Plan Review Details - Permit 18021230
Plan Review Stops For Permit 18021230
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2018-08-25 Cont ID  
Sent By shill Date 2018-08-25 Time 18:20 Rev Time 0.00
Received By shill Date 2018-08-25 Time 18:20 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-03-26 Cont ID  
Sent By jwitmer Date 2018-03-26 Time 14:41 Rev Time 0.00
Received By jwitmer Date 2018-03-26 Time 09:51 Sent To  
Notes
2018-03-26 14:40:592017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 18021230
 ADD: 901 45TH ST.
 CONT: WESTBROOKE CORPORATION
 TEL: 561-395-4126
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: MONDAY MARCH 26, 2018
 ACTION: DENIED
  
 1A) SHEET A1.1 NOTE # 1 INDICATES NEW WALL LOUVERS .
 SHEET M1.1 INDICATES THE INSTALLATION OF (2) LOUVERS,
 ONE 10 FOOT WIDE X 8 FEET TALL AND THE OTHER A 2 X2
 FOOT MAKE UP AIR LOUVER. PLEASE SUBMIT PRODUCT
 APPROVALS TO COMPLY WITH:
 2017 FBC-B 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA
 DEPARTMENT OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE
 61G20-3.005, RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY
 OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE
 PRODUCT APPROVALS:
 (31)(C) WALL LOUVERS.
  
 1B) W. P. B. 107.3.4.1 PRODUCT APPROVALS. THOSE
 PRODUCTS WHICH ARE REGULATED BY THE DCA RULE 9N-03
 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL. FL 61G1-23.015 (2) THE
 ARCHITECT IS RESPONSIBLE FOR SUPERVISING AND REVIEWING
 ALL PROJECT DATA, REPORTS, SHOP DRAWINGS ETC..
  
 2) A MIAMI-DADE NOA 17-0320.06 A STEEL CRAFT H SERIES
 FLUSH OUTSWING COMMERCIAL DOOR W/ WO PANIC EXIT LMI WAS
 SUBMITTED PLEASE IDENTIFY ON SHEET 1 OF 13 WHICH DOOR
 IS TO BE INSTALLED WITH THE APPROPRIATE PRESSURES.
 107.2.1.3 ADDITIONAL INFORMATION IS REQUIRED TO
 DETERMINE CODE COMPLIANCE FOR PRESSURES.
  
 3) A MIAMI-DADE NOA 16-0413.21 JOHNS MANVILLE MODIFIED
 BITUMEN ROOFING SYSTEMS OVER STEEL DECKS WAS SUBMITTED.
 THIS REPORT HAS 78 PAGES WITHIN THE REPORT.
 FOR ALL ROOFING PRODUCTS PLEASE IDENTIFY ALL ROOFING
 SUB-SYSTEMS AND THEIR ASSOCIATED PRESSURES FOR ROOF
 ZONE # 1. REVIEW THE PRODUCT APPROVAL LIMITATIONS, IF
 ENHANCED FASTENING IS ALLOWED FOR ROOF ZONES 2 & 3.
 FASTENER DENSITIES SHALL BE INCREASED FOR BOTH
 INSULATION & THE BASE SHEET AS CALCULATED IN COMPLIANCE
 WITH ROOFING APPLICATION STANDARDS RAS 117. CALCULATION
 PREPARED, SIGNED AND
 SEALED BY A FLORIDA REGISTERED PROFESSIONAL ENGINEER OR
 REGISTERED ARCHITECT. 1609.6.4.4.1 COMPONENTS &
 CLADDING.
  
 4A) SHEET A2.1 AND SHEET M1.1 BOTH SHOW NEW NOA RATED
 ROOF PROPELLER SUPPLY FANS WITH HOODS. THIS REVIEW NO
 SUCH PRODUCT APPROVALS WERE SUBMITTED. PLEASE PROVIDE
 COMPLIANCE WITH:
 2017 FBC-B SECTION 1609.6.4.4.1 COMPONENTS & CLADDING.
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS, ADMINISTRATIVE
 CODE 61G20-3.005, RULE 9N-3 NOV. 01/ 2010 (31)
 SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT
 WILL REQUIRE PRODUCT APPROVALS:
 (31) (D) ROOFING PRODUCTS AND ASSEMBLIES, ROOF TOP
 VENTILATORS, ETC.
  
 4B) W. P. B. 107.3.4.1 PRODUCT APPROVALS. THOSE
 PRODUCTS WHICH ARE REGULATED BY THE DCA RULE 9N-03
 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL. FL 61G1-23.015 (2) THE
 ARCHITECT IS RESPONSIBLE FOR SUPERVISING AND REVIEWING
 ALL PROJECT DATA, REPORTS, SHOP DRAWINGS ETC..
  
