Plan Review Details - Permit 18020929
Plan Review Stops For Permit 18020929
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-02-27 Cont ID  
Sent By jwitmer Date 2018-02-27 Time 12:29 Rev Time 0.00
Received By jwitmer Date 2018-02-27 Time 08:14 Sent To  
Notes
2018-02-27 12:15:012017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 18020929
 ADD: 8230 OKEECHOBEE BLVD.
 CONT: KAST CONSTRUCTION IV, LLC.
 TEL: 561-689-2910
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: TUES. FEB. 27/ 2018
 ACTION: DENIED
  
 1) THIS PERMIT IS FOR A TEMPORARY CONSTRUCTION TRAILER.
 THE CITY NEEDS A BETTER DEFINITION OF THE USE FOR THIS
 CONSTRUCTION TRAILER. IS THE CONSTRUCTION TRAILER GOING
 TO BE USED FOR ONSITE PERSONNEL ONLY OR WILL THERE BE
 MEETINGS WITH OFFSITE VENDORS, ARCHITECT AND OR
 ENGINEERS THAT WOULD REQUIRE ACCESSIBLE ELEMENTS,
 ACCESSIBLE PARKING, ACCESSIBLE LANDINGS, RAMPS, STAIRS,
 HANDRAILS AND GUARDRAILS?
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION 102.2 BUILDING. (E) MOBILE OR MODULAR
 STRUCTURES USED AS TEMPORARY OFFICES, EXCEPT THAT THE
 PROVISIONS OF PART V (SECTION 553.501-553.513, FLORIDA
 STATUTES) RELATING TO ACCESSIBILITY BY PERSONS WITH
 DISABILITIES, AND PERMITS SHALL BE REQUIRED FOR
 STRUCTURAL SUPPORT AND TIE DOWN, ELECTRICAL SUPPLY, AND
 ALL UTILITY CONNECTIONS TO SUCH MOBILE OR MODULAR
 STRUCTURES.
 2A) BOTH THE CIVIL SHEET C1 AND THE SOUTHEAST MODULAR
 MANUFACTURING PLANS 1-8 BOTH HAVE BEEN SHRUNK TO LESS
 THAN A 1/8 INCH SCALE, AND WILL NOT BE LEGIBLE AFTER
 SCANNING. THE PLANS DO NOT COMPLY WITH THE 2017 FLORIDA
 BUILDING CODE W 2017 WEST PALM BEACH AMENDMENTS TO THE
 FLORIDA BUILDING CODE, CHAPTER 1, ADMINISTRATION
 107.2.1.4 QUALITY OF BUILDING PLANS. BUILDING PLANS
 SHALL BE DRAWN TO A MINIMUM 1/8 INCH SCALE. THE
 BUILDING OFFICIAL MAY ESTABLISH THROUGH DEPARTMENTAL
 POLICY, OTHER STANDARDS FOR PLANS AND SPECIFICATIONS,
 IN ORDER TO PROVIDE CONFORMITY TO ITS RECORD RETENTION
 PROGRAM. THIS POLICY MAY INCLUDE SUCH THINGS AS MINIMUM
