Plan Review Details - Permit 18020839
Plan Review Stops For Permit 18020839
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2018-05-22 Cont ID  
Sent By shill Date 2018-05-22 Time 12:11 Rev Time 0.00
Received By shill Date 2018-05-22 Time 12:11 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-02-26 Cont ID  
Sent By jwitmer Date 2018-02-26 Time 11:19 Rev Time 0.00
Received By jwitmer Date 2018-02-26 Time 08:20 Sent To  
Notes
2018-02-26 11:19:472017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 18020839
 ADD: 901 45TH ST.
 CONT: WESTBROOKE CORP.
 TEL: 561-395-4126
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: MON. FEB. 26/ 2018
 ACTION: DENIED
  
 1) THE COVERSHEET A0.0 INDICATES UNDER THE HEADING
 BUILDING DATA THE 2017 FLORIDA BUILDING CODE WHEREAS
 UNDER THE HEADING APPLICABLE CODES THE 2014 FBC IS
 LISTED AS THE FAMILY OF CODES, BUILDING, ACCESSIBILITY,
 PLUMBING, MECHANICAL, & EXISTING BUILDING CODE. PLEASE
 UPDATE THE DISCREPANCY IN PLANS. DEC. 31/ 2017 THE 2017
 OR 6TH EDITION OF THE FLORIDA BUILDING CODE WAS ADOPTED
 STATEWIDE.
  
 2) PLEASE UPDATE THE PERMIT APPLICATION UNDER THE
 DESCRIPTION OF WORK. THE APPLICATION INDICATES THE
 RENOVATION OF 9 RESTROOMS WHEREAS THE SHEET A1.1 SHOWS
 9 PATIENT RESTROOMS AND TREATMENT RESTROOM 2257 BEING
 RENOVATED, A TOTAL OF 10. PLEASE CORRECT.
  
 3) THE PERMIT APPLICATION SHOWS A VALUE OF $91,420.00
 DOLLARS. THE 2017 FBC-ACCESSIBILITY CODE REQUIRES
 COMPLIANCE WITH:
 3A) 805.4 TOILET AND BATHING ROOMS. TOILET AND BATHING
 ROOMS THAT ARE PROVIDED AS PART OF A PATIENT OR
 RESIDENT SLEEPING ROOM SHALL COMPLY WITH 603. WHERE
 PROVIDED, NO FEWER THAN ONE WATER CLOSET, ONE LAVATORY,
 AND ONE BATHTUB OR SHOWER SHALL COMPLY WITH THE
 APPLICABLE REQUIREMENTS OF 603 THROUGH 610.
  
 3B) PLEASE SHOW HOW COMPLIANCE WITH ACCESS. CODE
 604.3.1 WILL BE MET:
 604.3.1 SIZE. CLEARANCE AROUND A WATER CLOSET SHALL BE
 60 INCHES (1525 MM) MINIMUM MEASURED PERPENDICULAR FROM
 THE SIDE WALL AND 56 INCHES (1420 MM) MINIMUM MEASURED
 PERPENDICULAR FROM THE REAR WALL.
  
 3C) EITHER THE DESIGNER OF RECORD OR THE CONTRACTOR CAN
 PLEASE PROVIDE ON THEIR LETTERHEAD IF DISPROPORTION
 COST WERE MET AND THE WHOLE OF THE BATHROOMS WERE NOT
 ABLE TO COME INTO COMPLETE COMPLIANCE, WHAT ELEMENTS
 WERE COVERED UNDER THE 20 % DISPROPORTION COST.
  
