| 2018-02-27 12:15:01 | 2017 FBC- BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 18020929 |
| | ADD: 8230 OKEECHOBEE BLVD. |
| | CONT: KAST CONSTRUCTION IV, LLC. |
| | TEL: 561-689-2910 |
| | E-MAIL: [email protected] |
| | |
| | 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| | BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: TUES. FEB. 27/ 2018 |
| | ACTION: DENIED |
| | |
| | 1) THIS PERMIT IS FOR A TEMPORARY CONSTRUCTION TRAILER. |
| | THE CITY NEEDS A BETTER DEFINITION OF THE USE FOR THIS |
| | CONSTRUCTION TRAILER. IS THE CONSTRUCTION TRAILER GOING |
| | TO BE USED FOR ONSITE PERSONNEL ONLY OR WILL THERE BE |
| | MEETINGS WITH OFFSITE VENDORS, ARCHITECT AND OR |
| | ENGINEERS THAT WOULD REQUIRE ACCESSIBLE ELEMENTS, |
| | ACCESSIBLE PARKING, ACCESSIBLE LANDINGS, RAMPS, STAIRS, |
| | HANDRAILS AND GUARDRAILS? |
| | |
| | 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION 102.2 BUILDING. (E) MOBILE OR MODULAR |
| | STRUCTURES USED AS TEMPORARY OFFICES, EXCEPT THAT THE |
| | PROVISIONS OF PART V (SECTION 553.501-553.513, FLORIDA |
| | STATUTES) RELATING TO ACCESSIBILITY BY PERSONS WITH |
| | DISABILITIES, AND PERMITS SHALL BE REQUIRED FOR |
| | STRUCTURAL SUPPORT AND TIE DOWN, ELECTRICAL SUPPLY, AND |
| | ALL UTILITY CONNECTIONS TO SUCH MOBILE OR MODULAR |
| | STRUCTURES. |
| | 2A) BOTH THE CIVIL SHEET C1 AND THE SOUTHEAST MODULAR |
| | MANUFACTURING PLANS 1-8 BOTH HAVE BEEN SHRUNK TO LESS |
| | THAN A 1/8 INCH SCALE, AND WILL NOT BE LEGIBLE AFTER |
| | SCANNING. THE PLANS DO NOT COMPLY WITH THE 2017 FLORIDA |
| | BUILDING CODE W 2017 WEST PALM BEACH AMENDMENTS TO THE |
| | FLORIDA BUILDING CODE, CHAPTER 1, ADMINISTRATION |
| | 107.2.1.4 QUALITY OF BUILDING PLANS. BUILDING PLANS |
| | SHALL BE DRAWN TO A MINIMUM 1/8 INCH SCALE. THE |
| | BUILDING OFFICIAL MAY ESTABLISH THROUGH DEPARTMENTAL |
| | POLICY, OTHER STANDARDS FOR PLANS AND SPECIFICATIONS, |
| | IN ORDER TO PROVIDE CONFORMITY TO ITS RECORD RETENTION |
| | PROGRAM. THIS POLICY MAY INCLUDE SUCH THINGS AS MINIMUM |
| | SIZE, SHAPE, CONTRAST, CLARITY, OR OTHER ITEMS RELATED |
| | TO RECORDS MANAGEMENT. ELECTRONIC MEDIA MUST BE |
| | COMPATIBLE WITH THE ARCHIVE REQUIREMENTS OF FLORIDA |
| | STATUTES. |
| | 2B) PLEASE NOTE THE SUBMITTED BOUNDARY & TOPOGRAPHIC |
| | SURVEY DOES NOT SHOW THERE ARE 2 AREAS WITHIN THE LOT |
| | LINE THAT ARE IN AN AE FLOOD ZONE. |
| | ARTICLE XVII ORDINANCES ARTICLE XVII FLOOD PREVENTION & |
| | CONTROL. FBC BUILDING 1612 AND CITY OF WPB CODE OF |
| | SECTION 94-546. STRUCTURE IS LOCATED IN AN "A" FLOOD |
