| Plan Review Stops For Permit 18020994 |
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2018-02-28 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2018-02-27 |
Time |
12:55 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2018-02-27 |
Time |
12:55 |
Sent To |
|
|
| Notes |
| 2018-02-27 13:02:55 | FLORIDA BUILDING CODE 2014 5TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH ED | | | NFPA 70 2011 EDITION | | | | | | JAKE LEAHY | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6713 | | | | | | RISER DIAGRAM FROM METER CAN TO DISCONNECT WIRE TO | | | SMALL 350 KCMIL AL ONLY GOOD FOR 250A, CANNOT BE FUSED | | | AT 300A 240.4(B) |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2018-02-27 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2018-02-27 |
Time |
13:03 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2018-02-27 |
Time |
13:03 |
Sent To |
|
|
| Notes |
| 2018-02-26 09:37:12 | REVISION ROUTED TO JLEAHY |
|
|
|