Plan Review Details - Permit 18020767
| Plan Review Stops For Permit 18020767 |
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
2018-05-02 |
Time |
|
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2018-04-20 |
Time |
11:12 |
Sent To |
|
|
| Notes |
| 2018-04-23 11:12:36 | RESUB ROUTED TO CCOLE |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
2018-04-13 |
Time |
|
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2018-03-28 |
Time |
10:41 |
Sent To |
|
|
| Notes |
| 2018-03-29 10:41:37 | RESUB OF REVISION ROUTED TO CCOLE |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
2018-02-27 |
Time |
|
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2018-02-20 |
Time |
14:15 |
Sent To |
|
|
| Notes |
| 2018-02-21 14:15:20 | REVISION ROUTED TO CCOLE |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
P |
Date |
2018-05-02 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2018-05-02 |
Time |
16:07 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2018-05-02 |
Time |
16:07 |
Sent To |
I |
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2018-04-13 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2018-04-13 |
Time |
09:49 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2018-04-13 |
Time |
09:49 |
Sent To |
I |
|
| Notes |
| 2018-04-13 09:58:03 | 2ND REVIEW FBC-2017 MECHANICAL \ | | | PERMIT #18020767 | | | 4/13/18 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) THE SUBMITTED PLAN SHEET IS A COPY OF THE REVISED | | | PLAN SHEET THAT HAS BEEN REDUCED IN SIZE, WHICH | | | INVALIDATES THE ENGINEER'S SEAL. A VALID ENGINEER'S | | | SEAL SHALL BE AN ORIGINAL FULL-SIZED 1-7/8' DIAMETER | | | SEAL WITH WET SIGNATURE- SECTIONS 61G15-23.001 AND | | | 23.002 FLORIDA ADMINISTRATIVE CODE. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2018-02-27 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2018-02-27 |
Time |
09:12 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2018-02-27 |
Time |
09:12 |
Sent To |
I |
|
| Notes |
| 2018-02-27 09:18:32 | 1ST REVIEW FBC-2014 MECHANICAL | | | PERMIT #18020767 | | | 2/27/18 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) PLEASE PROVIDE A REVISED M1 PLAN SHEET AND ANY OTHER | | | PLAN SHEETS AFFECTED BY THE CHANGE TO A LARGER FAN. | | | REVISE THE FAN SCHEDULE AND EXHAUST AND AIR BALANCE | | | CALCULATIONS ETC. ON THE M1 PLAN SHEET. | | | | | | 2) SUBMIT A FL. PRODUCT APPROVAL AND/OR A MIAMI-DADE | | | NOA FOR THE NEW ROOF CAP. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE | | | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND | | | KEEP THEM WITH THE SUBMITTALS. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|
|
|
Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved |
 |
 |