| | ZONE. A FLOOD ELEVATION CERTIFICATE WILL BE REQUIRED. |
| | PLEASE REVIEW CITY ORDINANCE FOR THE CITY REQUIREMENTS |
| | AFTER OCT. 11/ 2017 TWO FOOT OF FREE BOARD WILL BE |
| | REQUIRED ABOVE BASE FLOOD. |
| | DURING THE PERMITTING OF THIS STRUCTURE THERE WILL BE |
| | REQUIRED (3) DIFFERENT FLOOD ZONE CERTIFICATES |
| | REQUIRED: |
| | 2B)(1) A FLOOD ZONE CERTIFICATE IS REQUIRED AS PART OF |
| | THE PLAN REVIEW DOCUMENTS WITH THE PROPOSED FINISH |
| | FLOOR HEIGHT. W. P. B. ADMINISTRATIVE CODE 107.3.5.1.1 |
| | BUILDING MINIMUM PLAN REVIEW CRITERIA FOR COMMERCIAL |
| | BUILDINGS. ( 8) FLOOD REQUIREMENTS ELEVATIONS, |
| | ENCLOSURES, FLOOD DAMAGE-RESISTANT MATERIALS. |
| | 2B)(2) ONCE THE FIRST FLOOR SLAB IS POURED THE 2ND |
| | ELEVATION CERTIFICATE IS REQUIRED. W. P. B. |
| | ADMINISTRATIVE CODE 110.3 REQUIRED INSPECTIONS 1.2 |
| | FLOOR/ SLAB INSPECTION. IN FLOOD HAZARD AREAS, UPON |
| | PLACEMENT OF THE LOWEST FLOOR, INCLUDING BASEMENT, AND |
| | PRIOR TO FURTHER VERTICAL CONSTRUCTION, THE ELEVATION |
| | CERTIFICATION, REQUIRED IN SECTION 1612.5, SHALL BE |
| | SUBMITTED TO THE BUILDING OFFICIAL. |
| | 2B)(3) BEFORE THE ISSUANCE OF A CERTIFICATE OF |
| | OCCUPANCY OR A CERTIFICATE OF COMPLETION THE 3RD FLOOD |
| | ZONE CERTIFICATE IS REQUIRED WITH THE HEIGHT OF ALL |
| | EXTERIOR ATTENDANTS A/C PADS OR OTHER SLABS FOR |
| | GENERATORS. |
| | W. P. B. ADMINISTRATIVE CODE 110.3 REQUIRED INSPECTIONS |
| | (6) FINAL INSPECTION. TO BE MADE AFTER THE BUILDING IS |
| | COMPLETED AND READY FOR OCCUPANCY. 6.1. LOWEST FLOOR |
| | ELEVATION. IN FLOOD HAZARD AREAS, AS PART OF THE FINAL |
| | INSPECTION, A FINAL CERTIFICATION OF THE LOWEST FLOOR |
| | ELEVATION SHALL BE SUBMITTED TO THE AUTHORITY HAVING |
| | JURISDICTION. |
| | |
| | 3) PLEASE NOTE THE SOUTHEAST MODULAR MANUFACTURING |
| | THIRD PARTY STATE APPROVED PLAN ON SHEET 1 OF 8 THE |
| | SITE INSTALLED NOTE # 1 STATES A COMPLETE FOUNDATION |
| | SUPPORT AND TIE DOWN SYSTEM IS REQUIRED, THIS IS NOT |
| | PART OF THE STATE APPROVED PLAN. NOTE ON SHEET 1 OF 8 |
| | FOUNDATION NOTE STATES THE FOUNDATION PLANS IS NOT |
| | INCLUDED UNDER THE STATE REVIEW. 107.2.1.3 ADDITIONAL |
| | INFORMATION IS REQUIRED. |
| | 2017 FBC-B 1604.8.1 ANCHORAGE OF THE ROOF TO WALLS AND |
| | COLUMNS, AND OF WALLS AND COLUMNS TO FOUNDATIONS, SHALL |
| | BE PROVIDED TO RESIST THE UPLIFT AND SLIDING FORCES |
| | THAT RESULT FROM THE APPLICATION OF THE PRESCRIBED |
| | LOADS. |
| | |
| | 4) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| | & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |