Plan Review Details - Permit 18021223
Plan Review Stops For Permit 18021223
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2018-08-13 Cont ID  
Sent By dbattles Date 2018-08-13 Time 16:24 Rev Time 0.00
Received By dbattles Date 2018-08-13 Time 16:24 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2018-06-28 Cont ID  
Sent By shill Date 2018-06-28 Time 18:26 Rev Time 0.00
Received By shill Date 2018-06-28 Time 17:53 Sent To  
Notes
2018-06-28 18:03:05****CORRECTIONS****
 W.P.B. PERMIT: 18021223
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1-2. OK
  
 3. [FBC R401.3] DRAINAGE PLAN PROVIDED NEEDS
 ADJUSTMENTS.
 SIDES SHOW DRAINAGE TO ADJACENT PROPERTIES. PLEASE
 PROVIDE PLAN TO INDICATE HOW YOU WILL HANDLE DRAINAGE
 WITHIN SITE. PROVIDE DRAINS SWALES OR GUTTERS TO SHED
 WATER TO THE FRONT AND BACK.
 PROVIDE ELEVATION OF LOWEST FINISHED FLOOR USING
 NAVD88. PROVIDE DRAINAGE ELEVATIONS TO SHOW HOW IT
 MEETS REQUIRMENTS FROM R401.3
  
 4-8. OK
  
 9 ELEVATION LABLES EAST AND WEST ARE REVERSED. WEST
 ELEVATION SHOULD BE LABLED EAST AND EAST SHOULD BE
 LABLED WEST. PUT ELEVATION CALL OUTS ON PLAN SHEET A-1
 AND ADD NORTH ARROW TO PLAN SHEET A-1 FOR CLARITY.
  
 10-11. OK
  
 12. [FBC R301.1]THERE IS A BREAK IN CONTINUITY WHERE
 6X6 WOOD COLUMN TIES INTO RAISED COLUMN. IT APPEARS
 THAT THE INCREASED MOMENT CONNECTION SHOULD BE BRACED
 OR CONTINUED TO THE FOUNDATION. IT APPEARS THAT THE
 CONNECTOR SPECIFIED, AB66, HAS BEEN DISCONTINUED AS IT
 IS NO LONGER AVAILABLEON THE SIMPSON STRONGTIE WEBSITE.
 THE FLORIDA PRODUCT APPROVAL NUMBER IS FOR A 2014
 APPROVAL. NOTE THAT SIMPSON'S PREVIOUSLY AVAILABLE
 DOCUMENTATION FOR THIS CONNECTOR AND THE DOCUMENTATION
 FOR THE REPLACEMENT CONNECTOR STATE:
  
 "POST BASES DO NOT PROVIDE ADEQUATE RESISTANCE TO
 PREVENT MEMBERS FROM ROTATING ABOUT THE BASE AND
 THEREFORE ARE NOT RECOMMENDED FOR NON-TOP-SUPPORTED
 INSTALLATIONS (SUCH AS FENCES OR UNBRACED CARPORTS)."
  
 PLEASE CONTACT ME IF YOU DISAGREE AND WISH TO DISCUSS.
  
 13. OK
  
 14. COMMENT PARTIALLY ADDRESSED.
 THE SOILS REPORT STATES THAT THE BOTTOM OF FOOTER
 SHOULD BE AT LEAST 18" BELOW GRADE. THE PLAN WAS
 UPDATED TO SHOW 18" BELOW FINISHED FLOOR THAT ONLY
 PROVIDES 14" BELOW FINISHED GRADE. PLEASE UPDATE OR
 PROVIDE LETTER SHOWING ANALYSIS OF HOW PROPOSED DESIGN
 WILL MEET THE SOILS TEST REPORT.
  
 15-16. OK
  
 17. A) OK
 B) OK
 C) CORRECT SHEET S-2 TO MATCH NOA # THAT WAS PROVIDED
 (NOA 17-0821.190
 D) OK
  
 18-19. OK
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-03-19 Cont ID  
Sent By jgomez Date 2018-03-19 Time 17:58 Rev Time 0.00
Received By jgomez Date 2018-03-19 Time 12:49 Sent To  
Notes
2018-03-19 13:00:27NEW SINGLE FAMILY RESIDENCE (R3) BUILDING REVIEW
 COMMENTS
 CODE: FBC 6TH EDITION (2017).
  
