Plan Review Details - Permit 18021075
Plan Review Stops For Permit 18021075
Review Stop ENG ENGINEERING CSD
Rev No 2 Status P Date 2018-06-04 Cont ID  
Sent By Mgonzale Date 2018-06-04 Time   Rev Time 1.00
Received By mgonzale Date 2018-06-04 Time   Sent To I
Notes
2018-06-04 11:27:42IT IS REQUIRED THAT YOU CONTACT MARK HURLEY AT CITY OF
 WPB CUSTOMER SERVICE TO COORDINATE THE LOCATION OF THIS
 DEVICE.
  
 THANK YOU!
  
 MARK HURLEY
 FIELD CUSTOMER SERVICE SUPERVISOR
 CITY OF WEST PALM BEACH PUBLIC UTILITIES
 561-822-2262
 [email protected]
  
 [email protected]
  
  

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2018-03-07 Cont ID  
Sent By Mgonzale Date 2018-03-07 Time   Rev Time 1.00
Received By mgonzale Date 2018-03-07 Time   Sent To M
Notes
2018-03-07 12:38:54ADDRESS FIRE COMMENTS.
 PLEASE RESPOND TO COMMENTS IN WRITING.
  
 NO COMMENTS FROM UTILITIES.
  
 MANNY GONZALEZ
 SENIOR ENGINEERING PROJECT COORDINATOR
 PUBLIC WORKS DEPARTMENT
 401 CLEMATIS STREET, 4TH FLOOR
 WEST PALM BEACH, FL 33401
 (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402)
 MAIN PHONE: (561) 822-1200
 DIRECT: (561) 494-1085
 FAX: (561) 494-1116
 EMAIL: [email protected]
 HTTP://WWW.WPB.ORG/DEPARTMENTS/ENGINEERING-PUBLIC-WORKS
 /FORMS,-PERMITS-APPLICATIONS
  
 IMPORTANT MESSAGE: AS OF DECEMBER 20, 2015 THE CITY OF
 WEST PALM BEACH
 CROSS-CONNECTION CONTROL MANUAL HAS BEEN REVISED,
 MAKING KNOWN THAT "ALL BACKFLOW DEVICES MUST BE LEAD
 FREE."
 FOR MORE INFORMATION REFER TO THE LINK BELOW:
 HTTP://WPB.ORG/DEPARTMENTS/PUBLIC-UTILITIES/FORMS-PUBLI
 CATIONS/BACKFLOW-CROSS-CONNECTION-CONTROL-MANUAL

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2018-05-25 Cont ID  
Sent By pleduc Date 2018-05-25 Time   Rev Time 0.00
Received By pleduc Date 2018-05-24 Time 17:26 Sent To M
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2018-02-28 Cont ID  
Sent By pleduc Date 2018-02-28 Time   Rev Time 0.00
Received By pleduc Date 2018-02-28 Time 11:40 Sent To ENG
Notes
2018-02-28 13:28:05 
 THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) ON REVIEW OF THE LOCATION OF THE DDCV IT DOES NOT
 APPEAR TO COMPLY WITH THE REQUIRMENTS OF NFPA 24.
  
 A REVIEW OF THE MASTER PERMIT, 17010799, SHEET FP 1 OF
 1, INDICATES THAT THE UNDERGROUND WORK SHALL COMPLY
 WITH NFPA 24.
  
