Plan Review Details - Permit 18020745
Plan Review Stops For Permit 18020745
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2018-09-12 Cont ID  
Sent By jgomez Date 2018-09-12 Time 12:25 Rev Time 0.00
Received By jgomez Date 2018-09-11 Time 12:41 Sent To  
Notes
2018-09-11 12:43:04 
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2018-06-13 Cont ID  
Sent By jgomez Date 2018-06-13 Time 12:43 Rev Time 0.00
Received By jgomez Date 2018-06-12 Time 18:02 Sent To  
Notes
2018-06-13 08:35:55RESIDENTIAL (R3) ADDITION, SECOND BUILDING REVIEW
 CHECKLIST.
 CODE: FBC 6TH EDITION (2017).
  
  
 ARCHITECTS-ENGINEERS
 FLORIDA STATUTE 553.80(2)(B):
 WITH RESPECT TO EVALUATION OF DESIGN PROFESSIONALS
 DOCUMENTS, IF A LOCAL GOVERNMENT FINDS IT NECESSARY, IN
 ORDER TO ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING
 CODE AND ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS
 REQUIRED BY THE CODE THREE OR MORE TIMES FOR FAILURE TO
 CORRECT A CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY
 NOTED IN EACH REJECTION, INCLUDING, BUT NOT LIMITED TO,
 EGRESS, FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY,
 ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL,
 MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER
 REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING
 COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL
 GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH
 REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION,
 A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE
 PERMIT FEE ATTRIBUTED TO PLANS REVIEW
  
  
 1- BEFORE A PERMIT TO CONSTRUCT CAN BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. UPON APPROVAL,
 ONE SET OF PLANS SHALL BE SIGNED OUT AND SUBMITTED TO
 PALM BEACH COUNTY FOR AN IMPACT FEE REVIEW. THE PLANS
 WITH THE IMPACT FEE STAMP AND A COPY OF THE PAID
 RECEIPT MUST BE RETURNED TO THE CITY BUILDING
 DEPARTMENT BEFORE THE BUILDING PERMIT CAN BE ISSUED.
 FOR INFORMATION CALL PALM BEACH COUNTY IMPACT FEES AT
 (561) 233-5025.
 NOTE: THIS MAY BE DONE LATER WHEN THE PLANS ARE
 APPROVED.
  
 2- ORIGINAL COMMENT:
 PROVIDE ENERGY CALCULATIONS (2 COPIES) AS REQUIRED BY
 SEC. 1106 FBC-EXISTING BUILDING.
  
 RESPONSE:
 A) THE BUILDING'S OWNER OR OWNER'S AUTHORIZED PERSON
 NEEDS TO CERTIFY AT THE BOTTOM OF FORM AS REQUIRED BY
 SEC. R103.1.1.2 FBC-ENERGY CONSERVATION.
  
 B) ITEM #10 OF FORM R402-2017 SUBMITTED DOESN'T COMPLY
 WITH GENERAL INSTRUCTION #1. NEED R-30 CEILING
 INSULATION. THE "TO BE INSTALLED ITEMS" MUST BE EQUAL
 TO OR MORE EFFICIENT THAN THE REQUIRED LEVELS. SEE
 TABLE R402A ON FORM SUBMITTED AND REVISE AS REQUIRED.
 NOTE: ACCORDING TO PLANS SUBMITTED R-30 BATT INSULATION
 DOESN'T FIT ON 2X10 ROOF JOISTS SPECIFIED ON PLANS.
 R-30 INSULATION IS ABOUT 9-1/2" THICK. IN ADDITION ROOF
 NEEDS AT LEAST 1 INCH CLEARANCE BETWEEN THE INSULATION
 AND ROOF DECK FOR VENTILATION. (SEC. R806.3
 FBC-RESIDENTIAL). REVISE AS REQUIRED.
  
 C) FORM R402-2017 SUBMITTED IS NOT CLEAR. LETTERING IS
 TOO SMALL AND IS NOT LEGIBLE. PROVIDE 2 LEGIBLE AND
 CLEAR COPIES. SEC. 107.2.1 CITY AMENDMENTS.
  
 3- COMPLIED.
  
 4- COMPLIED.
  
 5- COMPLIED.
  