 SIZE, SHAPE, CONTRAST, CLARITY, OR OTHER ITEMS RELATED
 TO RECORDS MANAGEMENT. ELECTRONIC MEDIA MUST BE
 COMPATIBLE WITH THE ARCHIVE REQUIREMENTS OF FLORIDA
 STATUTES.
 2B) PLEASE NOTE THE SUBMITTED BOUNDARY & TOPOGRAPHIC
 SURVEY DOES NOT SHOW THERE ARE 2 AREAS WITHIN THE LOT
 LINE THAT ARE IN AN AE FLOOD ZONE.
 ARTICLE XVII ORDINANCES ARTICLE XVII FLOOD PREVENTION &
 CONTROL. FBC BUILDING 1612 AND CITY OF WPB CODE OF
 SECTION 94-546. STRUCTURE IS LOCATED IN AN "A" FLOOD
 ZONE. A FLOOD ELEVATION CERTIFICATE WILL BE REQUIRED.
 PLEASE REVIEW CITY ORDINANCE FOR THE CITY REQUIREMENTS
 AFTER OCT. 11/ 2017 TWO FOOT OF FREE BOARD WILL BE
 REQUIRED ABOVE BASE FLOOD.
 DURING THE PERMITTING OF THIS STRUCTURE THERE WILL BE
 REQUIRED (3) DIFFERENT FLOOD ZONE CERTIFICATES
 REQUIRED:
 2B)(1) A FLOOD ZONE CERTIFICATE IS REQUIRED AS PART OF
 THE PLAN REVIEW DOCUMENTS WITH THE PROPOSED FINISH
 FLOOR HEIGHT. W. P. B. ADMINISTRATIVE CODE 107.3.5.1.1
 BUILDING MINIMUM PLAN REVIEW CRITERIA FOR COMMERCIAL
 BUILDINGS. ( 8) FLOOD REQUIREMENTS ELEVATIONS,
 ENCLOSURES, FLOOD DAMAGE-RESISTANT MATERIALS.
 2B)(2) ONCE THE FIRST FLOOR SLAB IS POURED THE 2ND
 ELEVATION CERTIFICATE IS REQUIRED. W. P. B.
 ADMINISTRATIVE CODE 110.3 REQUIRED INSPECTIONS 1.2
 FLOOR/ SLAB INSPECTION. IN FLOOD HAZARD AREAS, UPON
 PLACEMENT OF THE LOWEST FLOOR, INCLUDING BASEMENT, AND
 PRIOR TO FURTHER VERTICAL CONSTRUCTION, THE ELEVATION
 CERTIFICATION, REQUIRED IN SECTION 1612.5, SHALL BE
 SUBMITTED TO THE BUILDING OFFICIAL.
 2B)(3) BEFORE THE ISSUANCE OF A CERTIFICATE OF
 OCCUPANCY OR A CERTIFICATE OF COMPLETION THE 3RD FLOOD
 ZONE CERTIFICATE IS REQUIRED WITH THE HEIGHT OF ALL
 EXTERIOR ATTENDANTS A/C PADS OR OTHER SLABS FOR
 GENERATORS.
 W. P. B. ADMINISTRATIVE CODE 110.3 REQUIRED INSPECTIONS
 (6) FINAL INSPECTION. TO BE MADE AFTER THE BUILDING IS
 COMPLETED AND READY FOR OCCUPANCY. 6.1. LOWEST FLOOR
 ELEVATION. IN FLOOD HAZARD AREAS, AS PART OF THE FINAL
 INSPECTION, A FINAL CERTIFICATION OF THE LOWEST FLOOR
 ELEVATION SHALL BE SUBMITTED TO THE AUTHORITY HAVING
 JURISDICTION.
  