 2017 FBC-ACCESSIBILITY CODE 202.4.2 ACCESSIBLE FEATURES
 IN THE EVENT OF DISPROPORTIONALITY. WHEN THE COST OF
 ALTERATIONS NECESSARY TO MAKE THE PATH OF TRAVEL TO THE
 ALTERED AREA FULLY ACCESSIBLE IS DISPROPORTIONATE TO
 THE COST OF THE OVERALL ALTERATION, THE PATH OF TRAVEL
 SHALL BE MADE ACCESSIBLE TO THE EXTENT THAT IT CAN BE
 MADE ACCESSIBLE WITHOUT INCURRING DISPROPORTIONATE
 COSTS. IN CHOOSING WHICH ACCESSIBLE ELEMENTS TO
 PROVIDE, PRIORITY SHOULD BE GIVEN TO THOSE ELEMENTS
 THAT WILL PROVIDE THE GREATEST ACCESS, IN THE FOLLOWING
 ORDER: (I) AN ACCESSIBLE ENTRANCE; (II) AN ACCESSIBLE
 ROUTE TO THE ALTERED AREA; (III) AT LEAST ONE
 ACCESSIBLE RESTROOM FOR EACH SEX OR A SINGLE UNISEX
 RESTROOM; (IV) ACCESSIBLE TELEPHONES; (V) ACCESSIBLE
 DRINKING FOUNTAINS; AND (VI) WHEN POSSIBLE, ADDITIONAL
 ACCESSIBLE ELEMENTS SUCH AS PARKING, STORAGE, AND
 ALARMS.
  
 4) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status N Date 2018-05-17 Cont ID  
Sent By ppetty Date 2018-05-17 Time 14:53 Rev Time 0.00
Received By ppetty Date 2018-05-17 Time 14:53 Sent To  
Notes
2018-05-17 14:55:39NO ELECTRICAL WORK REVIEWED OR APPROVED.
 PHIL PETTY

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-03-14 Cont ID  
Sent By jpearson Date 2018-03-14 Time 10:58 Rev Time 0.00
Received By jpearson Date 2018-03-14 Time 10:51 Sent To I
Notes
2018-03-14 10:56:23CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE ELECTRICAL PLAN FOR REVIEW, SIGNED AND
 SEALED BY A LICENSED DESIGN PROFESSIONAL OR THE
 ELECTRICAL CONTRACTOR QUALIFIER. IF THERE IS NOT ANY
 ELECTRICAL WORK INCLUDED WITH THIS PERMIT, STATE THAT
 ON PLAN. FS 471.003(2)(H); 471.025; FBC 107.2.1,
 107.3.5
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2018-05-15 Cont ID  
Sent By pleduc Date 2018-05-15 Time   Rev Time 0.00
Received By pleduc Date 2018-05-14 Time 15:27 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2018-02-22 Cont ID  
Sent By pleduc Date 2018-02-22 Time   Rev Time 0.00
Received By pleduc Date 2018-02-22 Time 12:57 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-05-25 Cont ID  
Sent By gjohnson Date 2018-05-25 Time 08:45 Rev Time 0.00
Received By gjohnson Date 2018-05-04 Time 13:58 Sent To  
Notes
2018-05-07 13:58:39B29

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2018-03-14 Time   Rev Time 0.00
Received By lmarchan Date 2018-02-20 Time 14:05 Sent To  
Notes
2018-02-21 14:05:18B25

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2018-02-26 Cont ID  
Sent By jwitmer Date 2018-02-26 Time 11:20 Rev Time 0.00
Received By jwitmer Date 2018-02-26 Time 09:57 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2018-03-08 Cont ID  
Sent By ccole Date 2018-03-08 Time 08:21 Rev Time 0.00
Received By ccole Date 2018-03-08 Time 08:21 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2018-05-25 Cont ID  
Sent By gjohnson Date 2018-05-25 Time 08:45 Rev Time 0.00
Received By gjohnson Date 2018-05-25 Time 06:13 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2018-03-14 Cont ID  
Sent By gjohnson Date 2018-03-14 Time 10:03 Rev Time 0.00
Received By gjohnson Date 2018-03-14 Time 07:23 Sent To  
Notes
2018-03-14 10:14:53 
 1ST REVIEW: FBC 2017 6TH EDITION
  
 PLUMBING COMMENTS:
  