 1-BEFORE A PERMIT TO CONSTRUCT CAN BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. UPON APPROVAL,
 ONE SET OF PLANS SHALL BE SIGNED OUT AND SUBMITTED TO
 PALM BEACH COUNTY FOR AN IMPACT FEE REVIEW. THE PLANS
 WITH THE IMPACT FEE STAMP AND A COPY OF THE PAID
 RECEIPT MUST BE RETURNED TO THE CITY BUILDING
 DEPARTMENT BEFORE THE BUILDING PERMIT CAN BE ISSUED.
 FOR INFORMATION CALL PALM BEACH COUNTY IMPACT FEES AT
 (561) 233-5025.
  
 2- SITE PLAN ON SHEET C-1 IS NOT LEGIBLE AND IS MISSING
 ALL DIMENSIONS. PROVIDE COMPLETE AND LEGIBLE
 INFORMATION. CITY AMENDMENTS 107.3.5.3 RESIDENTIAL (ONE
 AND TWO-FAMILY).
  
 3- PROVIDE DRAINAGE PLAN SHOWING COMPLIANCE WITH SEC.
 R401.3 FBC-RESIDENTIAL:
 SURFACE DRAINAGE SHALL BE DIVERTED TO A STORM SEWER
 CONVEYANCE OR OTHER APPROVED POINT OF COLLECTION THAT
 DOES NOT CREATE A HAZARD. LOTS SHALL BE GRADED TO DRAIN
 SURFACE WATER AWAY FROM FOUNDATION WALLS. THE GRADE
 SHALL FALL A MINIMUM OF 6 INCHES (152 MM) WITHIN THE
 FIRST 10 FEET (3048 MM).
 EXCEPTION: WHERE LOT LINES, WALLS, SLOPES OR OTHER
 PHYSICAL BARRIERS PROHIBIT 6 INCHES (152 MM) OF FALL
 WITHIN 10 FEET (3048 MM), DRAINS OR SWALES SHALL BE
 CONSTRUCTED TO ENSURE DRAINAGE AWAY FROM THE STRUCTURE.
 IMPERVIOUS SURFACES WITHIN 10 FEET (3048 MM) OF THE
 BUILDING FOUNDATION SHALL BE SLOPED A MINIMUM OF 2
 PERCENT AWAY FROM THE BUILDING.
  
 4- ROOF PITCH OF 2:12 REQUIRES TWO LAYERS OF
 UNDERLAYMENT. SEC. R905.1.1 FBC-RESIDENTIAL. PROVIDE
 SPECIFICATIONS ON PLANS.
  
 5- THE CURRENT CODE IS THE FBC 6TH EDITION (2017) NOT
 THE FBC 5TH EDITION (2014). CHAPTER 553 FLORIDA
 STATUTE. UPDATE ALL NOTES ON SHEETS C-1, A-2, S-1, S-2
 PLANS AS REQUIRED.
  
 6- PROVIDE DETAIL/SPECS FOR FLOOR INSULATION R-11 AS
 SPECIFIED ON SHEET A-1. SEC. 107.2.1 CITY AMENDMENTS.
  
 7- SHEET A-2: REVISE THE WIND DESIGN CRITERIA. WALL
 DIMENSION FOR END ZONE "A" IS 4'-0" NOT "3". FIGURE
 R301.2(7) FBC-RESIDENTIAL COMPONENT AND CLADDING
 PRESSURE ZONES
  
 8- PROVIDE COMPLETE SKYLIGHT FRAMING DETAILS AND
 SPECIFICATIONS. SPECIFY ALL FRAMING MEMBERS AND
 CONNECTORS. SEC. R301.1 FBC-RESIDENTIAL. NOTE: SPECIFY
 SKYLIGHT SIZE.
  
 9- WINDOW DESIGN PRESSURES SOWN ON SHEET A-1 DON'T
 CORRESPOND TO EXPOSURE "D" AS SPECIFIED ON THE WIND
 DESIGN CRITERIA ON SHEET S-2. ALSO, SPECIFY THE DESIGN
 PRESSURES FOR ALL THE EXTERIOR DOORS AND SKYLIGHTS
 SPECIFIED ON PLANS. SEC. R301.1 FBC-RESIDENTIAL.
  
