Plan Review Details - Permit 18021164
Plan Review Stops For Permit 18021164
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2018-03-05 Cont ID  
Sent By jwitmer Date 2018-03-05 Time 07:59 Rev Time 0.00
Received By jwitmer Date 2018-03-05 Time 07:30 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2018-03-16 Cont ID  
Sent By jpearson Date 2018-03-16 Time 15:04 Rev Time 0.00
Received By jpearson Date 2018-03-16 Time 15:04 Sent To I
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-03-06 Cont ID  
Sent By jpearson Date 2018-03-06 Time 08:32 Rev Time 0.00
Received By jpearson Date 2018-03-06 Time 07:30 Sent To  
Notes
2018-03-06 08:32:30CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. LOAD CALCULATION PROVIDED CONFLICTS WITH PLAN
 PROVIDED. PLAN SHOWS EACH TRAILER HAS 2 PANELS, ONE
 DRAWING AROUND 75 AMPS AND THE OTHER DRAWING AROUND 67
 AMPS. FOR A TOTAL OF 4 TRAILERS, THIS WOULD BE AROUND
 568 AMPS. PROVIDE ACCURATE LOAD CALCULATION. NEC 220
 2. RISER DIAGRAM CONFLICTS WITH STATEMENT ON LOAD
 CALCULATION. LOAD CALCULATION STATES THAT THERE WILL BE
 FOUR DOUBLEWIDE TRAILERS, THE RISER DIAGRAM SHOWS
 CONNECTIONS TO 6 TRAILERS. CLARIFY AND/OR CORRECT. FBC
 107.2.1; NEC 215.5, 215.2
 3. IT APPEARS THAT THE DESIGN WITH TWO 200 AMP PANELS
 FEEDING THE TRAILERS WILL OVERLOAD THE 200 AMP PANELS.
 PROVIDE CORRECTION. NEC 408.30
 4. PROVIDE THE REQUIRED SERVICE AREA RECEPTACLE PER
 CODE. NEC 210.64
 5. PROVIDE INTERSYSTEM BONDING TERMINATION POINT AT
 SERVICE. SHOW ON PLAN. NEC 250.94
 6. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR EACH
 PANEL INCLUDING INFORMATION FROM THE POWER COMPANY
 STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR
 THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE
 SERVICE EQUIPMENT AND DOWNSTREAM PANELS IS ADEQUATE.
 NEC 110.9, 110.10
 7. PROVIDE AIC RATING OF SERVICE DISCONNECTS AND
 PANELS. NEC 110.3, 110.9
 8. ALL SHEETS SUBMITTED SHOULD BE SIGNED BY THE DESIGN
 PROFESSIONAL OR THE ELECTRICAL CONTRACTOR QUALIFIER.
 FBC 107.1; FS 471, 481
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2018-03-01 Cont ID  
Sent By scaldero Date 2018-03-01 Time 12:19 Rev Time 0.00
Received By scaldero Date 2018-03-01 Time 12:18 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2018-03-16 Time   Rev Time 0.00
Received By lmarchan Date 2018-03-15 Time 10:49 Sent To  
Notes
2018-03-16 10:49:55RESUB ROUTED TO JPEARSON

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2018-03-15 Time   Rev Time 0.00
Received By lmarchan Date 2018-02-27 Time 13:48 Sent To  
Notes
2018-02-28 13:48:32B31

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2018-03-07 Cont ID  
Sent By ccole Date 2018-03-07 Time 08:44 Rev Time 0.00
Received By ccole Date 2018-03-07 Time 08:44 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2018-03-14 Cont ID  
Sent By lcrespo Date 2018-03-14 Time 16:24 Rev Time 0.00
Received By lcrespo Date 2018-03-14 Time 16:24 Sent To  
Notes
2018-03-14 16:25:4303/14/18 APPROVED BY PLUMBING AND PUT SENT TO
 ELECTRICAL JP, LAC

Review Stop Z ZONING
Rev No 1 Status P Date   Cont ID  
Sent By   Date 2018-03-14 Time   Rev Time 0.00
Received By pgreilic Date 2018-03-14 Time 11:04 Sent To  
Notes
2018-03-14 11:04:38PAUL GREILICH, SENIOR PLANNER
 561-822-1443
 [email protected]