 5A) SHEET A2.2 AND S-100 BOTH SHOW NEW ROOF TOP CURBS
 THAT THE ROOF TOP FANS SIT ON. S-100 DETAIL 01 ROOF
 SECTION INDICATES THE ROOF TOP CURBS WILL NEED TO
 PROVIDE A NOA, A MIAMI-DADE NOTICE OF ACCEPTANCE
 REPORT, NONE WERE SUBMITTED. PLEASE PROVIDE COMPLIANCE
 WITH:
 2017 FBC-B SECTION 1609.6.4.4.1 COMPONENTS & CLADDING.
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS, ADMINISTRATIVE
 CODE 61G20-3.005, RULE 9N-3 NOV. 01/ 2010 (31)
 SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT
 WILL REQUIRE PRODUCT APPROVALS:
 (31) (D) ROOFING PRODUCTS AND ASSEMBLIES, ROOF TOP
 VENTILATORS, ETC.
  
 5B) W. P. B. 107.3.4.1 PRODUCT APPROVALS. THOSE
 PRODUCTS WHICH ARE REGULATED BY THE DCA RULE 9N-03
 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL. FL 61G1-23.015 (2) THE
 ARCHITECT IS RESPONSIBLE FOR SUPERVISING AND REVIEWING
 ALL PROJECT DATA, REPORTS, SHOP DRAWINGS ETC..
  
 5C) SHEET S-100 DETAIL 01 INDICATES THE ROOF TOP FANS
 TO CURB AS PER THE MANUFACTURERS RECOMMENDATIONS. FOR
 ALL ROOF TOP EQUIPMENT, CURBS, FANS OR VENTILATORS,
 DETAILED ATTACHMENT TO THE ROOF FRAMING & DECK AS WELL
 AS FROM THE CURB TO THE EQUIPMENT ABOVE.
  
 2017 FBC-B 1604.4 ANALYSIS. LOAD EFFECTS ON STRUCTURAL
 MEMBERS AND THEIR CONNECTIONS SHALL BE DETERMINED BY
 METHODS OF STRUCTURAL ANALYSIS THAT TAKE INTO ACCOUNT
 EQUILIBRIUM, GENERAL STABILITY, GEOMETRIC COMPATIBILITY
 AND BOTH SHORT- AND LONG-TERM MATERIAL PROPERTIES.
 EVERY STRUCTURE SHALL BE DESIGNED TO RESIST THE
 OVERTURNING EFFECTS CAUSED BY THE LATERAL FORCES
 SPECIFIED IN THIS CHAPTER. SEE SECTION 1609 FOR WIND
 LOADS.
  
 6 SHEET A2.1 NOTE # 8 INDICATES NEW EXHAUST DUCT COVER
 AND REFERS TO SHEET A2.2 DETAIL # 5. THERE IS NO
 MENTION ON THE STRUCTURAL SHEETS OF THE NEW EXHAUST
 DUCT COVER. THE SHEET M1.2 NOTES 6 & 8 BOTH MAKE
 REFERENCE TO THE EXTERIOR DUCT AND COVER TO BE ANCHORED
 TO THE BUILDING TO RESIST HURRICANE FORCE WINDS, 180
 MPH VULT, CATEGORY III BUILDING. PLEASE PROVIDE
 ADDITIONAL INFORMATION TO BE ABLE TO SHOW CODE
 COMPLIANCE. 107.2.1.3 ADDITIONAL INFORMATION IS
 REQUIRED.
  
 7) THE STRUCTURAL SHEET DOES NOT MENTION HOW THE 16
 INCH VENT THAT EXTENDS UP THE 3 STORY BUILDING AND 10
 FEET ABOVE THE PENTHOUSE LEVEL IS TO BE SECURED AGAINST
 HURRICANE FORCE WINDS (180 MPH VULT). SHEET M1.3 THE
 PENTHOUSE DETAIL MENTIONS THIS BUT NEITHER SHEET
 PROVIDES AN ENGINEERING DETAIL HOW THIS WILL BE
 ACCOMPLISHED.
 FOR ALL ROOF TOP EQUIPMENT, CURBS, FANS OR A/C STANDS,
 AND OR VENTS, DETAILED ATTACHMENT TO THE ROOF FRAMING &
 DECK AS WELL AS FROM THE CURB OR ROOF STAND TO THE
 EQUIPMENT ABOVE.
  