 10- ACCORDING TO FIGURE R803.2.3.1 FBC-RESIDENTIAL ROOF
 SHEATHING NAILING ZONES, THE MINIMUM DIMENSION AT GABLE
 ENDS IS 5'-0". REVISE ROOF SHEATHING NAILING DIMENSION
 "Z" ON SHEET S-2.
  
 11- PROVIDE COMPLETE WALL SECTION DETAIL 2/A-5 SHOWN ON
 ROOF FRAMING PLAN ON SHEET S-2. CLEARLY SPECIFY TRUSS
 GIRDER CONNECTION. SEC. R301.1 FBC-RESIDENTIAL.
  
 12- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE
 CONSTRUCTION OF THE FRONT AND REAR WOOD TRELLIS AND THE
 6'-0" HIGH WOOD PRIVACY WALL SHOWN ON PLANS. SPECIFY
 ALL FRAMING MEMBERS AND CONNECTORS. SEC. R301.1
 FBC-RESIDENTIAL.
  
 13- ENERGY CALCULATIONS SUBMITTED;
 A) THE ENERGY FORM R405-2017 IS REQUIRED TO BE SIGNED
 AND DATED BY THE OWNER OR OWNER'S LEGALLY DESIGNATED
 AGENT AS REQUIRED BY SEC. R103.1.1.2 FBC-ENERGY
 CONSERVATION, 6TH EDITION (2017).
  
 B) PROVIDE ALL THE INFORMATION REQUIRED BY SEC.
 R405.4.2.1 FBC-ENERGY CONSERVATION FOR PERMIT
 APPLICATION. NEED THE STATEMENT, INSPECTION CHECKLIST,
 SITE SPECIFIC ANALYSIS).
  
 C) ITEM #9 IS MISSING THE WALL INFORMATION BETWEEN THE
 NON-A/C STORAGE ROOM AND THE A/C AREA OF THE MASTER
 BEDROOM AND BEDROOM #1. PROVIDE COMPLETE AND CORRECT
 INFORMATION. SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 D) PAGE 2 OF 5 SPECIFIES ATTIC VENT RATIO OF 1/300.
 TYPICALLY, THE MIN. VENT RATIO IS 1/150. HOUSE PLANS
 DON'T PROVIDE SPECIFICATIONS FOR 1/300 VENTILATION
 RATIO. REVISE AS REQUIRED TO MATCH PLANS OR PROVIDE
 COMPLETE DETAILS AND SPECIFICATIONS SHOWING COMPLIANCE
 WITH THE EXCEPTION ON SEC. R806.2 FBC-RESIDENTIAL.
  
 E) WOOD DOOR ON PAGE 3 OF 5 IS FOR THE NON A/C STORAGE
 ROOM. ONLY THE DOORS THAT ARE LOCATED IN A/C AREAS ARE
 THE ONES TO BE CONSIDERED. REVISE AS REQUIRED. SEC.
 R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 F) REVISE WINDOWS OVERHANG SEPARATION SHOWN ON PAGE 3
 OF 5 TO-MATCH PLANS. SEC. R101.5.1.1.2 FBC-ENERGY
 CONSERVATION.
  
 G) WINDOWS INFORMATION ON PAGE 3 OF 5 IS MISSING THE
 SKYLIGHTS. SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 H) BUILDER TO COMPLETE THE ENERGY PERFORMANCE LEVEL
 (EPL) DISPLAY CARD. SEC. R405.4.3 FBC-RESIDENTIAL.
  
 I) PROVIDE COMPLETE INFORMATION ON TOP OF FORM,
 INCLUDING THE OWNER'S NAME AND BUILDER'S NAME. SEC.
 R101.5.1.1.2 FBC-RESIDENTIAL.
  
 14- RECOMMENDED FOOTING SIZES SHOWN ON THE SOIL TEST
 REPORT ARE DIFFERENT THAN THE PROPOSED FOOTING SIZES
 SPECIFIED BY THE ARCHITECT OF RECORD. ARCHITECT TO
 REVIEW SOIL TEST REPORT AND ACKNOWLEDGE IN WRITING IF
 REVISING FOOTING SIZE OR PROVIDE ANALYSIS SHOWING THAT
 THE PROPOSED DESIGN WILL MEET THE SOIL TEST REPORT
 RECOMMENDATIONS. SEC. 107.2.1.2 CITY AMENDMENTS.
  
