Plan Review Details - Permit 18021105
Plan Review Stops For Permit 18021105
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2018-06-11 Cont ID  
Sent By rmcdouga Date 2018-06-11 Time 18:57 Rev Time 0.00
Received By rmcdouga Date 2018-06-11 Time 18:03 Sent To I
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-05-18 Cont ID  
Sent By rmcdouga Date 2018-05-18 Time 08:47 Rev Time 0.00
Received By rmcdouga Date 2018-05-18 Time 07:11 Sent To I
Notes
2018-05-18 08:47:12PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW FOR THE GENERATOR
 SLAB:
  
 1) FBC 107.2.1 - INFORMATION ON CONSTRUCTION DOCUMENTS.
 ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND
 ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE OF
 THE PERSON RESPONSIBLE FOR THE DESIGN.
  
 2) ON SHEET 5 OF 5 OF THE 22 KW GENERAC GENERATOR
 DOCUMENTS THAT WERE SUBMITTED THE NOTE STATES THAT THE
 DIMENSIONS SHOWN ARE APPROXIMATE AND REFERS YOU TO THE
 INSTALLATION MANUAL FOR EXACT DIMENSIONS. SUBMIT TWO
 SETS OF THE INSTALLATION MANUALS FOR THE 22 KW GENERAC
 GENERATOR. FBC 107.2.1.2
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2018-03-12 Cont ID  
Sent By jleahy Date 2018-03-12 Time 16:33 Rev Time 0.00
Received By jleahy Date 2018-03-12 Time 16:33 Sent To I
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2018-05-16 Cont ID  
Sent By tklarge Date 2018-05-16 Time 13:48 Rev Time 0.00
Received By tklarge Date 2018-05-16 Time 06:17 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2018-03-09 Cont ID  
Sent By thunt Date 2018-03-09 Time 16:28 Rev Time 0.00
Received By thunt Date 2018-03-09 Time 16:28 Sent To E
Notes
2018-03-09 16:38:0603/09/2018 1ST GAS REVIEW**DENIED**
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS
  
  
 1) YOU LIST A EXISTING GAS METER. SUBMIT AN ISOMETRIC
 DRAWING THAT CLEARLY SHOWS THE LENGTH OF ALL CUT
 SECTIONS OF PIPE PER 2014 FBC-FUEL GAS, SECS. 402.4.1,
 402.4.2. OR 2014 FBC-RES SEC. G2413
  
 2) TYPE OF GAS (LP OR NATURAL).
  
 3) LIST THE BTU LOAD OF EACH APPLIANCE AND THE TOTAL
 BTU LOAD ON THIS EXISTING SYSTEM. REFER TO THE 2014
 FBC-FUEL GAS SECS.401.8 THRU 402.6.1 AND TABLES 402.4
 (1) THRU 402.4 (37) OR 2014 FBC-RES. SEC. G2413.
  
 4) INDICATE THE DELIVERY PRESSURE (PSI) OF THE SYSTEM
 ON THE PLAN PER 2014 FBC-FUEL GAS SEC.402.2 OR FBC RES.
 SEC. G2413.2.
  
 5) 17) SUBMIT TWO COPIES OF THE APPLICABLE SIZING
 TABLES USED TO SIZE THE GAS SYSTEM OR PLACE A NOTE ON
 THE PLANS/DRAWINGS SPECIFYING WHICH SIZING TABLE(S)
 FROM THE GAS CODE OR OTHER STANDARD THAT WERE USED IN
 THE DESIGN OF THIS GAS SYSTEM. REFER TO THE 2014
 FBC-FUEL GAS SECS. 401.4, 401.8 THRU 402.6.1 AND TABLES
 402.4 (1) THRU 402.4 (37) OR 2014 FBC-RES. SEC.
 G2412.4, G2412.8, G2413.1, G2413.2, & G2413.3
  
 6) YOU LIST THE BTU RATING AS 142,000 BTU. THE
 MANUFACTURES MANUAL SUPPLIED LIST FULL LOAD AS 327,000
 BTU. PER FBC-F 402.2 THE SYSTEM IS REQUIRED TO BE SIZED
 WITH APPLIANCE AT FULL LOAD.
  
 7) I CAN ONLY GUESS THAT THIS SYSTEM MAY BE 12" WC AS
 YOU DON NOT SHOW A PRESSURE REGULATOR. IF IN FACT IT IS
 THE 1" P.E PIPING WOULD BE UNDERSIZED.
  
  
  
 TIM HUNT
 PLUMBING INSPECTOR / PLUMBING PLAN REVIEWER
 CITY OF WEST PALM BEACH DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 561-805-6695
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2018-06-11 Cont ID  
Sent By rmcdouga Date 2018-06-11 Time 18:57 Rev Time 0.00
Received By rmcdouga Date 2018-06-05 Time 13:51 Sent To  
Notes
2018-06-06 13:51:19RESUB ROUTED TO ZONING INBOX

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-05-16 Cont ID  
Sent By tklarge Date 2018-05-16 Time 13:48 Rev Time 0.00
Received By tklarge Date 2018-05-08 Time 10:42 Sent To  
Notes
2018-05-09 10:42:20RESUB ROUTED TO ZONING INBOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-03-12 Cont ID  
Sent By jleahy Date 2018-03-12 Time 16:33 Rev Time 0.00
Received By jleahy Date 2018-02-27 Time 11:19 Sent To  
Notes
2018-02-28 11:19:52ROUTED TO ZONING

Review Stop Z ZONING
Rev No 3 Status P Date 2018-06-11 Cont ID  
Sent By fmittner Date 2018-06-11 Time 12:55 Rev Time 0.00
Received By fmittner Date 2018-06-11 Time 12:55 Sent To B
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status F Date 2018-05-15 Cont ID  
Sent By mcruz Date 2018-05-15 Time 11:23 Rev Time 0.00
Received By fmittner Date 2018-05-11 Time   Sent To G
Notes
2018-05-15 11:24:04COMMENTS FROM FIRST REVIEW NOT ADDRESSED. QUESTIONS,
 CONTACT FRIEDERIKE MITTNER AT (561) 822-1457,
 [email protected]

Review Stop Z ZONING
Rev No 1 Status F Date 2018-03-08 Cont ID  
Sent By ES Date 2018-03-08 Time 15:26 Rev Time 0.00
Received By fmittner Date 2018-03-02 Time 15:56 Sent To E
Notes
2018-03-08 15:27:35LOCATION OF GENERATOR NOT CLEARLY DELINEATED,
 SPECIFICALLY AS IT RELATES TO PROPERTY LINES. GENERAL
 LOCATION INDICATES IN FRONT OF GARAGE DOOR IN CLEAR
 SIGHT DOWN DRIVEWAY. PROPERTY IN HISTORIC DISTRICT,
 GARGE DOOR SHALL BE KEPT CLEAR.