Plan Review Details - Permit 18021190
Plan Review Stops For Permit 18021190
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2018-03-30 Cont ID  
Sent By rmcdouga Date 2018-03-30 Time 14:47 Rev Time 0.00
Received By rmcdouga Date 2018-03-30 Time 14:47 Sent To I
Notes
2018-03-30 14:47:50FBC-R4501.19 FINAL ELECTRICAL AND BARRIER CODE
 INSPECTION SHALL BE COMPLETED PRIOR TO FILLING THE POOL
 WITH WATER.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2018-03-19 Cont ID  
Sent By rmcdouga Date 2018-03-19 Time 07:36 Rev Time 0.00
Received By rmcdouga Date 2018-03-19 Time 07:36 Sent To I
Notes
2018-03-19 07:50:031) FBC-R4501.19 FINAL ELECTRICAL AND BARRIER CODE
 INSPECTION SHALL BE COMPLETED PRIOR TO FILLING THE POOL
 WITH WATER.
  
 2) SECTION R403.10.3 OF THE 2017 ENERGY CONSERVATION
 CODE REQUIRES HEATED POOLS TO HAVE COVERS TO REDUCE
 HEAT LOSS.
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2018-03-09 Cont ID  
Sent By jleahy Date 2018-03-09 Time 14:25 Rev Time 0.00
Received By jleahy Date 2018-03-09 Time 14:24 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2018-03-08 Cont ID  
Sent By lcrespo Date 2018-03-08 Time 07:02 Rev Time 0.00
Received By lcrespo Date 2018-03-08 Time 07:02 Sent To  
Notes
2018-03-08 07:07:48SEPARATE GAS PERMIT APPLICATION SHALL BE REQUIRED
 REQUIRED FOR HEATER EQUIPMENT BY A LICENSED CONTRACTOR.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-03-30 Cont ID  
Sent By rmcdouga Date 2018-03-30 Time 14:47 Rev Time 0.00
Received By rmcdouga Date 2018-03-20 Time 12:46 Sent To  
Notes
2018-03-21 12:46:45ROUTED TO ZONING INBOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-03-19 Cont ID  
Sent By rmcdouga Date 2018-03-19 Time 07:37 Rev Time 0.00
Received By rmcdouga Date 2018-02-28 Time 10:39 Sent To  
Notes
2018-03-01 10:39:25ROUTED TO ZONING INBOX

Review Stop P PLUMBING
Rev No 2 Status P Date 2018-03-27 Cont ID  
Sent By lcrespo Date 2018-03-27 Time 14:24 Rev Time 0.00
Received By lcrespo Date 2018-03-27 Time 14:24 Sent To  
Notes
2018-03-27 14:25:3603/27/18 APPROVED BY PLUMBING AND SENT TO BUILDING, LAC

Review Stop P PLUMBING
Rev No 1 Status F Date 2018-03-08 Cont ID  
Sent By lcrespo Date 2018-03-08 Time 07:00 Rev Time 0.00
Received By lcrespo Date 2018-03-08 Time 07:00 Sent To  
Notes
2018-03-08 07:21:2203/08/2018 **1ST PLUMBING REVIEW**DENIED **
 321 MONCEAUX ROAD
  
 1. SEPARATE GAS PERMIT REQUIRED FOR HEATER EQUIPMENT,
 SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY SHOWS THE
 LENGTH OF ALL CUT SECTIONS OF PIPE PER 2017 FBC FUEL
 GAS, SECS. 402.4.1, 402.4.2. OR 2017 FBC FUEL GAS RES
 SECS. G2413.4.1, G2413.4.2.
 2. SUBMIT MANUFACTURES SPECIFICATION FOR POOL PUMP,
 FILTER AND ALL EQUIPMENT, SHEETS/INSTALLATION MANUAL
 FOR ALL GAS HEATER EQUIPMENT TO VERIFY COMPLIANCE WITH
 FLORIDA ENERGY CODE, FBC FUEL GAS SEC.305.1 OR FBC FUEL
 GAS RES. SEC. G2408.1.
 3. SUBMIT TWO COPIES OF THE SIZING TABLE USED IN THE
 DESIGN FOR THE GAS SYSTEM OR PLACE A NOTE ON BOTH SETS
 OF PLANS LISTING THE SIZING TABLES FROM GAS CODES OR
 ANOTHER STANDARD THAT WERE USED IN THE DESIGN OF THIS
 SYSTEM 2017 FBC FUEL GAS SEC. 402.3 OR 2017 FBC FUEL
 GAS RES. SEC. G2413.3
 4. SUBMIT MANUFACTURER?S SPECIFICATIONS FOR THE
 PRESSURE REGULATORS. REGULATORS INSTALLED ON THE
 EXTERIOR OF THE BUILDING SHALL BE APPROVED FOR OUTDOOR
 INSTALLATION. 2017 FBC FUEL GAS SEC.410.1 OR 2017 FBC
 FUEL GAS RES. SEC. G2421.1.
 5. SOLAR COVER SHALL BE PROVIDED OR FBC RE 403.10.3
 COVERS. OUTDOOR HEATED SWIMMING POOLS AND OUTDOOR
 PERMANENT SPAS SHALL BE EQUIPPED WITH A VAPOR-RETARDANT
 COVER ON OR AT THE WATER SURFACE OR A LIQUID COVER OR
 OTHER MEANS PROVEN TO REDUCE HEAT LOSS.
 6. BACKFLOW PREVENTER REQUIRED PER THE CITY OF WEST
 PALM BEACH ORD #2853-95. PLEASE CONTACT CITY OF WPB
 UTILITIES AT 561-822-2240 FOR FURTHER DIRECTIONS.
 7. PLEASE PROVIDE MAIN DRAIN SPECICATION FOR COMPLIANCE
 WITH ANSI/APSP/ICC 7.
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 LUIS A. CRESPO
 PLUMBING INSPECTOR /
 PLUMBING PLAN REVIEW
 [email protected]
 561-805-6720
  

Review Stop Z ZONING
Rev No 2 Status P Date 2018-03-26 Cont ID  
Sent By ajones Date 2018-03-26 Time 16:15 Rev Time 0.00
Received By ajones Date 2018-03-26 Time 16:15 Sent To P
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2018-03-06 Cont ID  
Sent By ajones Date 2018-03-06 Time 17:56 Rev Time 0.00
Received By ajones Date 2018-03-02 Time 16:09 Sent To I
Notes
2018-03-06 17:57:533/6/18- FAILED. THE POOL EQUIPMENT CAN ONLY GO 4 FEET
 INTO THE 8.93 FOOT REQUIRED REAR SETBACK.
  
 ANGELLA VANN
 561-822-1441
 [email protected]