| 2018-02-28 07:43:02 | 1ST REVIEW FBC-2014 MECHANICAL |
| | PERMIT #18021157 |
| | 2/28/18 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) THERE ARE DISCREPANCIES BETWEEN THE ORIGINAL FAN |
| | SCHEDULE SHOWN IN THE APPROVED GARAGE PLANS UNDER |
| | PERMIT #07090764 AND THE FAN SUBMITTAL DOCUMENTS: A) |
| | EF-20 DOES NOT MATCH IN ELECTRICAL VOLTAGE. THE |
| | SCHEDULE INDICATES 277/1, HOWEVER THE SUBMITTAL |
| | INDICATES 115/1. B) EF-21 IS A 3/4 HP IN THE SCHEDULE, |
| | BUT LISTED AS A 1/2 HP IN YOUR SUBMITTAL. |
| | |
| | 2) THE SCOPE IOF WORK FOR CO2 SENSOR REPLACEMENTS NEEDS |
| | TO BE CLARIFIED. THERE ARE APPROXIMATELY 62 SENSORS IN |
| | THE EXISTING GARAGE, HOWEVER THE CONTRACT INDICATES |
| | ONLY 16 TO BE REPLACED. PLEASE NOTE THAT THE THE |
| | ORIGINAL SENSORS PER PLAN WERE CO2, AND THE CODE AT THE |
| | TIME SET AUTOMATIC EXHAUST FAN OPERATION FOR CO2 AT 25 |
| | PPM (PARTS PER MILLION). |
| | |
| | THE CURRENT CODE REQUIRES BOTH CO2 AND NO2 SENSORS. THE |
| | SUBMITTAL FROM HONEYWELL IS RECOMMENDING THAT TYPE OF |
| | MULTI-SENSOR FOR PARKING GARAGES. |
| | |
| | PLEASE VERIFY THAT THOSE WILL BE THE TYPE OF SENSORS TO |
| | BE INSTALLED, AND INDICATE AT WHAT PPM LEVEL(S) THE |
| | FANS WILL AUTO OPERATE. |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS. |
| | |