 15- SOIL TEST REPORT SUBMITTED NEEDS THE ENGINEER'S
 ORIGINAL SEAL AND SIGNATURE AS REQUIRED BY CHAPTER 471
 FLORIDA STATUTE WHEN SUBMITTING DOCUMENTS FOR PUBLIC
 RECORDS.
  
 16- PROVIDE COMPLETE FRAMING DETAILS AND SPECIFICATIONS
 FOR ATTIC ACCESS INSTALLATION IN THE ORIENTATION THAT
 IS SHOWN ON SHEET A-1 AND S-2. SEC. R301.1
 FBC-RESIDENTIAL.
  
 17- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.001 FOR:
 A) EXTERIOR FRENCH DOOR. PROVIDE 2 COPIES. ONLY ONE
 COPY OF NOA 17-0504.01 WAS SUBMITTED.
  
 B) SKYLIGHTS AS SHOWN ON PLANS.
  
 C) PRECAST LINTELS AS SPECIFIED ON PLANS.
  
 D) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON PLANS
 AND DETAILS. NOTE: PROVIDE ONLY THE FLORIDA PRODUCT
 APPROVAL COVER PAGE AND PAGE SHOWING THE SPECIFIED
 CONNECTOR OR DESIGN PROFESSIONAL TO LIST THE FLORIDA
 PRODUCT APPROVAL NUMBER NEXT TO EACH SPECIFIED
 CONNECTOR.
  
 18-DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
  
 19- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO
 LOW. VALUATION TO INCLUDE ALL LABOR, MATERIALS,
 CONTRACTOR'S OVERHEAD AND PROFIT AND ALL DESIGN
 PROFESSIONAL FEES AS REQUIRED BY SEC. 109.3 CITY
 AMENDMENTS. VALUATION WAS UPDATED TO $207.576. THE
 PERMIT FEE BALANCE IS $4233.65.
  