 2017 FBC-B 1604.4 ANALYSIS. LOAD EFFECTS ON STRUCTURAL
 MEMBERS AND THEIR CONNECTIONS SHALL BE DETERMINED BY
 METHODS OF STRUCTURAL ANALYSIS THAT TAKE INTO ACCOUNT
 EQUILIBRIUM, GENERAL STABILITY, GEOMETRIC COMPATIBILITY
 AND BOTH SHORT- AND LONG-TERM MATERIAL PROPERTIES.
 EVERY STRUCTURE SHALL BE DESIGNED TO RESIST THE
 OVERTURNING EFFECTS CAUSED BY THE LATERAL FORCES
 SPECIFIED IN THIS CHAPTER. SEE SECTION 1609 FOR WIND
 LOADS.
  
 8) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2018-08-16 Cont ID  
Sent By jpearson Date 2018-08-16 Time 09:51 Rev Time 0.00
Received By jpearson Date 2018-08-16 Time 09:27 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-03-28 Cont ID  
Sent By jpearson Date 2018-03-28 Time 10:44 Rev Time 0.00
Received By jpearson Date 2018-03-27 Time 10:09 Sent To  
Notes
2018-03-28 10:44:51CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. THE NEC AND FBC SPECIFIED FOR DESIGN ON SHEET E0.1
 IS NOT THE CURRENT CODE. PROVIDE CORRECTION. FBC
 PREFACE (ALSO SEE CURRENT CODES ABOVE)
 2. PROVIDE LISTING FOR RECONDITIONED 2000 AMP BREAKER.
 NEC110.3
 3. PROVIDE GFI PROTECTION FOR 2000 AMP BREAKER AND
 DOWNSTREAM PANELS WHERE APPLICABLE. NEC 230.95, 517.17
 4. PLAN STATES THAT THE LOADING OF THE GENERATOR IS
 BASED ON A 3 MONTH STUDY FROM OCTOBER THROUGH DECEMBER
 OF 2016. PER NEC 517.30(D): ?THE ESSENTIAL ELECTRICAL
 SYSTEM SHALL HAVE THE CAPACITY AND RATING TO MEET THE
 MAXIMUM ACTUAL DEMAND LIKELY TO BE PRODUCED BY THE
 CONNECTED LOAD.? THE TIME PERIOD DESCRIBED FOR THE
 STUDY DOES NOT SEEM TO BE THE TIME OF YEAR WHERE THE
 MAXIMUM DEMAND WOULD BE ENCOUNTERED. PROVIDE
 CLARIFICATION AND/OR CORRECTION OF THE DEMAND LOAD FOR
 THE GENERATOR. THIS REVIEWER FEELS THAT LOOKING AT 12
 MONTHS OF HISTORY WOULD GIVE A BETTER REPRESENTATION OF
 THE LIKELY DEMAND. NEC 517.30(D)
 5. PROVIDE DETAILS OF COMPLIANCE WITH NEC 240.87.
 6. BE ADVISED THAT FIRE ALARM, LOW VOLTAGE SYSTEMS,
 DAS, LIGHTNING PROTECTION, COMMERCIAL HOOD SYSTEMS,
 WALK IN COOLERS, SIGNS, SITE LIGHTING, AND SWIMMING
 POOLS (WHERE APPLICABLE) ARE NOT INCLUDED IN THE SCOPE
 OF THIS PLAN REVIEW. PROVIDE A BLOCK NOTE INDICATING
 THE REQUIRED SEPARATE PERMITS AND DATA SPECIFICATION
 SHEET SUBMITTALS FOR ANY OF THESE SYSTEMS PRESENT. WPB
 FBC 105.1, 107.2.1
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2018-08-10 Cont ID  
Sent By pleduc Date 2018-08-10 Time   Rev Time 0.00
Received By pleduc Date 2018-08-10 Time 12:20 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2018-03-29 Cont ID  
Sent By pleduc Date 2018-03-29 Time   Rev Time 0.00
Received By pleduc Date 2018-03-28 Time 14:17 Sent To  
Notes
2018-03-28 16:26:01THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) SHEET A 0.0 - THERE ARE REFERENCES TO APPLICABLE
 NFPA CODES; HWEVER, NFPA 37 IS NOT INDICATED
  
 PER NFPA 110:
  
 7.10 EXHAUST SYSTEM.
 7.10.1 THE EXHAUST SYSTEM EQUIPMENT AND INSTALLATION,
 INCLUDING
 PIPING, MUFFLER, AND RELATED ACCESSORIES, SHALL BE IN
 ACCORDANCE WITH NFPA37, STANDARD FOR THE INSTALLATION
 AND USE OF
 STATIONARY COMBUSTION ENGINES AND GAS TURBINES, AND
 OTHER APPLICABLE
 STANDARDS.
  
