Plan Review Details - Permit 18021229
Plan Review Stops For Permit 18021229
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2018-05-15 Cont ID  
Sent By shill Date 2018-05-15 Time 09:00 Rev Time 0.00
Received By shill Date 2018-05-15 Time 09:00 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2018-05-13 Cont ID  
Sent By shill Date 2018-05-13 Time 12:17 Rev Time 0.00
Received By shill Date 2018-05-13 Time 12:17 Sent To  
Notes
2018-05-13 12:20:00****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. I SPOKE WITH SOMEONE WHO VERBALLY TOLD ME WHICH
 FLOORING UNDERLAYMENT WAS PROPOSED, BUT THERE IS
 NOTHING IN THE PACKAGE. THE ONE PROPOSED IS ONE FOR
 WHICH WE HAVE TEST REPORTS ON FILE, BUT SINCE NOTHING
 WAS SUBMITTED, NOT INDICATED ON THE PLAN OR THE PERMIT
 APPLICATION, AND I REVIEW DOZENS OF PROJECTS EACH
 MONTH, I CANNOT RECALL WHAT PRODUCT WAS PROPOSED.
  
 APPLICANT IS TO PROVIDE TEST REPORTS (UNLESS APPLICANT
 KNOWS WE HAVE THE TEST REPORTS ON FILE, IN WHICH CASE A
 SPEC SHEET OR OTHER WISE INDICATED PRODUCT IS
 ACCEPTABLE).
  
 A. FBC 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR
 BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90.
 THE TEST REPORT CANNOT INCLUDE A DROPPED GYPSUM
 CEILING. PROVIDE A COPY OF THE TEST REPORT.
  
 B. FBC 1207.3, FLOOR/CEILING ASSEMBLIES BETWEEN
 DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC
 OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN
 IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN
 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH
 ASTM E 492. THE TEST REPORT CANNOT INCLUDE A DROPPED
 GYPSUM CEILING. PROVIDE A COPY OF THE TEST REPORT.
  
 C. FBC 603.1, ALLOWABLE MATERIALS IN NON COMBUSTIBLE
 BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. SEE
 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM E 84
 OR UL 723.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-03-07 Cont ID  
Sent By jwitmer Date 2018-03-07 Time 06:58 Rev Time 0.00
Received By jwitmer Date 2018-03-07 Time 06:15 Sent To  
Notes
2018-03-07 06:48:292017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 18021229
 ADD: 400 N. FLAGLER DR. SUITE: 503
 CONT: USHER & ASSOCIATES
 TEL: 561-543-2185
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: WED. MARCH 07/2018
 ACTION: DENIED
  
 1) THE DRAFTSMAN ANDRE GERALD HARRIS INC. MAY QUALIFY
 UNDER THE F. S. 481.229 EXEMPTION (1)( C ) TO DESIGN
 THE SUBMITTED PLANS BUT NOT UNDER THE 2017 FLORIDA
 BUILDING CODE W 2017 WEST PALM BEACH AMENDMENTS TO THE
 FLORIDA BUILDING CODE, CHAPTER 1, ADMINISTRATION
 107.3.4.3 CERTIFICATION BY CONTRACTOR. PLEASE NOTE THE
 EXCEPTION TO ENGINEERED PLANS UNDER 471.003(H)
 ELECTRICAL/ PLUMBING/ MECHANICAL, 481.229(1)(C)
 (BUILDING) REQUIRES THE CONTRACTOR FOR THAT TRADE THAT
 WILL BE LICENSED IN THAT TRADE, WILL ALSO BE THE
 CONTRACTOR THAT DESIGNS THE SYSTEM UNDER THAT TRADE.
 FOR EACH TRADE THE CONTRACTOR RESPONSIBLE FOR THE
 DESIGN UNDER THE TRADE LICENSED IN MUST PRINT THEIR
 NAME, SIGN THEIR NAME AND LICENSE NUMBER, NOTE THESE
 PLANS APPEAR TO BE DRAWN BY ONE INDUVIAL, THEY WOULD
 HAVE TO BE LICENSED AS A BUILDING, ELECTRICAL AND
 PLUMBING CONTRACTOR TO SUBMIT ALL THESE TRADES UNDER
 ONE SHEET.
  
