Plan Review Details - Permit 18020922
Plan Review Stops For Permit 18020922
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2018-03-06 Cont ID  
Sent By cthroop Date 2018-03-06 Time 15:36 Rev Time 0.00
Received By cthroop Date 2018-03-06 Time 14:56 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2018-03-02 Cont ID  
Sent By jleahy Date 2018-03-02 Time 13:57 Rev Time 0.00
Received By jleahy Date 2018-03-02 Time 13:57 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2018-03-01 Cont ID  
Sent By lcrespo Date 2018-03-01 Time 14:14 Rev Time 0.00
Received By lcrespo Date 2018-03-01 Time 14:14 Sent To  
Notes
2018-03-01 14:17:39DENIED
  
 1. THE DETAILS ON OF THE CATHODIC PROTECTION ARE NOT
 CLEAR AS IT IS A COPY OF A COPY; SIZE (LBS) & A NUMBER
 OF MAGNESIUM BAG(S), SIZE & TYPE OF ANODE CABLE. A
 CATHODIC PROTECTION SYSTEM SHALL BE REQUIRED PER NFPA
 58 SECS. 5.2.1.11, 6.6.6.1 (I) AND SHALL BE MONITORED
 PER NFPA 58 SEC.6.6.6.1 (J). WPB AMENDMENTS TO THE FBC
 SEC. 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 2. NEED REGULATORS MANUAL, WHEN INSTALLED OUTDOORS
 SHALL BE DESIGNED, INSTALLED OR PROTECTED SO THEIR
 OPERATION WILL NOT BE AFFECTED BY THE ELEMENTS. PROVIDE
 DOCUMENTATION FROM THE MANUFACTURER THAT THE REGULATORS
 ARE APPROVED FOR EXTERIOR USE AND HAVE IT ON SITE AT
 THE TIME OF INSPECTIONS. NFPA 58-11 SEC. 6.8.1.5.
  
 3. NFPA 37, SECTION 4.1.4, ENGINES LOCATED OUTDOORS.
 ENGINES, AND THEIR WEATHERPROOF HOUSINGS, IF PROVIDED,
 THAT ARE INSTALLED OUTDOORS SHALL BE LOCATED AT LEAST 5
 FT FROM OPENINGS IN WALLS AND AT LEAST 5 FT FROM
 STRUCTURES HAVING COMBUSTIBLE WALLS. A MINIMUM
 SEPARATION SHALL NOT BE REQUIRED WHERE EITHER OF THE
 FOLLOWING CONDITIONS EXIST;
  
 (1) ALL WALLS OF THE STRUCTURE THAT ARE CLOSER THAN 5
 FT FROM THE ENGINE ENCLOSURE HAVE A FIRE RESISTANCE
 RATING OF
 AT LEAST 1 HOUR.
  
 (2)*THE WEATHERPROOF ENCLOSURE IS CONSTRUCTED OF
 NONCOMBUSTIBLE MATERIALS AND IT HAS BEEN DEMONSTRATED
 THAT A FIRE WITHIN THE ENCLOSURE WILL NOT IGNITE
 COMBUSTIBLE MATERIALS OUTSIDE THE ENCLOSURE.
  
 A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS TIME
 AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE GENERATED
 UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 LUIS A. CRESPO
 PLUMBING INSPECTOR /
 PLUMBING PLAN REVIEW
 [email protected]
 561-805-6720
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-03-06 Cont ID  
Sent By cthroop Date 2018-03-06 Time 15:36 Rev Time 0.00
Received By cthroop Date 2018-02-22 Time 09:45 Sent To I
Notes
2018-02-23 09:46:09ROUTED TO ZONING INBOX

Review Stop Z ZONING
Rev No 1 Status F Date 2018-02-28 Cont ID  
Sent By PG Date 2018-02-28 Time   Rev Time 0.00
Received By pgreilic Date 2018-02-28 Time 09:59 Sent To  
Notes
2018-02-28 10:23:50FAILED
  
 SEC. 94-305. - SETBACKS.
 (4) MECHANICAL EQUIPMENT. MECHANICAL EQUIPMENT MAY NOT
 PROJECT MORE THAN FOUR FEET INTO A SETBACK. (10 FEET
 REQUIRED SETBACK PER ORD. 2541-92)
  
 PAUL GREILICH, SENIOR PLANNER
 561-822-1443
 [email protected]
  
  