 PLEASE REVIEW TO ENSURE COMPLIANCE AND ADD THE
 INDICATED REFERENCE.
  
  
  
  
 2) MECHANICAL SHEETS - THERE IS NO INDICATIONS OF THE
 FOLLOWING:
  
 PER NFPA 110:
  
 7.10.3* EXHAUST PIPING SHALL BE CONNECTED TO THE PRIME
 MOVER
 BY MEANS OF A FLEXIBLE CONNECTOR AND SHALL BE
 INDEPENDENTLY
 SUPPORTED THEREAFTER SO THAT NO DAMAGING WEIGHT OR
 STRESS IS
 APPLIED TO THE ENGINE EXHAUST MANIFOLD OR TURBOCHARGER.
 7.10.3.1 A CONDENSATE TRAP AND DRAIN VALVE SHALL BE
 PROVIDED
 AT THE LOW POINT(S) OF THE PIPING UNLESS THE PIPING IS
 SELFDRAINING.
  
  
  
 3) PRODUCT SPEC SHEETS - THERE ARE NO PRODUC SPEC
 SHEETS INDICATING COMLIANCE WITH THE FOLLOWING:
  
 PER NFPA 37:
  
 CHAPTER 8 ENGINE EXHAUST SYSTEMS
 8.1 DESIGN AND CONSTRUCTION.
 8.1.1* ENGINE EXHAUST SYSTEMS SHALL BE DESIGNED AND
 CONSTRUCTED
 SUCH THAT THE SYSTEM CAN WITHSTAND THE ANTICIPATED
 EXHAUST GAS TEMPERATURES.
 8.1.2* EXHAUST SYSTEMS SHALL BE DESIGNED AND
 CONSTRUCTED TO
 WITHSTAND THE INTENDED SERVICE.
  
 8.1.4* EXHAUST SYSTEMS SHALL BE DESIGNED AND
 CONSTRUCTED TO
 WITHSTAND FORCES CAUSED BY THE IGNITION OF UNBURNED
 FUEL OR
 SHALL HAVE PROVISIONS TO RELIEVE THOSE FORCES WITHOUT
 DAMAGING
 THE EXHAUST SYSTEM.
 8.1.5* LOW POINTS IN EXHAUST SYSTEMS SHALL HAVE DRAINS.
  
 8.3 CLEARANCE FROM EXHAUST SYSTEMS WITH EXHAUST GAS
 TEMPERATURES
 OF LESS THAN 760?C (1400?F).
  
 8.4* CLEARANCE FROM EXHAUST SYSTEMS WITH EXHAUST GAS
 TEMPERATURES
 OF 760?C (1400?F) OR GREATER. EXHAUST SYSTEMS WITH
 EXHAUST GAS TEMPERATURES OF 760?C (1400?F) OR GREATER
 SHALL
 COMPLY WITH NFPA 211, STANDARD FOR CHIMNEYS,
 FIREPLACES, VENTS,
 AND SOLID FUEL?BURNING APPLIANCES.
  
 PLEASE REVIEW AND PROVIDE SHEPC SHEETS OR SPECIFIC
 DETAILS INDICATING COMPLIANCE.
  
  
  
 4) GENERATOR SPEC SHEETS - THERE ARE NO GENERATOR SPEC
 SHEETS INDICATING THAT THE TYPE , SIZE AND LENGTH OF
 THE PROPOSED EXHAUST MEETS THEIR SPECIFICATIONS.
  
 PLEASE PROVIDE THE SPEC SHEETS AND/OR SPECIFIC DETAILS
 OF COMPLIANCE.
  
  
  
  
 5) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 6) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-08-27 Cont ID  
Sent By shill Date 2018-08-27 Time 16:39 Rev Time 0.00
Received By shill Date 2018-07-27 Time 13:37 Sent To  
Notes
2018-07-30 13:37:53B26

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2018-04-03 Time   Rev Time 0.00
Received By lmarchan Date 2018-02-28 Time 09:26 Sent To  
Notes
2018-03-23 10:41:15B25
2018-03-02 09:27:04ROUTED TO ZONING