  
 ****PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO HELP EXPEDITE THE REVIEW PROCESS.
  
 ****PLEASE INSERT ANY REVISED DRAWING AND REMOVE OLD
 DRAWING. SUBMIT OLD DRAWINGS FOR REFERENCE OF ALREADY
 REVIEWED DRAWINGS. DON'T STAPLE OLD DRAWINGS TO PLANS.
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2018-06-21 Cont ID  
Sent By jpearson Date 2018-06-21 Time 08:30 Rev Time 0.00
Received By jpearson Date 2018-06-21 Time 08:12 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-03-12 Cont ID  
Sent By jpearson Date 2018-03-12 Time 09:11 Rev Time 0.00
Received By jpearson Date 2018-03-12 Time 09:11 Sent To  
Notes
2018-03-12 09:11:31CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. NOTE # 9 STATES THAT RECEPTACLES SHALL BE TAMPER
 RESISTANT PER NEC 406.11. THIS CODE SECTION DOES NOT
 APPLY TO TAMPER RESISTANT RECEPTACLES. PROVIDE
 CORRECTION. NEC 406.12; FBC RE E4002.14
 2. THERE IS A CONFLICT WITH THE PANEL SCHEDULE/RISER
 DIAGRAM AND THE PLAN IN RELATION TO THE SERVICE. RISER
 AND PANEL SCHEDULE CALL FOR A 300 AMP SERVICE, WHILE
 THE PLAN SHOWS A 200 AMP SERVICE. PROVIDE CORRECTION.
 FBC 107.2.1
 3. PROVIDE ACCURATE LOAD CALCULATION INCLUDING ALL
 LOADS. LOAD CALCULATION PROVIDED DOES NOT SHOW THE 2ND
 A/C SYSTEM, AND THE MATH IS WRONG. ALSO, DEMAND FACTORS
 ARE NOT APPLIED PROPERLY. NEC 220.82; FBC RE E E3602.2
 4. PROVIDE GFCI PROTECTION FOR DISHWASHER. NEC
 210.8(D); FBC RE E3902.10
 5. PLAN STATES THAT AFCI PROTECTION SHOULD BE INSTALLED
 PER NEC 210.12(B), WHICH IS FOR CIRCUIT EXTENSIONS AND
 MODIFICATIONS. THIS IS A NEW DWELLING UNIT, THEREFORE,
 THIS CODE SECTION DOES NOT APPLY. CODE REQUIRES:
 ?BRANCH CIRCUITS THAT SUPPLY 120-VOLT, SINGLE-PHASE,
 15- AND 20-AMPERE OUTLETS INSTALLED IN KITCHENS, FAMILY
 ROOMS, DINING ROOMS, LIVING ROOMS, PARLORS, LIBRARIES,
 DENS, BEDROOMS, SUN-ROOMS, RECREATIONS ROOMS, CLOSETS,
 HALLWAYS, LAUNDRY AREAS AND SIMILAR ROOMS OR AREAS
 SHALL BE AFCI PROTECTED.? PROVIDE CORRECTION. NEC
 210.12(A); FBC RE E3902.16
 6. RISER SHOWS (3) 4/0 AND (1) 2/0 WIRE FOR 300 AMP
 SERVICE. THIS WIRE SIZE IS NOT RATED FOR A 300 AMP
 SERVICE. ALSO, WHY IS THERE THREE HOT WIRES AND A
 NEUTRAL IF THIS IS A SINGLE PHASE SERVICE? CLARIFY
 AND/OR CORRECT. NEC 310.15(B)(7) AND (B)(15); FBC RE
 E3603.1, E3705.1
 7. PROVIDE INTERSYSTEM BONDING TERMINATION POINT AT
 SERVICE. SHOW ON PLAN. NEC 250.94; FBC RE E3609.3
 8. SERVICE GROUNDING ELECTRODE TO BE AUGMENTED BY AN
 ADDITIONAL ELECTRODE AT LEAST 6 FEET AWAY OR PROVIDE
 EVIDENCE OF RESISTANCE TO GROUND OF 25 OHMS OR LESS.
 NEC 250.56; FBC RE E3608.4
 9. PROVIDE GFCI PROTECTED OUTLET FOR SERVICING OF A/C
 EQUIPMENT PER CODE. NEC 210.63; FBC RE E3901.12
 10. SEVERAL AREAS DO NOT COMPLY WITH THE WALL SPACING
 REQUIREMENTS FOR OUTLETS. RECEPTACLES SHALL BE
 INSTALLED SO THAT NO POINT MEASURED HORIZONTALLY ALONG
 THE FLOOR LINE OF ANY WALL SPACE IS MORE THAN 6 FEET
 FROM A RECEPTACLE OUTLET, EXCEPT FOR KITCHEN AREA WHICH
 REQUIRES THAT RECEPTACLE OUTLETS SHALL BE INSTALLED SO
 THAT NO POINT ALONG THE WALL LINE IS MORE THAN 24
 INCHES MEASURED HORIZONTALLY FROM A RECEPTACLE OUTLET
 IN THAT SPACE. PROVIDE CORRECTION. NEC 210.52; FBC RE
 E3901.2.1, E3901.4
 11. A GFCI PROTECTED OUTLET ON A 20 AMP CIRCUIT IS
 REQUIRED WITHIN 3 FEET OF EACH BASIN. PROVIDE
 CORRECTION FOR MASTER BATH. NEC 210.11(C)(3),
 210.52(D); FBC RE E3703.4, E3901.6
 12. PLAN SHOWS STANDARD RECESS LIGHTS IN MASTER CLOSET.
 PER CODE: "LIGHTING WITH OPEN OR PARTIALLY ENCLOSED
 LAMPS AND PENDANT LUMINAIRES OR LAMPHOLDERS SHALL NOT
 BE PERMITTED IN CLOTHES CLOSETS". PROVIDE CORRECTION.
 NEC 410.16; FBC RE E4003.12
 13. FOR DWELLING UNITS, ATTACHED GARAGES, AND DETACHED
 GARAGES WITH ELECTRIC POWER, AT LEAST ONE WALL
 SWITCH-CONTROLLED LIGHTING OUTLET SHALL BE INSTALLED ON
 THE EXTERIOR SIDE OF OUTDOOR ENTRANCES/EXITS WITH GRADE
 LEVEL ACCESS. PROVIDE CORRECTION FOR STORAGE AREA. NEC
 210.70(A)(2)(B), FBC RE E3903.3
 14. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR
 EACH PANEL INCLUDING INFORMATION FROM THE POWER COMPANY
 STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR
 THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE
 SERVICE EQUIPMENT AND DOWNSTREAM PANELS IS ADEQUATE.
 NEC 110.9, 110.10
 15. PROVIDE AIC RATING OF SERVICE PANEL. NEC 110.3,
 110.9
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  
  

