| Plan Review Stops For Permit 18030010 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2018-05-31 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2018-05-31 |
Time |
14:11 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2018-05-31 |
Time |
14:08 |
Sent To |
I |
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2018-05-11 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2018-05-11 |
Time |
17:14 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2018-05-11 |
Time |
09:13 |
Sent To |
I |
|
| Notes |
| 2018-05-11 17:14:29 | PLAN | | | REVIEW COMMENTS | | | | | | 2ND REVIEW: FBC FIFTH EDITION (2014) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) THE OWNER/AGENT IS REQUIRED TO SIGN AND DATE THE | | | FORMS. FBC ENERGY CONSERVATION R103.1.1.2 | | | | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2018-03-06 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2018-03-06 |
Time |
16:55 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2018-03-06 |
Time |
16:55 |
Sent To |
M |
|
| Notes |
| 2018-03-06 17:38:52 | PLAN | | | REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC FIFTH EDITION (2014) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) THE SCOPE OF WORK FOR THIS PERMIT IS FOR THE | | | INTERIOR REMODEL OF THE MAIN HOUSE AND A GUEST HOUSE. | | | THE PLANS THAT ARE ON FILE DO NOT INDICATE THAT ANY | | | HVAC WORK OTHER THAN INSTALLATION OF BATH, KITCHEN AND | | | DRYER EXHAUST IN THE MAIN HOUSE. NO ENERGY FORMS WERE | | | REQUIRED. PLEASE CLARIFY WHY YOU ARE SUBMITTING ENERGY | | | FORMS AND EQUIPMENTS SIZING CALCULATIONS UNDER THIS | | | PERMIT. FBC 107.2.1 | | | | | | 2) THE FORMS THAT WERE SUBMITTED ARE FOR THE 2017 FBC | | | (FORM R405-2017), THIS PROJECT IS PERMITED UNDER THE | | | 2014 FBC (FORM R405-2014). | | | | | | 3) THERE ARE TWO BUILDINGS AT THIS LOCATION. SPECIFY | | | EITHER MAIN HOUSE OR GUEST HOUSE ON THE FORMS. FBC | | | 107.2.1 | | | | | | 4) THERE WAS NO ADDITION IN THE SCOPE OF WORK FOR THIS | | | PROJECT. IF THERE IS AN ADDITION, THEN THE PLANS WILL | | | BE REQUIRED TO HAVE AN IMPACT FEE REVIEW. FBC 107.2.1 | | | | | | 5) BOTH OF THE STRUCTURES HAVE BEDROOMS AND NO BEDROOMS | | | IS SPECIFIED ON THE FORMS. CLARIFY. FBC 107.2.1 | | | | | | 6) THE OWNER/AGENT IS REQUIRED TO SIGN AND DATE THE | | | FORMS. FBC ENERGY CONSERVATION R103.1.1.2 | | | | | | 7) SUBMIT THE COMPLETE EQUIPMENT SIZING CALCULATIONS | | | NOT JUST THE SUMMARY PAGE. FBC 107.2.1.3 | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2018-05-31 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2018-05-31 |
Time |
14:11 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2018-05-29 |
Time |
10:20 |
Sent To |
|
|
| Notes |
| 2018-05-30 10:21:09 | RESUB ROUTED TO HMOSER |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2018-05-11 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2018-05-11 |
Time |
17:14 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2018-05-07 |
Time |
14:36 |
Sent To |
|
|
| Notes |
| 2018-05-08 14:37:07 | RESUB ROUTED TO HMOSER |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2018-03-08 |
|
|
Cont ID |
|
| Sent By |
hmoser |
Date |
2018-03-08 |
Time |
10:18 |
Rev Time |
0.00 |
| Received By |
hmoser |
Date |
2018-03-01 |
Time |
12:54 |
Sent To |
|
|
| Notes |
| 2018-03-02 12:54:26 | REVISION ROUTED TO RMCDOUGAL |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
P |
Date |
2018-05-31 |
|
|
Cont ID |
|
| Sent By |
hmoser |
Date |
2018-05-31 |
Time |
13:46 |
Rev Time |
0.00 |
| Received By |
hmoser |
Date |
2018-05-31 |
Time |
13:46 |
Sent To |
I |
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2018-05-09 |
|
|
Cont ID |
|
| Sent By |
hmoser |
Date |
2018-05-09 |
Time |
11:21 |
Rev Time |
0.00 |
| Received By |
hmoser |
Date |
2018-05-09 |
Time |
11:13 |
Sent To |
B |
|
| Notes |
| 2018-05-09 11:21:45 | REVISION DENIED | | | 1) THERE IS NO OWNER AGENT SIGNATURE | | | ON ENERGY CALCULATIONS. | | | 2) THERE IS NO MECHANICAL PLAN ISSUED | | | CAN'T DO A REVISION ON THE HEAT LOAD | | | TRIED TO CALL CONTACT PERSON CAN'T READ | | | PHONE NUMBER. | | | | | | PLAN REVIEW BY HAROLD MOSER | | | [email protected] | | | OFFICE 561-805-6732 | | | FAX 561-805-6676 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2018-03-08 |
|
|
Cont ID |
|
| Sent By |
hmoser |
Date |
2018-03-08 |
Time |
10:18 |
Rev Time |
0.00 |
| Received By |
hmoser |
Date |
2018-03-08 |
Time |
10:09 |
Sent To |
I |
|
| Notes |
| 2018-03-08 10:18:21 | PLAN DENIED | | | THERE WERE NO AIR CONDITIONING PLAN SUBMITTED | | | ON THIS JOB. CAN NOT DO A REVISION. | | | | | | PLAN REVIEW BY HAROLD MOSER | | | [email protected] | | | OFFICE 561-805-6732 | | | FAX 561-805-6676 |
|
|