 6- WALL SECTION A/S-1:
 A) ORIGINAL COMMENT:
 SPECIFY CONNECTOR FROM 2X6 STUDS TO BOTTOM PLATE. SEC.
 R301.1
  
 RESPONSE:
 REPEAT COMMENT. SEMI-COMPLIED. SPECIFIED CONNECTOR
 DOESN'T WORK. SIMPSON SP4 CONNECTORS ARE FOR 2X4 WALLS.
 THIS IS A 2X6 WALL. REVISE AS REQUIRED. ALSO, CLARIFY
 WHY THE DETAIL WAS REVISED TO INSTALL 2 BOTTOM PLATES
 INSTEAD OF ONE. IN ADDITION, ANY WOOD IN CONTACT WITH
 CONCRETE NEED TO BE PRESSURE TREATED OR PROVIDE
 SPECIFICATIONS HOW THE WOOD IS PROTECTED AGAINST DECAY.
 (SEC. R317 FBC-RESIDENTIAL),
  
 B) ORIGINAL COMMENT:
 SPECIFY THE 6" CLEARANCE FOR TERMITE INSPECTION AS
 REQUIRED BY SEC. R318.7 INSPECTION FOR TERMITES.
 IN ORDER TO PROVIDE FOR INSPECTION FOR TERMITE
 INFESTATION, CLEARANCE BETWEEN EXTERIOR WALL COVERINGS
 AND FINAL EARTH GRADE ON THE EXTERIOR OF A BUILDING
 SHALL NOT BE LESS THAN 6 INCHES (152 MM).
 NOTE: KEEP IN MIND THAT FOOTING NEEDS TO BE 12" BELOW
 GRADE.
  
 RESPONSE:
 REPEAT COMMENT. REVISED DRAWING IS NOT CLEAR. THE 6"
 CLEARANCE IS NOT PROVIDED. 1''-4" FOOTING CAN NOT
 PROVIDE 12" BELOW GRADE AND 6" CLEARANCE BETWEEN GRADE
 AND WALL COVERING. REVISE AS REQUIRED.
  
 C) ORIGINAL COMMENT:
 ROOF NEEDS CROSS VENTILATION AS REQUIRED BY SEC. R806.1
 FBC-RESIDENTIAL. R-19 BATT INSULATION DOESN'T FIT ON
 2X6 ROOF JOISTS. IT DOESN'T ALLOW ROOF CROSS
 VENTILATION. SEC. R806.3 FBC-RESIDENTIAL. REVISE AS
 REQUIRED INCLUDING THE ROOF FRAMING PLAN.
 NOTE: REVISE THE 2X4 BLOCKING LOCATION TO ALLOW CROSS
 VENTILATION. ALSO, COORDINATE R-VALUE WITH THE ENERGY
 CALCULATIONS TO AVOID CONFLICTS.
  
 RESPONSE:
 REPEAT COMMENT. REVISED 2 X 10 ROOF JOISTS ARE NOT
 SUITABLE FOR R-30 INSULATION AND CROSS VENTILATION. SEE
 ENERGY CALCULATIONS COMMENT # 2(B) ABOVE AND REVISE AS
 REQUIRED.
  
 D) COMPLIED.
  
 E) COMPLIED.
  
 7- COMPLIED.
  
 8- COMPLIED.
  
 9- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.001 FOR:
 A) COMPLIED.
  
 B)ORIGINAL COMMENT:
 EXTERIOR DOOR AS SHOWN ON PLANS.
  
 RESPONSE:
 SEMI-COMPLIED. ONLY THE FLORIDA PRODUCT APPROVAL
 FL13459-R5 WAS PROVIDED. NEED TO PROVIDE THE
 INSTALLATION INSTRUCTIONS DRAWINGS FOR THE DOOR TO BE
 INSTALLED.
  
