Plan Review Details - Permit 18020853
Plan Review Stops For Permit 18020853
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2018-04-13 Cont ID  
Sent By skennedy Date 2018-04-13 Time 08:45 Rev Time 0.00
Received By skennedy Date 2018-04-12 Time 15:24 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-03-21 Cont ID  
Sent By jgomez Date 2018-03-20 Time 18:43 Rev Time 0.00
Received By jgomez Date 2018-03-20 Time 16:14 Sent To  
Notes
2018-03-20 18:01:56RESIDENTIAL (R3) ADDITION/ALTERATION, BUILDING REVIEW
 COMMENTS
 CODE: FBC 6TH EDITION (2017).
  
 1- THE CURRENT CODE IS THE FBC 6TH EDITION (2017) NOT
 THE FBC 5TH EDITION (2014). CHAPTER 553 FLORIDA
 STATUTE. UPDATE ALL NOTES IN SHEET 01 AND SHEET D-1 AS
 REQUIRED.
  
 2- THE USE OF THE PROPOSED SPACE IS NOT CLEAR. PERMIT
 APPLICATION SPECIFIES "ENCLOSING ROOM TO BEDROOM",
 WHILE PLANS SHOW A NEW "DEN" ROOM. REVISE AS REQUIRED
 TO MATCH FOR PROPER PLAN REVIEW. SEC. 102.2 CITY
 AMENDMENTS.
  
 3- A) PROVIDE COMPLETE FRAMING DETAILS FOR NEW EXTERIOR
 DOOR. SPECIFY ALL FRAMING MEMBERS AND CONNECTORS. SEC.
 R301.1 FBC-RESIDENTIAL. NOTE: PROVIDE COMPLETE
 SPECIFICATIONS FOR ATTACHMENT OF (3)2X6 STUDS TO
 EXISTING CONCRETE BLOCK WALL. FLOOR PLAN ON SHEET 01
 ONLY SPECIFIES ATTACHMENT OF THE 1ST STUD.
  
 B) PROVIDE COMPLETE FRAMING DETAILS FOR NEW INTERIOR
 DOOR. SPECIFY ALL FRAMING MEMBERS AND CONNECTORS. IT'S
 NOT CLEAR IF THE INTERIOR NON-BEARING WALL IS METAL
 FRAMING OR WOOD FRAMING. FLOOR PLAN ON SHEET 01
 SPECIFIES METAL, WHILE NON-LOAD BEARING WALL DETAIL ON
 SHEET D-1 SPECIFIES WOOD. REVISE AS REQUIRED TO MATCH.
 SEC. 107.2.1 CITY AMENDMENTS.
  
 4- INFILL TYPICAL WALL SECTION ON SHEET D-1:
 A) DETAIL DOESN'T MATCH REAR ELEVATION SHOWN ON SHEET
 01. THERE IS NOT FLAT ROOF IN THIS AREA. REVISE AS
 REQUIRED TO MATCH. SEC. 107.2.1 CITY AMENDMENTS.
  
 B) DETAIL IS MISSING WALL SHEATHING FASTENING
 SPECIFICATIONS SPECIFY NAIL TYPE AND SPACING. SEC.
 R301.1 FBC-RESIDENTIAL.
  
 5- ENERGY CALCULATIONS SUBMITTED:
 A) ITEM #4 IS INCORRECT. IT LOOKS LIKE THERE IS A
 BEDROOM. NEED TO COORDINATE WITH ITEM #2 ABOVE. REVISE
 AS REQUIRED. SEC. R101.5.1.1.2 FBC-RESIDENTIAL.
  
 B) ITEM #9 IS INCORRECT. PLANS CALL FOR EXTERIOR WOOD
 FRAMED WALL. SEE PLANS AND REVISE AS REQUIRED. SEC.
 R101.5.1.1.2 FBC-RESIDENTIAL.
  
 C) ITEM #10 IS INCORRECT. PLANS CALL FOR R-19
 INSULATION. REVISE AS REQUIRED. SEC. R101.5.1.1.2
 FBC-RESIDENTIAL.
  
 D) ROOF MATERIAL SPECIFIED ON PAGE 2 OF 4 IS INCORRECT.
 IT IS NOT SHINGLES. REVISE AS REQUIRED. SEC.
 R101.5.1.1.2 FBC-RESIDENTIAL.
  
 E) PROVIDE COMPLETE INFORMATION ON TOP OF FORM,
 INCLUDING OWNER'S NAME AND BUILDER'S NAME. SEC.
 R101.5.1.1.2 FBC-RESIDENTIAL.
  
 F) PROVIDE THE NAME OF PERSON PERFORMING THE ANALYSIS
 AND GENERATING THE REPORT AS REQUIRED BY SEC.
 R405.4.2.1 FBC-RESIDENTIAL.
  
 6- SPECIFY CARBON MONOXIDE ALARM WITHING ALL SLEEPING
 ROOMS, INCLUDING EXISTING BEDROOMS AS REQUIRED BY SEC.
 R315.1 FBC-RESIDENTIAL.
 R315.1 CARBON MONOXIDE PROTECTION.
 EVERY SEPARATE BUILDING OR AN ADDITION TO AN EXISTING
 BUILDING FOR WHICH A PERMIT FOR NEW CONSTRUCTION IS
 ISSUED AND HAVING A FOSSIL-FUEL-BURNING HEATER OR
 APPLIANCE, A FIREPLACE, AN ATTACHED GARAGE, OR OTHER
 FEATURE, FIXTURE, OR ELEMENT THAT EMITS CARBON MONOXIDE
 AS BYPRODUCT OF COMBUSTION SHALL HAVE AN OPERATIONAL
 CARBON MONOXIDE ALARM INSTALLED WITHIN 10 FEET OF EACH
 ROOM USED FOR SLEEPING PURPOSES.
  