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2018-08-10 Cont ID  
Sent By ccole Date 2018-08-10 Time 10:54 Rev Time 0.00
Received By ccole Date 2018-08-10 Time 09:26 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2018-04-03 Cont ID  
Sent By ccole Date 2018-04-03 Time 08:35 Rev Time 0.00
Received By ccole Date 2018-04-03 Time 07:20 Sent To I
Notes
2018-04-03 09:06:381ST REVIEW FBC-2017 MECHANICAL, WEST PALM BEACH
 AMENDMENTS TO THE FBC-17
 PERMIT #18021230
 4/3/18
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) REQUIRED SUBMITTALS TO BE PROVIDED PRIOR TO
 PERMITTING:
  
 A) GENERATOR
 B) GENERATOR EXHAUST PIPING
 C) BACKPRESSURE CALCULATIONS FOR EXHAUST PIPING.
 D) NOA'S FOR THE EXHAUST LOUVER, SUPPLY FANS, EXHAUST
 FAN, FAN CURBS, AND EXHAUST PIPE SUPPORTS AND BRACKETS.
 E) FUEL PIPING.
  
 2) SHEET M1.3: ADDITIONAL INFORMATION REQUIRED:
  
 A) THE TOTAL RUN LENGTH OF THE EXHAUST PIPE AND THE
 LENGTH OF EACH SEGMENT FROM ELBOW TO ELBOW.
 B) MAX BACK PRESSURE FROM THE MANUFACTURER.
 C) BACKPRESSURE CALCULATIONS FOR THE EXHAUST PIPE RUN.
 D) TYPES AND SPACINGS OF HORIZONTAL AND VERTICAL PIPE
 SUPPORTS.
 E) FASTENING AND ANCHORING DETAILS FOR EXHAUST PIPE
 SUPPORTS AND BRACKETS.
 F) SHOP DRAWINGS FOR THE VERTICAL VENT PIPE COVER TO BE
 INSTALLED ABOVE THE ROOF INCUDING ANCHORING AND
 FASTENING DETAILS.
  
 3) PLEASE NOTE THAT ALL PRODUCT SUBMITTALS SHALL BE
 REVIEWED AND APPROVED BY THE ENGINEER OF RECORD. PLEASE
 REVIEW THE FOLLOWING WPB AMENDMENT PERTAINING TO
 DEFERRED SUBMITTALS.
  
 DEFERRED SUBMITTAL: 107.3.4.2 DEFERRED SUBMITTALS. FOR
 THE PURPOSES OF THIS SECTION, DEFERRED SUBMITTALS ARE
 DEFINED AS THOSE PORTIONS OF THE DESIGN THAT ARE NOT
 SUBMITTED AT THE TIME OF THEAPPLICATION AND THAT ARE TO
 BE SUBMITTED TO THE BUILDING OFFICIAL WITHIN A
 SPECIFIED PERIOD. DEFERRAL OF ANY SUBMITTAL ITEMS SHALL
 HAVE THE PRIOR APPROVAL OF THE BUILDING OFFICIAL. THE
 REGISTERED DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE
 SHALL LIST THE DEFERRED SUBMITTALS ON THE CONSTRUCTION
 DOCUMENTS FOR REVIEW BY THE BUILDING OFFICIAL.
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD
 THEM TO THE BUILDING OFFICIAL WITH A NOTATION
 INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL
 ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING
 OFFICIAL.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status N Date 2018-03-21 Cont ID  
Sent By tklarge Date 2018-03-21 Time 06:46 Rev Time 0.00
Received By tklarge Date 2018-03-21 Time 06:23 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status N Date 2018-08-25 Cont ID  
Sent By shill Date 2018-08-25 Time 18:10 Rev Time 0.00
Received By shill Date 2018-08-25 Time 18:10 Sent To  
Notes
2018-08-25 18:11:29****PROVISO****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 JOHN MANVILLE NOA 16-0413.21 WAS SUBMITTED
 ROOFING CONTRACTOR IS TO INDICATE WHICH APPROVED
 ASSEMBLY IS SELECTED AND PROVIDE RAS117 CALCULATIONS IF
 REQUIRED
  
  

Review Stop Z ZONING
Rev No 2 Status P Date   Cont ID  
Sent By   Date 2018-08-27 Time   Rev Time 0.00
Received By pgreilic Date 2018-08-07 Time 12:05 Sent To  
Notes
2018-08-27 14:44:46PAUL GREILICH, SENIOR PLANNER
 561-822-1443
 [email protected]

Review Stop Z ZONING
Rev No 1 Status P Date   Cont ID  
Sent By   Date 2018-03-09 Time   Rev Time 0.00
Received By pgreilic Date 2018-03-07 Time 13:27 Sent To  
Notes
2018-03-09 13:28:06 
  
 PAUL GREILICH, SENIOR PLANNER
 561-822-1443
 [email protected]