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2018-03-17 Cont ID  
Sent By gjohnson Date 2018-03-17 Time 11:24 Rev Time 0.00
Received By gjohnson Date 2018-03-17 Time 11:24 Sent To  
Notes
2018-03-17 11:26:27GAS PLAN REVIEW
 A GAS PLAN HAS NOT BEEN INCLUDED IN THIS SUBMITTAL
 PACKAGE. A GAS PLAN REVIEW HAS NOT BEEN PERFORMED AT
 THIS TIME. A SEPARATE GAS PERMIT AND PLANS WILL BE
 REQUIRED FOR A CONTRACTOR TO PERFORM THE RELATED WORK.
 PROVIDE COMPLETE PLANS, APPLIANCE/ EQUIPMENT
 SPECIFICATIONS AND GAS RISER THAT REFLECT THE ENTIRE
 SCOPE OF GAS WORK TO BE DONE. WPB AMEND. TO FBC SEC.
 107.2.1.
  
 GAS APPLIANCES SHALL BE LISTED AND LABELED PER THE
 FBC-R, SEC. G2404.3.
 GAS APPLIANCES SHALL BE LISTED AND LABELED PER FBC-FUEL
 GAS SEC. 301.3.
  
 A SEPARATE PERMIT AND PLANS IS REQUIRED FOR THE GAS
 INSTALLATION OR MODIFICATION OF SYSTEM.
  
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  
  
 GAS PERMIT APPLICATION REQUIREMENTS
  
 EFFECTIVE IMMEDIATELY THE FOLLOWING INFORMATION SHALL
 BE SHOWN ON ALL GAS DRAWINGS SUBMITTED FOR PERMITTING
 IN THE CITY OF WEST PALM BEACH:
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY SHOWS ALL
 CUT SECTIONS OF PIPE AND CORRESPONDING LENGTHS PER
 FBC-2014 FUEL GAS, SECS. 402.4.1, 402.4.2.
  
 2. SHOW TYPE OF PIPING MATERIAL BEING INSTALLED, ALL
 PIPE SIZES, AND THE EHD NUMBER OF CORRUGATED STAINLESS
 STEEL TUBING FOR EACH PIPE SIZE IF BEING USED. WPB
 AMENDMENTS TO FBC SEC. 107.2.1.
  
 3. TYPE OF GAS, (LP OR NATURAL).
  
 4. BTU LOAD OF EACH APPLIANCE AND THE TOTAL BTU LOAD ON
 THE SYSTEM. REFER TO THE FBC-2014 FUEL GAS SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU 402.4(37).
  
 5. SHOW THE DISTANCE FROM THE POINT OF DELIVERY,
 (METER), TO THE MOST REMOTE OUTLET IN THE BUILDING
 AND/OR SYSTEM PER THE FBC-2014 FUEL GAS APPENDIX A ?
 USE OF CAPACITY SECTION A.3.1(4) & 2014 FUEL GAS CODE
 SEC. 402.4.1.
  
 6. SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE
 FBC-2014 FUEL GAS CODE SEC. 304.
  
 7. INDICATE THE DELIVERY PRESSURE (PSI) PER FBC-2014
 FUEL GAS SEC. 402.2. IF NATURAL GAS SPECIFY .5 PSI OR 2
 PSI.
  
 8. SUBMIT A DETAIL SHOWING THE TYPE, LOCATION, LENGTH,
 SIZE AND TERMINATION OF THE GAS VENTS PER FBC-2014 FUEL
 GAS CODE SEC. 502 THRU 505.
  
 9. SUBMIT MANUFACTURER?S SPECIFICATION SHEETS FOR ALL
 GAS EQUIPMENT TO VERIFY COMPLIANCE WITH STANDARDS NFPA
 54, NFPA 58, AND FBC-2014 FUEL GAS SEC. 402.2
  
 10. CLEARLY SHOW THE LOCATION AND CAPACITY OF LP
 TANK(S), TYPE OF TANK (DOT OR ASME), THE DISTANCE OF
 THE TANK FROM THE BUILDING AND ADJACENT PROPERTY LINES
 THE DISTANCE OF THE TANK FROM ALL SOURCES OF IGNITION,
 OTHER CONTAINERS, BUILDINGS, AND THE LOCATION OF ANY
 BUILDING OPENINGS BELOW THE RELIEF VALVE OF THE TANK
 PER NFPA 58, TABLE 3-2.2.2.
  