 7- BEFORE A PERMIT TO CONSTRUCT CAN BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. UPON APPROVAL,
 ONE SET OF PLANS SHALL BE SIGNED OUT AND SUBMITTED TO
 PALM BEACH COUNTY FOR AN IMPACT FEE REVIEW. THE PLANS
 WITH THE IMPACT FEE STAMP AND A COPY OF THE PAID
 RECEIPT MUST BE RETURNED TO THE CITY BUILDING
 DEPARTMENT BEFORE THE BUILDING PERMIT CAN BE ISSUED.
 FOR INFORMATION CALL PALM BEACH COUNTY IMPACT FEES AT
 (561) 233-5025.
  
 ****PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO HELP EXPEDITE THE REVIEW PROCESS.
  
 ****PLEASE INSERT ANY REVISED DRAWING AND REMOVE OLD
 DRAWING. SUBMIT OLD DRAWINGS FOR REFERENCE OF ALREADY
 REVIEWED DRAWINGS. DON?T STAPLE OLD DRAWINGS TO PLANS.
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  
  
  
 -CARBON MONOXIDE ALARM

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2018-04-13 Cont ID  
Sent By skennedy Date 2018-04-13 Time 08:44 Rev Time 0.00
Received By skennedy Date 2018-04-13 Time 08:44 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-03-20 Cont ID  
Sent By jpearson Date 2018-03-20 Time 13:53 Rev Time 0.00
Received By jpearson Date 2018-03-20 Time 09:52 Sent To  
Notes
2018-03-20 13:53:35CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. ELECTRICAL PLAN IS REQUIRED TO BE SIGNED BY PERSON
 RESPONSIBLE FOR THE DESIGN. PROVIDE CORRECTION. FS
 481.229; WPB FBC 107.2.1, 107.3.5.1.2
 2. THE NEC AND FBC SPECIFIED FOR DESIGN IS NOT THE
 CURRENT CODE. PROVIDE CORRECTION. FBC PREFACE (ALSO SEE
 CURRENT CODES ABOVE)
 3. ALL BRANCH CIRCUITS THAT SUPPLY 120-VOLT,
 SINGLE-PHASE, 15- AND 20-AMPERE OUTLETS INSTALLED IN
 KITCHENS, FAMILY ROOMS, DINING ROOMS, LIVING ROOMS,
 PARLORS, LIBRARIES, DENS, BEDROOMS, SUN-ROOMS,
 RECREATIONS ROOMS, CLOSETS, HALLWAYS, LAUNDRY AREAS AND
 SIMILAR ROOMS OR AREAS SHALL BE AFCI PROTECTED. PROVIDE
 CORRECTION. NEC 210.12; FBC RE E3902.16
 4. PROVIDE SMOKE/CO ALARMS IN EACH LOCATION REQUIRED
 PER CODE. SHOW ON PLAN ALL EXISTING ALARMS. IF NONE ARE
 EXISTING OR NOT TO CODE, SHOW AS NEW INSTALLATIONS. FBC
 RE R314.3, R315.1; WPB FBC 107.2.1
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-04-13 Cont ID  
Sent By skennedy Date 2018-04-13 Time 08:45 Rev Time 0.00
Received By skennedy Date 2018-04-06 Time 10:48 Sent To  
Notes
2018-04-11 13:23:29TO SAK DESK
  
2018-04-09 10:49:03R17

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-03-21 Cont ID  
Sent By jgomez Date 2018-03-20 Time 18:43 Rev Time 0.00
Received By jgomez Date 2018-02-21 Time 14:02 Sent To I
Notes
2018-02-22 14:02:23R10

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2018-04-12 Cont ID  
Sent By skennedy Date 2018-04-12 Time 15:18 Rev Time 0.00
Received By skennedy Date 2018-04-12 Time 15:18 Sent To  
Notes
2018-04-13 08:44:50MU-2018-010431-0000 NO PAYMENT REQUIRED. THE OLD PLAN
 WAS INADVERTANTLY THROWN OUT. I VERIFIED WITH CALL TO
 PBCIF OFFICE.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2018-03-21 Cont ID  
Sent By jgomez Date 2018-03-20 Time 18:43 Rev Time 0.00
Received By jgomez Date 2018-03-20 Time 18:43 Sent To  
Notes
2018-03-21 09:52:40BEFORE A PERMIT TO CONSTRUCT CAN BE ISSUED, IMPACT FEES
 MUST BE PAID TO PALM BEACH COUNTY. UPON APPROVAL, ONE
 SET OF PLANS SHALL BE SIGNED OUT AND SUBMITTED TO PALM
 BEACH COUNTY FOR AN IMPACT FEE REVIEW. THE PLANS WITH
 THE IMPACT FEE STAMP AND A COPY OF THE PAID RECEIPT
 MUST BE RETURNED TO THE CITY BUILDING DEPARTMENT BEFORE
 THE BUILDING PERMIT CAN BE ISSUED. FOR INFORMATION CALL
 PALM BEACH COUNTY IMPACT FEES AT (561) 233-5025.
  
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2018-04-12 Cont ID  
Sent By skennedy Date 2018-04-12 Time 15:23 Rev Time 0.00
Received By skennedy Date 2018-04-12 Time 15:23 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2018-03-20 Cont ID  
Sent By cmontell Date 2018-03-20 Time 14:53 Rev Time 0.00
Received By cmontell Date 2018-03-20 Time 14:52 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date   Cont ID  
Sent By PG Date 2018-02-28 Time   Rev Time 0.00
Received By pgreilic Date 2018-02-28 Time 15:43 Sent To  
Notes