERFORMANCE ALTERNATIVE.
 AN ACCURATELY COMPLETED RESIDENTIAL BUILDING FORM R405
 (GENERATED BY COMMISSION APPROVED SOFTWARE) SHALL BE
 SUBMITTED TO THE BUILDING OFFICIAL TO DEMONSTRATE CODE
 COMPLIANCE BY SECTION 405.
  
 3. BUILDER/CONTRACTOR TO SIGN ENERGY PERFORMANCE LEVEL
 (EPL) DISPLAY CARD.
 R401.3 ENERGY PERFORMANCE LEVEL (EPL) DISPLAY CARD
 (MANDATORY).
 THE BUILDING OFFICIAL SHALL REQUIRE THAT AN ENERGY
 PERFORMANCE LEVEL (EPL) DISPLAY CARD BE COMPLETED AND
 CERTIFIED BY THE BUILDER TO BE ACCURATE AND CORRECT
 BEFORE FINAL APPROVAL OF THE BUILDING FOR OCCUPANCY.
 FLORIDA LAW [SECTION 553.9085, FLORIDA STATUTES)]
 REQUIRES THE EPL DISPLAY CARD TO BE INCLUDED AS AN
 ADDENDUM TO EACH SALES CONTRACT FOR BOTH PRESOLD AND
 NON-PRESOLD RESIDENTIAL BUILDINGS. THE EPL DISPLAY CARD
 CONTAINS INFORMATION INDICATING THE ENERGY PERFORMANCE
 LEVEL AND EFFICIENCIES OF COMPONENTS INSTALLED IN A
 DWELLING UNIT. THE BUILDING OFFICIAL SHALL VERIFY THAT
 THE EPL DISPLAY CARD COMPLETED AND SIGNED BY THE
 BUILDER ACCURATELY REFLECTS THE PLANS AND
 SPECIFICATIONS SUBMITTED TO DEMONSTRATE CODE COMPLIANCE
 FOR THE BUILDING. A COPY OF THE EPL DISPLAY CARD CAN BE
 FOUND IN APPENDIX C.
  
 4. PROVIDE 2ND COPY OF ENERGY SUBMITTAL.
 FBC107.1 GENERAL. SUBMITTAL DOCUMENTS CONSISTING OF
 CONSTRUCTION DOCUMENTS, STATEMENT OF SPECIAL
 INSPECTIONS, GEOTECHNICAL REPORT AND OTHER DATA SHALL
 BE SUBMITTED IN TWO OR MORE SETS WITH EACH PERMIT
 APPLICATION.
  
 5. PROVIDE RETURN AIR IN FRONT LEFT BEDROOM.
 M1602.4 BALANCED RETURN AIR
 ( BEDROOM) 2017 RESIDENTIAL CODE
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY
 REVIEWED SHEETS DETACHED.
  
  
  
  
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2018-08-27 Cont ID  
Sent By hmoser Date 2018-08-27 Time 15:12 Rev Time 0.00
Received By hmoser Date 2018-08-27 Time 14:04 Sent To  
Notes
2018-08-27 15:12:45PLAN DENIED
 PROVIDE AIR CONDITIONING INFORMATION ON
 EQUIPMENT SCHEDULE. SECTION 107 FBC
 2017.
  
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2018-03-23 Cont ID  
Sent By jgomez Date 2018-03-23 Time 17:24 Rev Time 0.00
Received By jgomez Date 2018-03-23 Time 17:24 Sent To  
Notes
2018-03-23 17:33:04RESIDENTIAL (R3) ADDITION/ ALTERATION, MECHANICAL
 REVIEW COMMENTS
 CODE: FBC 6TH EDITION (2017).
  
 1- PROVIDE COMPLETE EQUIPMENT SIZING CALCULATIONS AS
 REQUIRED BY SEC. M1401.3 FBC-RESIDENTIAL.
 M1401.3 EQUIPMENT AND APPLIANCE SIZING.
 HEATING AND COOLING EQUIPMENT AND APPLIANCES SHALL BE
 SIZED IN ACCORDANCE WITH ACCA MANUAL S OR OTHER
 APPROVED SIZING METHODOLOGIES BASED ON BUILDING LOADS
 CALCULATED IN ACCORDANCE WITH ACCA MANUAL J OR OTHER
 APPROVED HEATING AND COOLING CALCULATION METHODOLOGIES.
  
 2- PROVIDE COMPLETE EQUIPMENT SPECIFICATIONS ON THE
 MECHANICAL PLAN. SEC. 107.5.3(11) CITY AMENDMENTS.
 NOTE: COORDINATE WITH ITEM #1 ABOVE. ALSO, COORDINATE
 CFM'S SHOWN ON PLAN WITH EQUIPMENT SIZE TO AVOID
 CONFLICTS/DELAYS.
  
 3- THE RETURN AIR CAN NOT BE TAKEN FROM THE KITCHEN.
 REVISE A S REQUIRED. SEC. M1602.2 FBC-RESIDENTIAL.
  
 4- MASTER BATHROOM NEEDS ANOTHER EXHAUST FAN. ONLY ONE
 SHOWN IN THE WATER CLOSET COMPARTMENT. REVISE AS
 REQUIRED. SEC. R303.3 AND SEC. M1507.2 FBC-RESIDENTIAL.
  
 5- BEDROOM ADJACENT TO THE MASTER BEDROOM IS MISSING
 THE RETURN AIR OPENING FOR BALANCE RETURN AIR AS
 REQUIRED BY SEC. M1602.3. REVISE AS REQUIRED.
  