 11. CLEARLY INDICATE ON THE PLAN IF THE LP TANK IS
 ABOVE OR BELOW GROUND, AND SHOW REQUIRED PROTECTION OF
 THE TANK AND APPURTENANCES PER NFPA 58. IF THE TANK IS
 BELOW GROUND THE CONTAINER SHALL BE SECURELY ANCHORED
 PER NFPA 58 SECTION 3-2.2.7(H).
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2018-08-13 Cont ID  
Sent By dbattles Date 2018-08-13 Time 16:25 Rev Time 0.00
Received By dbattles Date 2018-07-30 Time 15:41 Sent To  
Notes
2018-08-11 15:30:318/11 TO DB DESK
  
  
2018-07-31 15:43:43ROUTED TO ZONING INBOX

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-07-23 Cont ID  
Sent By shill Date 2018-07-23 Time 12:32 Rev Time 0.00
Received By shill Date 2018-06-07 Time 14:30 Sent To  
Notes
2018-06-08 14:30:32R39

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-03-20 Cont ID  
Sent By jgomez Date 2018-03-19 Time 18:44 Rev Time 0.00
Received By jgomez Date 2018-02-28 Time 14:51 Sent To I
Notes
2018-03-01 14:51:24R24

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 4 Status P Date 2018-08-17 Cont ID  
Sent By skennedy Date 2018-08-17 Time 15:17 Rev Time 0.00
Received By skennedy Date 2018-08-17 Time 15:17 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 3 Status F Date 2018-08-13 Cont ID  
Sent By dbattles Date 2018-08-13 Time 16:42 Rev Time 0.00
Received By dbattles Date 2018-08-13 Time 16:42 Sent To  
Notes
2018-08-13 16:43:36[FBC 109] PLANS REQUIRE REVIEW BY THE PBC IMPACT FEE
 OFFICE. CALL (561) 233-5025. UPON APPROVAL, YOU MAY
 CHECK OUT ONE PLAN SET AND TAKE TO THAT OFFICE FOR
 REVIEW. PLEASE RETURNED STAMPED AND WITH A COPY OF THE
 RECEIPT AS APPLICABLE. PROVIDE THE MUNICIPAL IMPACT FEE
 QUESTIONNAIRE FORM TO THE PBC IMPACT FEE OFFICE.
  
 THE QUESTIONARE IS FILLED OUT AND IN THE PERMIT
 PACKAGE.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status F Date 2018-06-28 Cont ID  
Sent By shill Date 2018-06-28 Time 18:24 Rev Time 0.00
Received By shill Date 2018-06-28 Time 18:03 Sent To  
Notes
2018-06-28 18:07:39PLEASE PROVIDE THE PLAN STAMPED BY PALM BEACH COUNTY
 WHEN RESUBMITTING
  
 MU2018-9757
 $0 DUE
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2018-03-19 Cont ID  
Sent By jgomez Date 2018-03-19 Time 18:42 Rev Time 0.00
Received By jgomez Date 2018-03-19 Time 18:42 Sent To  
Notes
2018-03-19 18:44:341-BEFORE A PERMIT TO CONSTRUCT CAN BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. UPON APPROVAL,
 ONE SET OF PLANS SHALL BE SIGNED OUT AND SUBMITTED TO
 PALM BEACH COUNTY FOR AN IMPACT FEE REVIEW. THE PLANS
 WITH THE IMPACT FEE STAMP AND A COPY OF THE PAID
 RECEIPT MUST BE RETURNED TO THE CITY BUILDING
 DEPARTMENT BEFORE THE BUILDING PERMIT CAN BE ISSUED.
 FOR INFORMATION CALL PALM BEACH COUNTY IMPACT FEES AT
 (561) 233-5025.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2018-07-19 Cont ID  
Sent By cmontell Date 2018-07-19 Time 14:29 Rev Time 0.00
Received By cmontell Date 2018-07-19 Time 14:23 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2018-03-20 Cont ID  
Sent By cmontell Date 2018-03-16 Time 15:31 Rev Time 0.00
Received By cpuell Date 2018-03-16 Time 15:25 Sent To  
Notes
2018-03-16 15:30:57MECHANICAL PLAN REVIEW FAIL
  