 C) ORIGINAL COMMENT:
 FLAT ROOF AS SHOWN ON PLANS. AND, CLEARLY MARK WHICH
 APPROVED ASSEMBLY IS GOING TO BE INSTALLED TO VERIFY
 COMPLIANCE WITH THE DESIGN PRESSURES OF SEC. R301.1
 FBC-RESIDENTIAL. IF THE SELECTED ASSEMBLY DOESN'T MEET
 THE DESIGN PRESSURES FOR ALL ROOF ZONES, THEN SIGNED
 AND SEALED RAS 117 CALCULATIONS ARE REQUIRED. RAS 117
 CALCULATIONS ARE REQUIRED TO HAVE THE FLORIDA
 ENGINEER'S SEAL AND ORIGINAL HANDWRITTEN SIGNATURE,
 COPIES OR OTHER FACSIMILES ARE NOT ACCEPTABLE. FAC
 61G15 - 23.002 DIGITAL SIGNATURES ARE ONLY ACCEPTABLE
 FOR ELECTRONICALLY TRANSMITTED PLANS AND DOCUMENTS.
  
 RESPONSE;
 SEMI-COMPLIED. ROOF PITCH WAS CHANGED TO 3:12 PITCH.
 ROOF SHINGLES NOA 14-1022.16 SPECIFIED BY THE ENGINEER
 OF RECORD ON SHEET S-1 IS EXPIRED. REVISE INFORMATION
 ON SHEET S-1 AND PROVIDE 2 COPIES OF CURRENT SHINGLES
 PRODUCT APPROVAL.
  
 D) COMPLIED.
  
 10- COMPLIED.
  
  
 ****PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO HELP EXPEDITE THE REVIEW PROCESS.
  
 ****PLEASE INSERT ANY REVISED DRAWING AND REMOVE OLD
 DRAWING. SUBMIT OLD DRAWINGS FOR REFERENCE. DON'T
 STAPLE OLD DRAWINGS TO PLANS.
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-03-16 Cont ID  
Sent By jgomez Date 2018-03-16 Time 18:42 Rev Time 0.00
Received By jgomez Date 2018-03-16 Time 13:48 Sent To  
Notes
2018-03-16 15:57:48RESIDENTIAL (R3) ADDITION, BUILDING REVIEW COMMENTS
 CODE: FBC 6TH EDITION (2017).
  
 1- BEFORE A PERMIT TO CONSTRUCT CAN BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. UPON APPROVAL,
 ONE SET OF PLANS SHALL BE SIGNED OUT AND SUBMITTED TO
 PALM BEACH COUNTY FOR AN IMPACT FEE REVIEW. THE PLANS
 WITH THE IMPACT FEE STAMP AND A COPY OF THE PAID
 RECEIPT MUST BE RETURNED TO THE CITY BUILDING
 DEPARTMENT BEFORE THE BUILDING PERMIT CAN BE ISSUED.
 FOR INFORMATION CALL PALM BEACH COUNTY IMPACT FEES AT
 (561) 233-5025.
  
 2-PROVIDE ENERGY CALCULATIONS (2 COPIES) AS REQUIRED BY
 SEC. 1106 FBC-EXISTING BUILDING.
  
 3- THE CURRENT CODE IS THE FBC 6TH EDITION (2017) NOT
 THE FBC 5TH EDITION (2014). CHAPTER 553 FLORIDA
 STATUTE. UPDATE ALL PLANS AS REQUIRED.
  
 4- SPECIFY THE DESIGN PRESSURES FOR EXTERIOR DOORS AND
 WINDOWS. SEC. R301.2.1 FBC-RESIDENTIAL.
  
 5- EXISTING BATHROOM WINDOW WAS CLOSED TO ALLOW FOR
 ADDITION. NEED VENTILATION. FOR EXISTING BATHROOM.
 SPECIFY EXHAUST FAN AS REQUIRED BY THE EXCEPTION ON
 SEC. R303.3 FBC-RESIDENTIAL.
  
 6- WALL SECTION A/S-1:
 A) SPECIFY CONNECTOR FROM 2X6 STUDS TO BOTTOM PLATE.
 SEC. R301.1
  
 B) SPECIFY THE 6" CLEARANCE FOR TERMITE INSPECTION AS
 REQUIRED BY SEC. R318.7 INSPECTION FOR TERMITES.
 IN ORDER TO PROVIDE FOR INSPECTION FOR TERMITE
 INFESTATION, CLEARANCE BETWEEN EXTERIOR WALL COVERINGS
 AND FINAL EARTH GRADE ON THE EXTERIOR OF A BUILDING
 SHALL NOT BE LESS THAN 6 INCHES (152 MM).
 NOTE: KEEP IN MIND THAT FOOTING NEEDS TO BE 12" BELOW
 GRADE.
  