 3) PLEASE NOTE THE SOUTHEAST MODULAR MANUFACTURING
 THIRD PARTY STATE APPROVED PLAN ON SHEET 1 OF 8 THE
 SITE INSTALLED NOTE # 1 STATES A COMPLETE FOUNDATION
 SUPPORT AND TIE DOWN SYSTEM IS REQUIRED, THIS IS NOT
 PART OF THE STATE APPROVED PLAN. NOTE ON SHEET 1 OF 8
 FOUNDATION NOTE STATES THE FOUNDATION PLANS IS NOT
 INCLUDED UNDER THE STATE REVIEW. 107.2.1.3 ADDITIONAL
 INFORMATION IS REQUIRED.
 2017 FBC-B 1604.8.1 ANCHORAGE OF THE ROOF TO WALLS AND
 COLUMNS, AND OF WALLS AND COLUMNS TO FOUNDATIONS, SHALL
 BE PROVIDED TO RESIST THE UPLIFT AND SLIDING FORCES
 THAT RESULT FROM THE APPLICATION OF THE PRESCRIBED
 LOADS.
  
 4) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-03-15 Cont ID  
Sent By jpearson Date 2018-03-15 Time 17:08 Rev Time 0.00
Received By jpearson Date 2018-03-15 Time 15:15 Sent To  
Notes
2018-03-15 17:08:21CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE RISER DIAGRAM, SHOWING ALL DETAILS OF
 SERVICE EQUIPMENT, UNDERGROUND OR OVERHEAD SERVICE,
 WIRE AND BREAKER SIZES FOR SERVICE AND FEED TO ANY
 SUB-PANEL(S). SHOW GEC SIZE AND SYSTEM, SHOW
 INTERSYSTEM BONDING TERMINATION POINT. NEC 215.5, 230,
 250.50, 250.94, 408.30
 2. PROVIDE LOAD CALCULATION FOR SERVICE TO CONFIRM
 CAPACITY OF SERVICE IS ADEQUATE. NEC 215.2, 220, 408.30
 3. PROVIDE AIC RATING OF SERVICE DISCONNECT AND PANEL.
 NEC 110.3, 110.9
 4. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR EACH
 PANEL INCLUDING INFORMATION FROM THE POWER COMPANY
 STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR
 THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE
 SERVICE EQUIPMENT AND DOWNSTREAM PANELS IS ADEQUATE.
 NEC 110.9, 110.10
 5. PROVIDE NOTES TO INDICATE THE REQUIRED MARKING OF
 SERVICE EQUIPMENT FOR ARC FLASH HAZARD WARNING AND
 AVAILABLE FAULT CURRENT PER CODE. NEC 110.16, 110.24
 6. PROVIDE THE REQUIRED SERVICE AREA RECEPTACLE PER
 CODE. NEC 210.64
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2018-03-01 Cont ID  
Sent By scaldero Date 2018-03-01 Time 11:51 Rev Time 0.00
Received By scaldero Date 2018-03-01 Time 11:38 Sent To  
Notes
2018-03-01 11:51:16PERMIT # 18020929
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 FIRE COMMENTS:
  
 1) PLEASE ADDRESS COMMENTS UNDER BUILDING REVIEW.
  
 2) PLEASE PROVIDE THE DISTANCE FROM THE TRAILER TO THE
 LIFT STATION SHOWN ON THE SITE PLAN. DISTANCES FROM
 OTHER STRUCTURES SHALL COMPLY WITH THE FOLLOWING:
  
 PER NFPA 241 ? STANDARD FOR SAFEGUARDING CONSTRUCTION,
 ALTERATION, AND DEMOLITION OPERATIONS, SECTION 4.2
 TEMPORARY CONSTRUCTION TRAILERS SHALL BE SEPARATED FROM
 ADJACENT TRAILERS OR STRUCTURES IN ACCORDANCE WITH
 TABLE 4.2.1. PER TABLE 4.2.1:
 1) 20 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 30 FEET.
 2) 30 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 35 FEET.
 3) 40 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 40 FEET.
 4) 50 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 45 FEET.
 5) 60 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 60 FEET.
 **A 75 PERCENT REDUCTION IN SEPARATION DISTANCES SHALL
 BE PERMITTED TO BE APPLIED, PROVIDED AUTOMATIC
 SPRINKLER PROTECTION IS USED IN THE EXPOSING STRUCTURE.
  
 3) DRAWINGS WILL BE STAMPED, INITIALED, AND DATED BY
 THE FIRE DEPARTMENT AFTER ALL PLAN REVIEWER COMMENTS
 HAVE BEEN SATISFIED.
  
  
 SUE ELLEN CALDERON
 ASSISTANT FIRE MARSHAL
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-04-19 Cont ID  
Sent By cpuell Date 2018-04-19 Time 14:01 Rev Time 0.00
Received By cpuell Date 2018-02-22 Time 10:20 Sent To  
Notes
2018-02-23 10:20:43B02

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2018-03-08 Cont ID  
Sent By ccole Date 2018-03-08 Time 11:42 Rev Time 0.00
Received By ccole Date 2018-03-08 Time 11:42 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2018-03-17 Cont ID  
Sent By gjohnson Date 2018-03-17 Time 06:25 Rev Time 0.00
Received By gjohnson Date 2018-03-17 Time 06:25 Sent To  
Notes
2018-03-17 06:33:511ST REVIEW: FBC 2017 6TH EDITION
  
 PLUMBING COMMENTS:
  
 1. SHOW LOCATION AND SIZE OF WATER SERVICE. PER WPB
 AMEND TO FBC 107.2.1
  
 2. BACKFLOW REQUIRED ON WATER SERVICE PLACE NOTE ON
 PLAN SEPARATE PERMIT REQUIRED FOR BACKFLOW. PER WPB
 UTILITIES DEPT CROSS CONNECTION MANUAL
  
 3. SHOW SIZE AND LOCATION OF HOLDING TANK IF OVER 300
 GAL A PERMIT FROM FLORIDA DEPARTMENT OF HEALTH IS
 REQUIRED. PER WPB AMEND TO FBC 107.2.1
  
 4. PROVIDE CONTRACT FOR HOLDING TANK PUMP OUT. PER WPB
 AMEND TO FBC 107.2.1
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop Z ZONING
Rev No 1 Status P Date 2018-04-19 Cont ID  
Sent By AH Date 2018-04-19 Time   Rev Time 0.00
Received By ahansen Date 2018-04-19 Time 10:43 Sent To I
Notes
***NONE***