 PER NFPA 24, CHAPTER 6, VALVES
  
  
 6.2.11 ALL CONNECTIONS TO PRIVATE FIRE SERVICE MAINS
 FOR FIRE
 PROTECTION SYSTEMS SHALL BE ARRANGED IN ACCORDANCE WITH
 ONE
 OF THE FOLLOWING SO THAT THEY CAN BE ISOLATED:
 (1)*A POST INDICATOR VALVE INSTALLED NOT LESS THAN 40
 FT (12 M)
 FROM THE BUILDING
 (A) FOR BUILDINGS LESS THAN 40 FT (12 M) IN HEIGHT, A
 POST
 INDICATOR VALVE SHALL BE PERMITTED TO BE INSTALLED
 CLOSER THAN 40 FT (12 M) BUT AT LEAST AS FAR FROM THE
 BUILDING AS THE HEIGHT OF THE WALL FACING THE POST
 INDICATOR
 VALVE.
 (2) A WALL POST INDICATOR VALVE
 (3) AN INDICATING VALVE IN A PIT, INSTALLED IN
 ACCORDANCE WITH
 SECTION 6.4
 (4)*A BACKFLOW PREVENTER WITH AT LEAST ONE INDICATING
 VALVE NOT
 LESS THAN 40 FT (12 M) FROM THE BUILDING
 (A) FOR BUILDINGS LESS THAN 40 FT (12 M) IN HEIGHT, A
 BACKFLOW
 PREVENTER WITH AT LEAST ONE INDICATING VALVE SHALL
 BE PERMITTED TO BE INSTALLED CLOSER THAN 40 FT (12 M)
 BUT AT LEAST AS FAR FROM THE BUILDING AS THE HEIGHT OF
 THE WALL FACING THE BACKFLOW PREVENTER.
 (5)*A NONINDICATING VALVE, SUCH AS AN UNDERGROUND GATE
 VALVE
 WITH AN APPROVED ROADWAY BOX, COMPLETE WITH T-WRENCH,
 LOCATED NOT LESS THAN 40 FT (12 M) FROM THE BUILDING
 (A) FOR BUILDINGS LESS THAN 40 FT (12 M) IN HEIGHT, A
 NONINDICATING
 VALVE, SUCH AS AN UNDERGROUND GATE VALVE WITH AN
 APPROVED ROADWAY BOX, COMPLETE WITH T-WRENCH, SHALL
 BE PERMITTED TO BE INSTALLED CLOSER THAN 40 FT (12 M)
 BUT
 AT LEAST AS FAR FROM THE BUILDING AS THE HEIGHT OF THE
 WALL
 FACING THE BACKFLOW PREVENTER.
 (6) CONTROL VALVES INSTALLED IN A FIRE-RATED ROOM
 ACCESSIBLE
 FROM THE EXTERIOR
 (7) CONTROL VALVES IN A FIRE-RATED STAIR ENCLOSURE
 ACCESSIBLE
 FROM THE EXTERIOR AS PERMITTED BY THE AUTHORITY HAVING
 JURISDICTION.
  
 6.5 BACKFLOW PREVENTION ASSEMBLIES.
 6.5.1 WHERE USED IN ACCORDANCE WITH 6.2.11(4), BACKFLOW
 PREVENTION
 ASSEMBLIES SHALL BE INSTALLED IN ACCORDANCE WITH THEIR
 INSTALLATION INSTRUCTIONS.
 6.5.2 WHERE BACKFLOW PREVENTION ASSEMBLIES ARE USED,
 THEY
 SHALL BE PROTECTED AGAINST MECHANICAL DAMAGE WHERE
 NEEDED.
  
 THE LOCATION OF THE DDCV APPEARS TO BE CLOSER THAN THE
 HEIGHT OF THE WALL.
  
 PLEASE PROVIDE AN ALTERNATE LOCATION OR PROVIDE
 PROTECTION SHOULD THE WALL COLLASPE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-06-05 Cont ID  
Sent By cpuell Date 2018-06-05 Time 11:03 Rev Time 0.00
Received By cpuell Date 2018-05-22 Time 13:29 Sent To  
Notes
2018-05-23 13:29:33RESUB ROUTED TO FIRE INBOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2018-03-15 Time   Rev Time 0.00
Received By lmarchan Date 2018-02-26 Time 11:26 Sent To  
Notes
2018-02-27 11:26:39ROUTED TO FIRE INBOX

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2018-05-31 Cont ID  
Sent By ccole Date 2018-05-31 Time 14:14 Rev Time 0.00
Received By ccole Date 2018-05-31 Time 14:13 Sent To ENG
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2018-03-15 Cont ID  
Sent By ccole Date 2018-03-15 Time 07:10 Rev Time 0.00
Received By ccole Date 2018-03-15 Time 06:53 Sent To I
Notes
2018-03-15 07:24:181ST REVIEW FBC-2014 MECHANICAL
 PERMIT #18021075
 3/15/18
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) NO CONTRACTOR OR LICENSE NUMBER HAVE BEEN PROVIDED
 ON THE PERMIT APPLICATION TO INSTALL THE UNDERGROUND
 FIRE LINE. REFER TO FLORIDA STATUTES 489.113(3)(N), AND
 633.021 (5) FOR LICENSURE REQUIREMENTS FOR UNDERGOUND
 UTILITY AND FIRE LINE INSTALLATIONS. THE PERMIT CANNOT
 BE ISSUED TO THE OWNER OF THE PROPERTY.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  