 C) ROOF NEEDS CROSS VENTILATION AS REQUIRED BY SEC.
 R806.1 FBC-RESIDENTIAL. R-19 BATT INSULATION DOESN'T
 FIT ON 2X6 ROOF JOISTS. IT DOESN'T ALLOW ROOF CROSS
 VENTILATION. SEC. R806.3 FBC-RESIDENTIAL. REVISE AS
 REQUIRED INCLUDING THE ROOF FRAMING PLAN.
 NOTE: REVISE THE 2X4 BLOCKING LOCATION TO ALLOW CROSS
 VENTILATION. ALSO, COORDINATE R-VALUE WITH THE ENERGY
 CALCULATIONS TO AVOID CONFLICTS.
  
 D) NEED TO SPECIFY THE 7/8" MIN. STUCCO THICKNESS AS
 REQUIRED BY TABLE R702.1(1).
  
 E) NEED TO SPECIFY 2 LAYERS OF WATER RESISTIVE BARRIERS
 AS REQUIRED BY SEC. R703.7.3 WATER-RESISTIVE BARRIERS.
  
 7- ROOF FRAMING PLAN ON SHEET S-1: SPECIFY ROOF PITCH
 AS REQUIRED BY SEC. R905.11.1 SLOPE.
 MODIFIED BITUMEN MEMBRANE ROOFS SHALL HAVE A DESIGN
 SLOPE OF NOT LESS THAN ONE-FOURTH UNIT VERTICAL IN 12
 UNITS HORIZONTAL (2-PERCENT SLOPE) FOR DRAINAGE
  
 8- REVISE ROOF SHEATHING NAILING INFORMATION ON SHEET
 S-1. DIMENSION FOR "Z" NEEDS TO BE 4'-0" MIN. AS
 REQUIRED BY NOTE ON FIGURE R301.2(7).
  
 9- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.001 FOR:
 A) WINDOW AS SHOWN ON PLANS.
  
 B) EXTERIOR DOOR AS SHOWN ON PLANS.
  
 C) FLAT ROOF AS SHOWN ON PLANS. AND, CLEARLY MARK WHICH
 APPROVED ASSEMBLY IS GOING TO BE INSTALLED TO VERIFY
 COMPLIANCE WITH THE DESIGN PRESSURES OF SEC. R301.1
 FBC-RESIDENTIAL. IF THE SELECTED ASSEMBLY DOESN'T MEET
 THE DESIGN PRESSURES FOR ALL ROOF ZONES, THEN SIGNED
 AND SEALED RAS 117 CALCULATIONS ARE REQUIRED. RAS 117
 CALCULATIONS ARE REQUIRED TO HAVE THE FLORIDA
 ENGINEER'S SEAL AND ORIGINAL HANDWRITTEN SIGNATURE,
 COPIES OR OTHER FACSIMILES ARE NOT ACCEPTABLE. FAC
 61G15 - 23.002 DIGITAL SIGNATURES ARE ONLY ACCEPTABLE
 FOR ELECTRONICALLY TRANSMITTED PLANS AND DOCUMENTS.
  
 D) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON PLANS
 AND DETAILS. PROVIDE ONLY THE FLORIDA PRODUCT APPROVAL
 COVER PAGE AND PAGE SHOWING THE SPECIFIED CONNECTOR OR
 DESIGN PROFESSIONAL TO LIST THE FLORIDA PRODUCT
 APPROVAL NUMBER NEXT TO EACH SPECIFIED CONNECTOR.
  
 10- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
  
 ****PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO HELP EXPEDITE THE REVIEW PROCESS.
  
 ****PLEASE INSERT ANY REVISED DRAWING AND REMOVE OLD
 DRAWING. SUBMIT OLD DRAWINGS FOR REFERENCE OF ALREADY
 REVIEWED DRAWINGS. DON?T STAPLE OLD DRAWINGS TO PLANS.
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2018-05-17 Cont ID  
Sent By ppetty Date 2018-05-17 Time 11:58 Rev Time 0.00
Received By ppetty Date 2018-05-17 Time 11:35 Sent To  
Notes
2018-05-17 11:35:48CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: OK, SEE COMMENTS BELOW.
  
