Plan Review Details - Permit 18020949
Plan Review Stops For Permit 18020949
Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date   Cont ID  
Sent By   Date 2018-04-25 Time   Rev Time 0.00
Received By lmarchan Date 2018-04-20 Time 11:19 Sent To  
Notes
2018-04-23 11:20:03RESUB ROUTED TO CCOLE

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date   Cont ID  
Sent By   Date 2018-04-13 Time   Rev Time 0.00
Received By lmarchan Date 2018-04-10 Time 10:36 Sent To  
Notes
2018-04-11 10:36:32RESUB ROUTED TO CCOLE

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2018-03-15 Time   Rev Time 0.00
Received By lmarchan Date 2018-03-12 Time 13:10 Sent To  
Notes
2018-03-13 13:10:28RESUB ROUTED TO CCOLE

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2018-02-27 Time   Rev Time 0.00
Received By lmarchan Date 2018-02-22 Time 09:35 Sent To  
Notes
2018-02-23 09:35:19ROUTED TO MECHANICAL INBOX

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2018-04-25 Cont ID  
Sent By ccole Date 2018-04-25 Time 07:29 Rev Time 0.00
Received By ccole Date 2018-04-24 Time 17:54 Sent To I
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2018-04-13 Cont ID  
Sent By ccole Date 2018-04-13 Time 16:10 Rev Time 0.00
Received By ccole Date 2018-04-13 Time 16:10 Sent To I
Notes
2018-04-13 16:18:443RD REVIEW FBC-2017 MECHANICAL
 PERMIT #18020949
 4/13/18
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PROVIDE DUPLICATE COPIES OF THE AC PLANS- ONLY ONE
 PLAN SET WAS SUBMITED- SECTION 107.2.1 WPB AMENDMENTS
 TO THE FBC.
  
 2) PROVIDE THE MAKES AND MODEL NUMBERS OF THE AC
 SYSTEMS ON THE PLAN. SECTION 107.2.1.
  
 3 ) THE CONTRACTOR SHALL PROVIDE HIS SIGNATURE ON THE
 PLANS. ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND
 ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE OF
 THE PERSON RESPONSIBLE FOR THE DESIGN- SECTION 107.2.1
 FBC. WPB AMENDMENTS TO THE FBC.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2018-03-15 Cont ID  
Sent By ccole Date 2018-03-15 Time 14:02 Rev Time 0.00
Received By ccole Date 2018-03-15 Time 14:02 Sent To I
Notes
2018-03-15 14:05:242ND REVIEW FBC-2017 RESIDENTIAL MECHANICAL
 PERMIT #18020949
 3/15/18
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) AS PREVIOUSLY NOTED IN THE 1ST REVIEW, THE RETURN
 TRANSFER GRILLS IN THE BEDROOMS ARE UNDERSIDED. PLEASE
 ENLARGE THE GRILLS IN ACCORDANCE WITH SECTION M1602.3.
  
 2) THE PALM BEACH COUNTY PROPERTY APPRAISORS REPORT
 INDICATES THE RESIDENCE HAS HEATING AND AIR
 CONDITIONING, HOWEVER ACCORDING TO THE CONTRACTOR OF
 RECORD, THERE ARE NO EXISTING SYSTEMS. THE CONTRACTOR
 SHALL PROVIDE AC COOLING AND HEATING CALCULATIONS TO
 VERIFY SYSTEMS SELECTED ARE PROPERLY SIZED- M1401.3
  
 3) AN ELECTRICAL PLAN AND A PERMIT APPLICATION MUST BE
 SUBMITTED TO PROVIDE POWER TO THE AC SYSTREMS. SUBMIT A
 PLAN AND SUB-PERMIT APPLICATION UNDER THIS MECHANICAL
 PERMIT, OR SUBMIT A PLAN AND APPLICATION AS A SEPARATE
 PERMIT.
  
 4) THE SUBMITTAL FOR THE TIE-DOWN CLIP IS INCOMPLETE.
 PROVIDE THE COVER SHEET OF THE FLORIDA PRODUCT APPROVAL
 OR THE MIAMI-DADE NOA FOR THE CLIP, WHICHEVER IS
 APPLICABLE.
  
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2018-02-27 Cont ID  
Sent By ccole Date 2018-02-27 Time 12:56 Rev Time 0.00
Received By ccole Date 2018-02-27 Time 12:56 Sent To I
Notes
2018-02-27 13:23:011ST REVIEW FBC-2017 RESIDENTIAL MECHANICAL
 PERMIT #18020949
 2/27/18
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) CONTRACTOR'S SIGNATURE ON THE PLAN REQUIRED. ALL
 INFORMATION, DRAWINGS, SPECIFICATIONS AND ACCOMPANYING
 DATA SHALL BEAR THE NAME AND SIGNATURE OF THE PERSON
 RESPONSIBLE FOR THE DESIGN- SECTION 107.2.1 WEST PALM
 BEACH AMENDMENTS TO THE FBC.
  
 2) PROVIDE AC EQUIPMENT SCHEDULES ON THE PLANS.
  
 3) THE RETURN TRANSFERS ARE UNDERSIZED PER SECTION
 M1602.3. THE GRILLS SHALL BE SIZED 50 SQ. INCHES PER
 100 CFMS.
  
 4) PROVIDE ENGINEERING FOR TIE-DOWN OF THE NEW
 CONDENSERS- SECTION M1305.1.4.1
  
 CHRISTOPHER L. COLE
 BUILDING PLANS EXAMINER