 6- ENGINEER OF RECORD TO SIGN AND SEAL DRAWING AS
 REQUIRED BY CHAPTER 471 F.S. WHEN SUBMITTING DOCUMENTS
 FOR PUBLIC RECORDS.
  
  
 ****PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO HELP EXPEDITE THE REVIEW PROCESS.
  
 ****PLEASE INSERT ANY REVISED DRAWING AND REMOVE OLD
 DRAWING. SUBMIT OLD DRAWINGS FOR REFERENCE OF ALREADY
 REVIEWED DRAWINGS. DON?T STAPLE OLD DRAWINGS TO PLANS.
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]

Review Stop P PLUMBING
Rev No 3 Status P Date 2019-01-02 Cont ID  
Sent By cthroop Date 2019-01-02 Time 15:38 Rev Time 0.00
Received By cthroop Date 2018-12-31 Time 17:04 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2018-08-28 Cont ID  
Sent By jgomez Date 2018-08-28 Time 13:09 Rev Time 0.00
Received By jgomez Date 2018-08-28 Time 13:06 Sent To  
Notes
2018-08-28 13:23:01RESIDENTIAL (R3) ADDITION/ ALTERATION, SECOND PLUMBING
 REVIEW CHECKLIST.
 CODE: FBC 6TH EDITION (2017).
  
 1- PROVIDE SANITARY RISER DIAGRAM. SEC. 107.5.3(12)
 CITY AMENDMENTS. NOTE: SHOW LOCATION OF ALL VENTS.
  
 ****PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO HELP EXPEDITE THE REVIEW PROCESS.
  
 ****PLEASE INSERT ANY REVISED DRAWING AND REMOVE OLD
 DRAWING. SUBMIT OLD DRAWINGS FOR REFERENCE OF ALREADY
 REVIEWED DRAWINGS. DON?T STAPLE OLD DRAWINGS TO PLANS.
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2018-03-23 Cont ID  
Sent By jgomez Date 2018-03-23 Time 18:05 Rev Time 0.00
Received By jgomez Date 2018-03-23 Time 18:05 Sent To  
Notes
2018-03-23 18:07:11RESIDENTIAL (R3) ADDITION/ ALTERATION, PLUMBING REVIEW
 COMMENTS
 CODE: FBC 6TH EDITION (2017).
  
 1- PROVIDE PLUMBING RISER DIAGRAM. SEC. 107.5.3(12)
 CITY AMENDMENTS.
  
 ****PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO HELP EXPEDITE THE REVIEW PROCESS.
  
 ****PLEASE INSERT ANY REVISED DRAWING AND REMOVE OLD
 DRAWING. SUBMIT OLD DRAWINGS FOR REFERENCE OF ALREADY
 REVIEWED DRAWINGS. DON?T STAPLE OLD DRAWINGS TO PLANS.
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status P Date 2018-08-28 Cont ID  
Sent By jgomez Date 2018-08-28 Time 13:04 Rev Time 0.00
Received By jgomez Date 2018-08-28 Time 13:04 Sent To  
Notes
2018-08-28 13:05:48A) SHINGLES NOA 16-0811.11.
  
 B) UNDERLAYMENT NOA 15-0707.09.

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2018-03-23 Cont ID  
Sent By jgomez Date 2018-03-23 Time 18:07 Rev Time 0.00
Received By jgomez Date 2018-03-23 Time 13:45 Sent To  
Notes
2018-03-23 18:08:231- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.001 FOR:
 A) PEEL & STICK ROOF UNDERLAYMENT FOR SHINGLES AS
 SPECIFIED ON WALL SECTIONS.
  
 D) ROOF SHINGLES AS SHOWN ON PLANS.

Review Stop Z ZONING
Rev No 4 Status F Date 2019-01-28 Cont ID  
Sent By fmittner Date 2019-01-28 Time 15:31 Rev Time 0.00
Received By fmittner Date 2019-01-28 Time 15:31 Sent To M
Notes
2019-01-28 15:31:33COMMENTS FROM LAST REVIEW NOT ADDRESSED.

Review Stop Z ZONING
Rev No 3 Status F Date 2018-12-14 Cont ID  
Sent By fmittner Date 2018-12-14 Time 15:26 Rev Time 0.00
Received By fmittner Date 2018-12-14 Time 15:26 Sent To  
Notes
2018-12-14 15:27:12SEPARATE DRIVEWAY AND LANDSCAPE PERMIT TO BE APPLIED
 FOR. APPLICANT INCLUDED THIS INFORMATION IN SAM EPERMIT
 PACKAGE.

Review Stop Z ZONING
Rev No 2 Status F Date 2018-07-27 Cont ID  
Sent By fmittner Date 2018-07-27 Time 12:06 Rev Time 0.00
Received By fmittner Date 2018-07-27 Time 12:06 Sent To  
Notes
2018-07-27 12:09:47REQUIRES SEPARATE LANDSCAPE PERMIT DUE TO VALUE

Review Stop Z ZONING
Rev No 1 Status P Date 2018-03-08 Cont ID  
Sent By fmittner Date 2018-03-08 Time 09:43 Rev Time 0.00
Received By fmittner Date 2018-03-08 Time 09:43 Sent To  
Notes
2018-03-08 09:58:49REQUIRES SEPERATE LANDSCAPE PERMIT. REQURIES SEPERATE
 DRIVEWAY PERMIT.
  
 LANDSCAPE PERMIT MUST BE OBTAINED AND LANDSCAPE
 INSPECTION MUST PASS PRIOR TO FINAL BUILDING INSPECTION
 FOR PERMIT CLOSE OUT. QUESTIONS, CONTACT RAY CARANCI AT
 822-1462.