 2) THE DESIGNER OF RECORD ANDRE GERALD HARRIS INC. HAS
 A WIND DESIGN CRITERIA LISTED ON THE PLANS. YOU CANNOT
 PUT WIND DESIGN ON THE PLANS SINCE YOU ARE NOT
 QUALIFIED TO DO SO. YOUR DESIGN IS ALSO WRONG, THE
 EXPOSURE IS A D EXPOSURE. A CONTRACTOR CAN LIST THE
 WIND DESIGN CRITERIA IF HE HAS THE WIND CERTIFICATION
 ONLY FOR 1 & 2 FAMILY DWELLINGS.
 107.3.4.3 CERTIFICATIONS BY CONTRACTORS AUTHORIZED
 UNDER THE PROVISIONS OF SECTION 489.115 FLORIDA
 STATUTES, SHALL BE CONSIDERED EQUIVALENT TO SEALED
 PLANS AND SPECIFICATIONS BY A PERSON LICENSED UNDER
 CHAPTER 471, FLORIDA STATUTES, OR CHAPTER 481 FLORIDA
 STATUTES, BY LOCAL ENFORCEMENT AGENCIES FOR PLANS
 REVIEW FOR PERMITTING PURPOSES RELATING TO COMPLIANCE
 WITH THE WIND-RESISTANCE PROVISIONS OF THE CODE OR
 ALTERNATE METHODOLOGIES APPROVED BY THE FLORIDA
 BUILDING COMMISSION FOR ONE AND TWO-FAMILY DWELLINGS.
 LOCAL ENFORCEMENT AGENCIES MAY RELY UPON SUCH
 CERTIFICATION BY CONTRACTORS THAT THE PLANS AND
 SPECIFICATIONS SUBMITTED CONFORM TO THE REQUIREMENTS OF
 THE CODE FOR WIND RESISTANCE. UPON GOOD CAUSE SHOWN,
 LOCAL GOVERNMENT CODE ENFORCEMENT AGENCIES MAY ACCEPT
 OR REJECT PLANS SEALED BY PERSONS LICENSED UNDER
 CHAPTERS 471,481 OR 489, FLORIDA STATUTES.
  
 3) THE A1 SHEET LIST THE REMOVAL OF FLOOR TILE. BLDG
 TYPE: TYPE I/ TYPE II FLOOR INSULATION (FBC-B 2014)
 FOR TILE, STONE, MARBLE, VINYL AND WOOD FLOORING ALL
 NEED TO HAVE HAD THE SOUND UNDERLAYMENT TESTED FLOOR
 ASSEMBLIES TO THE FOLLOWING STANDARDS AND MEET THE
 QUALIFICATIONS LISTED UNDER EACH OF THE STANDARDS FOR A
 6 INCH CONCRETE FLOOR ASSEMBLY/ NO DROPPED CEILING:
 PLEASE PROVIDE TEST REPORTS SHOWING COMPLIANCE WITH:
  
 3A) FBC-B 2014 1207.3 STRUCTURE-BORNE SOUND.
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492.
  
 3B) FBC-B 2014 1207.2 AIR-BORNE SOUND.
 WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES
 SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM
 PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION
 CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED)
 FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM
 E 90.
  
 3C) FLAME SPREAD- FBC-B 2014 603.1. EXCEPTION 2.
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200.
  
 FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS
 A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL
 MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A
 MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723.
  
 4) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2018-05-02 Cont ID  
Sent By jpearson Date 2018-05-02 Time 11:19 Rev Time 0.00
Received By jpearson Date 2018-05-02 Time 11:19 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-03-19 Cont ID  
Sent By jpearson Date 2018-03-19 Time 17:23 Rev Time 0.00
Received By jpearson Date 2018-03-19 Time 16:24 Sent To  
Notes
2018-03-19 17:23:44CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. ELECTRICAL PLAN IS REQUIRED TO BE DESIGNED AND
 SIGNED/SEALED BY A DESIGN PROFESSIONAL OR THE
 ELECTRICAL CONTRACTOR QUALIFIER. PROVIDE CORRECTION. FS
 471.003(2)(H); 471.025; FBC 107.2.1
 2. LIGHTING OVER SHOWER SHALL BE SUITABLE FOR DAMP
 LOCATIONS. PROVIDE CORRECTION. NEC 410.10(D)
 3. PROVIDE TAMPER RESISTANT RECEPTACLES PER CODE. A
 NOTE WILL SUFFICE. NEC 406.12
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2018-05-04 Cont ID  
Sent By pleduc Date 2018-05-04 Time   Rev Time 0.00
Received By pleduc Date 2018-05-02 Time 16:48 Sent To  
Notes
2018-05-04 09:37:21PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
  