 1. CORRECTED
 2. CORRECTED
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 PHIL PETTY
 ELECTRICAL PLANS EXAMINER,CHIEF ELECTRICAL INSPECTOR
 561-805-6742
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-03-16 Cont ID  
Sent By jpearson Date 2018-03-16 Time 11:15 Rev Time 0.00
Received By jpearson Date 2018-03-16 Time 09:02 Sent To  
Notes
2018-03-16 11:15:57CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. THE NEC AND FBC SPECIFIED FOR DESIGN IS NOT THE
 CURRENT CODE. PROVIDE CORRECTION. FBC PREFACE (ALSO SEE
 CURRENT CODES ABOVE)
 2. NOTE # 9 DOES NOT INCLUDE ALL AREAS REQUIRED TO HAVE
 AFCI PROTECTION: "BRANCH CIRCUITS THAT SUPPLY 120-VOLT,
 SINGLE-PHASE, 15- AND 20-AMPERE OUTLETS INSTALLED IN
 KITCHENS, FAMILY ROOMS, DINING ROOMS, LIVING ROOMS,
 PARLORS, LIBRARIES, DENS, BEDROOMS, SUN-ROOMS,
 RECREATIONS ROOMS, CLOSETS, HALLWAYS, LAUNDRY AREAS AND
 SIMILAR ROOMS OR AREAS SHALL BE AFCI PROTECTED."
 PROVIDE CORRECTION. NEC 210.12; FBC RE E3902.16
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2018-09-18 Cont ID  
Sent By jgomez Date 2018-09-18 Time 18:30 Rev Time 0.00
Received By jgomez Date 2018-09-13 Time 15:27 Sent To I
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2018-09-12 Cont ID  
Sent By jgomez Date 2018-09-12 Time 12:25 Rev Time 0.00
Received By jgomez Date 2018-09-04 Time 14:00 Sent To I
Notes
2018-09-05 14:00:12RESUB ROUTED TO JGOMEZ

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-06-13 Cont ID  
Sent By jgomez Date 2018-06-13 Time 12:53 Rev Time 0.00
Received By jgomez Date 2018-05-09 Time 14:45 Sent To I
Notes
2018-05-09 14:45:26R15

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-03-21 Cont ID  
Sent By ajones Date 2018-03-21 Time 14:10 Rev Time 0.00
Received By ajones Date 2018-02-16 Time 11:39 Sent To  
Notes
2018-02-20 11:39:58R05

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 4 Status P Date 2018-09-18 Cont ID  
Sent By jgomez Date 2018-09-18 Time 18:25 Rev Time 0.00
Received By jgomez Date 2018-09-18 Time 18:24 Sent To  
Notes
2018-09-18 18:26:06NO FEES. MU-2018-032067

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 3 Status F Date 2018-09-11 Cont ID  
Sent By jgomez Date 2018-09-11 Time 14:42 Rev Time 0.00
Received By jgomez Date 2018-09-11 Time 14:42 Sent To  
Notes
2018-09-11 14:42:58IMPACT FEES - PAPER SUBMITTALS
  
 PLANS REQUIRE REVIEW BY THE PBC IMPACT FEE OFFICE. CALL
 (561) 233-5025. UPON APPROVAL, YOU MAY CHECK OUT ONE
 PLAN SET AND TAKE TO THAT OFFICE FOR REVIEW. PLEASE
 RETURNED STAMPED AND WITH A COPY OF THE RECEIPT AS
 APPLICABLE. PLEASE PROVIDE THE MUNICIPAL IMPACT FEE
 QUESTIONNAIRE FORM TO THE PBC IMPACT FEE OFFICE. THE
 FORM CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/AD
 MINISTRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status F Date 2018-06-13 Cont ID  
Sent By jgomez Date 2018-06-13 Time 12:51 Rev Time 0.00
Received By jgomez Date 2018-06-13 Time 12:51 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2018-03-16 Cont ID  
Sent By jgomez Date 2018-03-16 Time 19:04 Rev Time 0.00
Received By jgomez Date 2018-03-16 Time 19:04 Sent To  
Notes
2018-03-16 19:04:58BEFORE A PERMIT TO CONSTRUCT CAN BE ISSUED, IMPACT FEES
 MUST BE PAID TO PALM BEACH COUNTY. UPON APPROVAL, ONE
 SET OF PLANS SHALL BE SIGNED OUT AND SUBMITTED TO PALM
 BEACH COUNTY FOR AN IMPACT FEE REVIEW. THE PLANS WITH
 THE IMPACT FEE STAMP AND A COPY OF THE PAID RECEIPT
 MUST BE RETURNED TO THE CITY BUILDING DEPARTMENT BEFORE
 THE BUILDING PERMIT CAN BE ISSUED. FOR INFORMATION CALL
 PALM BEACH COUNTY IMPACT FEES AT (561) 233-5025.
  
