Plan Review Details - Permit 18021018
Plan Review Stops For Permit 18021018
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date   Cont ID  
Sent By   Date 2018-03-06 Time 07:29 Rev Time 0.00
Received By jwitmer Date 2018-03-06 Time 06:47 Sent To  
Notes
2018-03-06 07:43:422017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 18021018
 ADD: 622 N. FLAGLER DR. SUITE: 1001
 CONT: GREGORY GIULIANO CONSTRUCTION INC.
 TEL: 561-301-1591
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2074 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: TUES. MARCH 6, 2018
 ACTION: BUILDING PROVISO
 1) THIS BUILDING WAS BUILT IN 2003 AND IS UNDER FAIR
 HOUSING GUIDELINE. THE KITCHEN ISLAND MUST COMPLY WITH:
  
 FAIR HOUSING GUIDELINES: REQUIREMENT 7 USEABLE
 KITCHENS.
  
 (1)USABLE KITCHENS. USABLE KITCHENS WOULD MEET SECTION
 100.205(C)(3)(IV) IF:
  
 (A)A CLEAR FLOOR SPACE AT LEAST 30 INCHES BY 48 INCHES
 THAT ALLOWS A PARALLEL APPROACH BY A PERSON IN A
 WHEELCHAIR IS PROVIDED AT THE RANGE OR COOKTOP AND SINK
 AND EITHER A PARALLEL OR FORWARD APPROACH IS PROVIDED
 AT OVEN, DISH WASHER, REFRIGERATOR/FREEZER OR TRASH
 COMPACTOR. (SEE FIGURE FHAG-6)
  
 (B)CLEARANCE BETWEEN COUNTERS AND ALL OPPOSING BASE
 CABINETS, COUNTERTOPS, APPLIANCES OR WALLS IS AT LEAST
 40 INCHES.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2018-03-23 Cont ID  
Sent By jpearson Date 2018-03-23 Time 09:15 Rev Time 0.00
Received By jpearson Date 2018-03-23 Time 09:15 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-03-13 Cont ID  
Sent By jpearson Date 2018-03-13 Time 11:05 Rev Time 0.00
Received By jpearson Date 2018-03-13 Time 06:31 Sent To  
Notes
2018-03-13 11:05:10CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. WRONG CODE SPECIFIED FOR DESIGN. THE PROVISIONS OF
 THE FLORIDA BUILDING CODE, RESIDENTIAL SHALL APPLY TO
 THE CONSTRUCTION, ALTERATION, MOVEMENT, ENLARGEMENT,
 REPLACEMENT, REPAIR, EQUIPMENT, USE AND OCCUPANCY,
 LOCATION, REMOVAL AND DEMOLITION OF DETACHED ONE- AND
 TWO-FAMILY DWELLINGS AND TOWNHOUSES NOT MORE THAN THREE
 STORIES ABOVE GRADE PLANE IN HEIGHT WITH A SEPARATE
 MEANS OF EGRESS AND THEIR ACCESSORY STRUCTURES NOT MORE
 THAN THREE STORIES ABOVE GRADE PLANE IN HEIGHT. PROVIDE
 CORRECTION. FBC RE R101.2
 2. NOTE STATES THAT RECEPTACLES SHALL BE TAMPER
 RESISTANT PER NEC 406.11. THIS CODE SECTION DOES NOT
 APPLY TO TAMPER RESISTANT RECEPTACLES. PROVIDE
 CORRECTION. NEC 406.12; FBC RE E4002.14
 3. PROVIDE PANEL SCHEDULE INDICATING ANY NEW OR ALTERED
 CIRCUITS, THE WIRE AND BREAKER SIZE FOR THESE CIRCUITS,
 AND AFCI OR GFCI PROTECTION WHERE APPLICABLE TO COMPLY
 WITH CODE. NEC 210.8, 210.12, 215.5, 408.4
 4. PROVIDE GFCI PROTECTION FOR DISHWASHER. NEC 210.8(D)
 5. PROVIDE AFCI PROTECTION PER CODE: ?BRANCH CIRCUITS
 THAT SUPPLY 120-VOLT, SINGLE-PHASE, 15- AND 20-AMPERE
 OUTLETS INSTALLED IN KITCHENS, FAMILY ROOMS, DINING
 ROOMS, LIVING ROOMS, PARLORS, LIBRARIES, DENS,
 BEDROOMS, SUN-ROOMS, RECREATIONS ROOMS, CLOSETS,
 HALLWAYS, LAUNDRY AREAS AND SIMILAR ROOMS OR AREAS
 SHALL BE AFCI PROTECTED.? PROVIDE CORRECTION. NEC
 210.12
 6. PROVIDE NOTE TO COMPLY WITH CODE FOR LIGHTING IN
 CLOSETS: "LIGHTING WITH OPEN OR PARTIALLY ENCLOSED
 LAMPS AND PENDANT LUMINAIRES OR LAMPHOLDERS SHALL NOT
 BE PERMITTED IN CLOTHES CLOSETS". NEC 410.16
 7. WILL THERE BE ANY ADDITIONAL LOADS ADDED, NEW
 EQUIPMENT? IF SO, PROVIDE LOAD CALCULATION, INCLUDE
 EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF SERVICE
 IS ADEQUATE. NEC 215.2, 220, 408.30
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2018-03-01 Cont ID  
Sent By scaldero Date 2018-03-01 Time 12:36 Rev Time 0.00
Received By scaldero Date 2018-03-01 Time 12:32 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2018-03-23 Time   Rev Time 0.00
Received By   Date 2018-03-23 Time   Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-03-15 Cont ID  
Sent By lcrespo Date 2018-03-15 Time 04:57 Rev Time 0.00
Received By lcrespo Date 2018-02-26 Time 11:03 Sent To  
Notes
2018-02-27 11:03:57C08

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2018-03-06 Cont ID  
Sent By   Date 2018-03-06 Time 07:29 Rev Time  
Received By   Date 2018-03-06 Time 06:47 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2018-03-13 Cont ID  
Sent By ccole Date 2018-03-13 Time 15:20 Rev Time 0.00
Received By ccole Date 2018-03-13 Time 15:20 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2018-03-15 Cont ID  
Sent By lcrespo Date 2018-03-15 Time 04:57 Rev Time 0.00
Received By lcrespo Date 2018-03-15 Time 04:34 Sent To  
Notes
***NONE***