 1) THE EXTENT OF THE REMODEL DOES NOT INDICATE
 SUFFICIENT DETAIL INDICATING THE LOCATION OF ANY FIRE
 SPRINKLER HEADS.
  
 ANY REMOVAL AND/OR CONSTRUCTION OF WALLS AND /OR
 CEILINGS REQUIRE AN EVALUATION OF THE FIRE SPRINKLER
 SYSTEM FOR CODE COVERAGE AND COMPLIANCE BY CERTIFIED
 LIFE SAFETY CONTRACTORS.
  
 THE FIRE INSPECTOR WILL REVIEW AT THE TIME OF FIRE
 INSPECTION.
  
 PLEASE ENSURE A PROPER EVALUATION IS COMPLETED.
  
  
 2) ANY AND ALL WORK ON THE FIRE SPRINKLER SYSTEMS SHALL
 BE DONE UNDER SEPARATE SHOP DRAWINGS AND BY CERTIFIED
 LIFE SAFETY CONTRACTORS.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 561-804-4709
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2018-03-06 Cont ID  
Sent By pleduc Date 2018-03-06 Time   Rev Time 0.00
Received By pleduc Date 2018-03-05 Time 12:38 Sent To  
Notes
2018-03-06 14:52:02PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
  
 1) THE EXTENT OF THE REMODEL DOES NOT INDICATE
 SUFFICIENT DETAIL INDICATING THE LOCATION OF ANY FIRE
 SPRINKLER HEADS.
  
 ANY REMOVAL AND/OR CONSTRUCTION OF WALLS AND /OR
 CEILINGS REQUIRE AN EVALUATION OF THE FIRE SPRINKLER
 SYSTEM FOR CODE COVERAGE AND COMPLIANCE BY CERTIFIED
 LIFE SAFETY CONTRACTORS.
  
 THE FIRE INSPECTOR WILL REVIEW AT THE TIME OF FIRE
 INSPECTION.
  
 PLEASE ENSURE A PROPER EVALUATION IS COMPLETED.
  
  
 2) ANY AND ALL WORK ON THE FIRE SPRINKLER SYSTEMS SHALL
 BE DONE UNDER SEPARATE SHOP DRAWINGS AND BY CERTIFIED
 LIFE SAFETY CONTRACTORS.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-05-15 Cont ID  
Sent By shill Date 2018-05-15 Time 09:00 Rev Time 0.00
Received By shill Date 2018-04-27 Time 15:21 Sent To  
Notes
2018-04-30 15:21:15B18

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-03-20 Cont ID  
Sent By cpuell Date 2018-03-20 Time 13:07 Rev Time 0.00
Received By cpuell Date 2018-02-28 Time 14:47 Sent To  
Notes
2018-03-01 14:47:55B32

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2018-03-07 Cont ID  
Sent By jwitmer Date 2018-03-07 Time 06:59 Rev Time 0.00
Received By jwitmer Date 2018-03-07 Time 06:48 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2018-03-14 Cont ID  
Sent By ccole Date 2018-03-14 Time 11:46 Rev Time 0.00
Received By ccole Date 2018-03-14 Time 11:46 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2018-05-14 Cont ID  
Sent By gjohnson Date 2018-05-14 Time 11:23 Rev Time 0.00
Received By gjohnson Date 2018-05-14 Time 11:02 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2018-03-20 Cont ID  
Sent By gjohnson Date 2018-03-20 Time 12:17 Rev Time 0.00
Received By gjohnson Date 2018-03-20 Time 11:27 Sent To  
Notes
***NONE***