| Plan Review Stops For Permit 18020762 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2018-03-26 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2018-03-26 |
Time |
18:03 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2018-03-26 |
Time |
18:02 |
Sent To |
I |
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2018-03-15 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2018-03-15 |
Time |
07:59 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2018-03-15 |
Time |
07:16 |
Sent To |
I |
|
| Notes |
| 2018-03-15 08:24:55 | PLAN | | | REVIEW COMMENTS | | | | | | 2ND REVIEW: FBC SIXTH EDITION (2017) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) THE SPECIFICATIONS SUBMITTED ARE FOR A 24 KW KOHLER | | | GENERATOR WITH MODEL NUMBER 24 RCL. THE AMERICAST | | | GENERATOR PAD ENGINEERING DOES NOT LIST THE 24 KW | | | KOHLER, MODEL 24 RCL. SUBMIT TWO SETS OF ENGINEERING | | | AND SPECIFICATIONS THAT MATCH. FBC 107.2.1 | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2018-03-06 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2018-03-06 |
Time |
19:00 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2018-03-06 |
Time |
19:00 |
Sent To |
I |
|
| Notes |
| 2018-03-06 19:03:16 | PLAN | | | REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC SIXTH EDITION (2017) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) THE GENERATOR PAD DRAWINGS HAVE SEVERAL REFERENCES | | | TO THE FBC FIFTH EDITION (2014). THE FBC SIXTH EDITION | | | (2017) WENT INTO EFFECT ON JANUARY 1, 2018. ALL NEW | | | PERMITS APPLIED FOR ON OR AFTER THAT DATE ARE REQUIRED | | | TO COMPLY WITH AND REFERENCE THE FBC SIXTH EDITION | | | (2017). FS CHAPTER 553 | | | | | | 2) THE ENGINEER THAT IS ON THE SLAB ANCHORING PLANS, | | | RONALD H. WILSON P.E. LICENSE NO. 9710, HAS HAD HIS FL | | | ENGINEERING LICENSE REVOKED SINCE 2/28/2017. SUBMIT | | | PLANS FROM A CURRENTLY LICENSED FL ENGINEER. FS 471 | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2018-03-13 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2018-03-13 |
Time |
16:22 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2018-03-13 |
Time |
16:22 |
Sent To |
G |
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2018-03-02 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2018-03-02 |
Time |
09:58 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2018-03-02 |
Time |
09:58 |
Sent To |
|
|
| Notes |
| 2018-03-02 09:58:54 | NEED CUT SHEETS FOR TRANSFER SWITCH |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
2 |
Status |
P |
Date |
2018-03-13 |
|
|
Cont ID |
|
| Sent By |
lcrespo |
Date |
2018-03-13 |
Time |
16:56 |
Rev Time |
0.00 |
| Received By |
lcrespo |
Date |
2018-03-13 |
Time |
16:37 |
Sent To |
B |
|
| Notes |
| 2018-03-13 17:02:12 | 03/13/18 APPROVED BY GAS AND SENT TO BUILDING, LAC |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
1 |
Status |
F |
Date |
2018-02-28 |
|
|
Cont ID |
|
| Sent By |
lcrespo |
Date |
2018-02-28 |
Time |
16:14 |
Rev Time |
0.00 |
| Received By |
lcrespo |
Date |
2018-02-28 |
Time |
16:13 |
Sent To |
|
|
| Notes |
| 2018-02-28 16:17:48 | DENIED | | | | | | 1. PE PIPE UNDER CONCRETE SLAB SHALL BE ENCASED IN A | | | PROTECTIVE SLEEVE, SHOW ON THE ISOMETIC PLANS WHERE AND | | | HOW LONG FBC FG G2415.6 UNDERGROUND PENETRATIONS. | | | | | | 2. TABLES SUBMITTED ARE AND ARE NOT THE RECENTLY | | | APPROVED. THE COPY OF THE TABLE FBC FG 2009 IS FROM AN | | | OUTDATED FUEL GAS CODE. THE FUEL GAS CODE IN EFFECT IS | | | THE 2017 FBC FUEL GAS. SUBMIT TWO COPIES OF THE CORRECT | | | SIZING TABLE. WPB AMENDMENTS TO THE FBC SEC. 107.2.1. | | | | | | 3. SUBMIT A GAS PIPING RISER DIAGRAM THAT SHOWS THE | | | TYPE OF EXISTING APPLIANCE, THE BTU LOAD OF EACH | | | APPLIANCE, THE PIPE SIZE AND TYPE OF PIPE TO EACH | | | APPLIANCE, AND THE DISTANCE OF THE LONGEST LENGTH OF | | | PIPING FROM THE POINT OF DELIVERY TO THE MOST REMOTE | | | OUTLET AND THE LOAD OF THE SECTION. NOTE: IF THE | | | EXISTING SYSTEM IS LESS THAN A 2 PSI SYSTEM AND THE | | | SYSTEM PRESSURE IS INCREASED TO 2 PSI, A LINE PRESSURE | | | REGULATOR IS REQUIRED AT ALL THE EXISTING APPLIANCES | | | 2017 FBC FUEL GAS SECS. 401.4, 401.8, 402.1, 402.2, | | | 402.3 OR 2017 FBC FUEL GAS RES. SECS.G2412.4, G2412.8, | | | G2413.1, G2413.2, G2413.3. | | | | | | 4. THE MANUFACTURER'S SPECIFICATIONS FOR THE GENERATOR | | | SHALL BE ONSITE FOR FINAL GAS INSPECTION. BTU RATING ON | | | DORMANT FLEX LINE MUST NOT BE EXCEEDED. | | | | | | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS | | | TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE | | | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. | | | | | | LUIS A. CRESPO | | | PLUMBING INSPECTOR / | | | PLUMBING PLAN REVIEW | | | [email protected] | | | 561-805-6720 | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2018-03-26 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2018-03-26 |
Time |
18:03 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2018-03-23 |
Time |
13:30 |
Sent To |
|
|
| Notes |
| 2018-03-26 13:30:30 | RESUB ROUTED TO RMCDOUGAL |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2018-03-15 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2018-03-15 |
Time |
07:59 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2018-03-09 |
Time |
13:20 |
Sent To |
|
|
| Notes |
| 2018-03-12 13:20:13 | RESUB ROUTED TO JLEAHY |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2018-03-06 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2018-03-06 |
Time |
19:00 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2018-02-20 |
Time |
10:31 |
Sent To |
|
|
| Notes |
| 2018-02-21 10:31:32 | ROUTED TO ZONING INBOX |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
|
|
|
Cont ID |
|
| Sent By |
PG |
Date |
2018-02-27 |
Time |
|
Rev Time |
0.00 |
| Received By |
pgreilic |
Date |
2018-02-26 |
Time |
15:59 |
Sent To |
|
|
| Notes |
| 2018-02-27 16:57:20 | 1.) LANDSCAPE SCREENING REQUIRED | | | | | | PAUL GREILICH, SENIOR PLANNER | | | 561-822-1443 | | | [email protected] |
|
|