Plan Review Details - Permit 18020994
Plan Review Stops For Permit 18020994
Review Stop E ELECTRICAL
Rev No 1 Status P Date 2018-02-28 Cont ID  
Sent By jleahy Date 2018-02-27 Time 12:55 Rev Time 0.00
Received By jleahy Date 2018-02-27 Time 12:55 Sent To  
Notes
2018-02-27 13:02:55FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH ED
 NFPA 70 2011 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
  
 RISER DIAGRAM FROM METER CAN TO DISCONNECT WIRE TO
 SMALL 350 KCMIL AL ONLY GOOD FOR 250A, CANNOT BE FUSED
 AT 300A 240.4(B)

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-02-27 Cont ID  
Sent By jleahy Date 2018-02-27 Time 13:03 Rev Time 0.00
Received By jleahy Date 2018-02-27 Time 13:03 Sent To  
Notes
2018-02-26 09:37:12REVISION ROUTED TO JLEAHY