 NEED RETURN AIR IN BEDROOM 1
  
 1 - 601.6 BALANCED RETURN AIR.
 RESTRICTED RETURN AIR OCCURS IN BUILDINGS WHEN RETURNS
 ARE LOCATED IN CENTRAL ZONES AND CLOSED INTERIOR DOORS
 IMPEDE AIR FLOW TO THE RETURN GRILL OR WHEN CEILING
 SPACES ARE USED AS RETURN PLENUMS AND FIRE WALLS
 RESTRICT AIR MOVEMENT FROM ONE PORTION OF THE RETURN
 PLENUM TO ANOTHER. PROVISIONS SHALL BE MADE IN BOTH
 RESIDENTIAL AND COMMERCIAL BUILDINGS TO AVOID
 UNBALANCED AIR FLOWS AND PRESSURE DIFFERENTIALS CAUSED
 BY RESTRICTED RETURN AIR..

Review Stop P PLUMBING
Rev No 2 Status P Date 2018-06-23 Cont ID  
Sent By gjohnson Date 2018-06-23 Time 12:29 Rev Time 0.00
Received By gjohnson Date 2018-06-23 Time 12:29 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2018-03-17 Cont ID  
Sent By gjohnson Date 2018-03-17 Time 11:19 Rev Time 0.00
Received By gjohnson Date 2018-03-17 Time 08:55 Sent To  
Notes
2018-03-17 11:24:251ST REVIEW: FBC 2017 6TH EDITION
  
 PLUMBING COMMENTS:
  
 1. PROVIDE SANITARY ISOMETRIC DRAWING. PER WPB AMEND TO
 FBC 107.3.5.3
  
 2. PROVIDE ELEVATION DRAWING SHOWING TANKLESS HEATER
 MOUNTING DISTANCE FROM OPENINGS SHALL BE MIN OF 4' PER
 MANUFACTURE SPECIFICATIONS.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 2018-03-20 Cont ID  
Sent By jgomez Date 2018-03-19 Time 18:41 Rev Time 0.00
Received By jgomez Date 2018-03-20 Time 09:10 Sent To  
Notes
2018-03-20 09:11:18SHINGLES NOA 16-0811.11

Review Stop Z ZONING
Rev No 4 Status P Date   Cont ID  
Sent By   Date 2018-08-17 Time   Rev Time 0.00
Received By pgreilic Date 2018-08-17 Time 15:13 Sent To  
Notes
2018-08-17 15:13:48PAUL GREILICH, SENIOR PLANNER
 561-822-1443
 [email protected]

Review Stop Z ZONING
Rev No 3 Status F Date   Cont ID  
Sent By   Date 2018-08-07 Time   Rev Time 0.00
Received By pgreilic Date 2018-08-07 Time 09:23 Sent To B
Notes
2018-08-07 09:25:331.) PROVIDE PROPOSED SITE PLAN OR SURVEY SHOWING
 PROPOSED DIMENSIONS (NOT INCLUDED IN PLAN SET)
 2.) LANDSCAPE PERMIT REQUIRED
  
 PAUL GREILICH, SENIOR PLANNER
 561-822-1443
 [email protected]

Review Stop Z ZONING
Rev No 2 Status P Date   Cont ID  
Sent By   Date 2018-07-10 Time   Rev Time 0.00
Received By pgreilic Date 2018-07-06 Time 14:49 Sent To  
Notes
2018-07-10 09:18:331.) LANDSCAPE PERMIT REQUIRED PRIOR TO C.O.
  
 PAUL GREILICH, SENIOR PLANNER
 561-822-1443
 [email protected]

Review Stop Z ZONING
Rev No 1 Status F Date   Cont ID  
Sent By PG Date 2018-03-14 Time   Rev Time 0.00
Received By pgreilic Date 2018-03-14 Time 10:57 Sent To  
Notes
2018-03-14 10:58:321.) PROVIDE A SURVEY INDICATING PROPOSED DIMENSIONS AND
 SETBACKS
 2.) LANDSCAPE PERMIT REQUIRED PRIOR TO C.O.
  
 PAUL GREILICH, SENIOR PLANNER
 561-822-1443
 [email protected]