 1. PLEASE SHOW COMPLIANCE WITH GRAB BARS AT THE TOILET
 PER FBC ACC
 A) 604.5.1 SIDE WALL.THE SIDE WALL GRAB BAR SHALL BE 42
 INCHES-LONG MINIMUM, LOCATED 12 INCHES MAXIMUM FROM THE
 REAR WALL AND EXTENDING 54 INCHES MINIMUM FROM THE REAR
 WALL.
 B) 604.5.2 REAR WALL. THE REAR WALL GRAB BAR SHALL BE
 36 INCHES LONG MINIMUM AND EXTEND FROM THE CENTERLINE
 OF THE WATER CLOSET 12 INCHES MINIMUM ON ONE SIDE AND
 24 INCHES MINIMUM ON THE OTHER SIDE.
 C) 609.4 POSITION OF GRAB BARS. GRAB BARS SHALL BE
 INSTALLED IN A HORIZONTAL POSITION, 33 INCHES MINIMUM
 AND 36 INCHES MAXIMUM ABOVE THE FINISH FLOOR MEASURED
 TO THE TOP OF THE GRIPPING SURFACE,
  
 COMPLY WITH BUILDINGS COMMENTS:
  
 3) THE PERMIT APPLICATION SHOWS A VALUE OF $91,420.00
 DOLLARS. THE 2017 FBC-ACCESSIBILITY CODE REQUIRES
 COMPLIANCE WITH:
 3A) 805.4 TOILET AND BATHING ROOMS. TOILET AND BATHING
 ROOMS THAT ARE PROVIDED AS PART OF A PATIENT OR
 RESIDENT SLEEPING ROOM SHALL COMPLY WITH 603. WHERE
 PROVIDED, NO FEWER THAN ONE WATER CLOSET, ONE LAVATORY,
 AND ONE BATHTUB OR SHOWER SHALL COMPLY WITH THE
 APPLICABLE REQUIREMENTS OF 603 THROUGH 610.
  
 3B) PLEASE SHOW HOW COMPLIANCE WITH ACCESS. CODE
 604.3.1 WILL BE MET:
 604.3.1 SIZE. CLEARANCE AROUND A WATER CLOSET SHALL BE
 60 INCHES (1525 MM) MINIMUM MEASURED PERPENDICULAR FROM
 THE SIDE WALL AND 56 INCHES (1420 MM) MINIMUM MEASURED
 PERPENDICULAR FROM THE REAR WALL.
  
 3C) EITHER THE DESIGNER OF RECORD OR THE CONTRACTOR CAN
 PLEASE PROVIDE ON THEIR LETTERHEAD IF DISPROPORTION
 COST WERE MET AND THE WHOLE OF THE BATHROOMS WERE NOT
 ABLE TO COME INTO COMPLETE COMPLIANCE, WHAT ELEMENTS
 WERE COVERED UNDER THE 20 % DISPROPORTION COST.
  
 2017 FBC-ACCESSIBILITY CODE 202.4.2 ACCESSIBLE FEATURES
 IN THE EVENT OF DISPROPORTIONALITY. WHEN THE COST OF
 ALTERATIONS NECESSARY TO MAKE THE PATH OF TRAVEL TO THE
 ALTERED AREA FULLY ACCESSIBLE IS DISPROPORTIONATE TO
 THE COST OF THE OVERALL ALTERATION, THE PATH OF TRAVEL
 SHALL BE MADE ACCESSIBLE TO THE EXTENT THAT IT CAN BE
 MADE ACCESSIBLE WITHOUT INCURRING DISPROPORTIONATE
 COSTS. IN CHOOSING WHICH ACCESSIBLE ELEMENTS TO
 PROVIDE, PRIORITY SHOULD BE GIVEN TO THOSE ELEMENTS
 THAT WILL PROVIDE THE GREATEST ACCESS, IN THE FOLLOWING
 ORDER: (I) AN ACCESSIBLE ENTRANCE; (II) AN ACCESSIBLE
 ROUTE TO THE ALTERED AREA; (III) AT LEAST ONE
 ACCESSIBLE RESTROOM FOR EACH SEX OR A SINGLE UNISEX
 RESTROOM; (IV) ACCESSIBLE TELEPHONES; (V) ACCESSIBLE
 DRINKING FOUNTAINS; AND (VI) WHEN POSSIBLE, ADDITIONAL
 ACCESSIBLE ELEMENTS SUCH AS PARKING, STORAGE, AND
 ALARMS.
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  