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2018-09-12 Cont ID  
Sent By jgomez Date 2018-09-12 Time 12:22 Rev Time 0.00
Received By jgomez Date 2018-09-12 Time 12:22 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2018-03-16 Cont ID  
Sent By jgomez Date 2018-03-16 Time 19:03 Rev Time 0.00
Received By jgomez Date 2018-03-16 Time 19:03 Sent To  
Notes
2018-03-16 19:03:44NO MECHANICAL WORK SHOWN.

Review Stop P PLUMBING
Rev No 2 Status P Date 2018-06-08 Cont ID  
Sent By lcrespo Date 2018-06-08 Time 15:26 Rev Time 0.00
Received By lcrespo Date 2018-06-08 Time 15:26 Sent To  
Notes
2018-06-08 15:27:4806/08/18 APPROVED BY PLUMBING AND PUT BACK IN R15, LAC

Review Stop P PLUMBING
Rev No 1 Status F Date 2018-03-17 Cont ID  
Sent By jgomez Date 2018-03-16 Time 18:43 Rev Time 0.00
Received By jgomez Date 2018-03-16 Time 18:43 Sent To  
Notes
2018-03-16 18:44:00RESIDENTIAL (R3) ADDITION PLUMBING REVIEW COMMENTS
 CODE: FBC 6TH EDITION (2017).
  
 1-THE CURRENT CODE IS THE FBC 6TH EDITION (2017) NOT
 THE FBC 5TH EDITION (2014). CHAPTER 553 FLORIDA
 STATUTE. UPDATE ALL NOTES ON PLANS AS REQUIRED.
  
 2- A) CLARIFY IF INSTALLING SHOWER OR BATHTUB. PLUMBING
 RISER AND DETAILS DON'T MATCH INFORMATION SHOWN ON
 PLANS. . REVISE AS REQUIRED TO MATCH. SEC. 107.2.1 CITY
 AMENDMENTS.
  
 B) IF SHOWER, THEN PROVIDE COMPLETE INFORMATION AS
 REQUIRED BY SEC. P2708.1 FBC-RESIDENTIAL.
  
 3- PLUMBING NOTES SPECIFY BROWARD COUNTY PLUMBING
 INSPECTOR. THIS IS NOT BROWARD COUNTY. REVISE AS
 REQUIRED. SEC. 107.2.1 CITY AMENDMENTS.
  
  
 ****PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO HELP EXPEDITE THE REVIEW PROCESS.
  
 ****PLEASE INSERT ANY REVISED DRAWING AND REMOVE OLD
 DRAWING. SUBMIT OLD DRAWINGS FOR REFERENCE OF ALREADY
 REVIEWED DRAWINGS. DON?T STAPLE OLD DRAWINGS TO PLANS.
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  
  
  

Review Stop R ROOF PLAN REVIEW
Rev No 3 Status P Date 2018-09-12 Cont ID  
Sent By jgomez Date 2018-09-12 Time 12:24 Rev Time 0.00
Received By jgomez Date 2018-09-12 Time 12:24 Sent To  
Notes
2018-09-12 12:25:03SHINGLES NOA 18-0123.06.

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status F Date 2018-06-13 Cont ID  
Sent By jgomez Date 2018-06-13 Time 12:52 Rev Time 0.00
Received By jgomez Date 2018-06-13 Time 12:52 Sent To  
Notes
2018-06-13 12:52:54RESPONSE;
 SEMI-COMPLIED. ROOF PITCH WAS CHANGED TO 3:12 PITCH.
 ROOF SHINGLES NOA 14-1022.16 SPECIFIED BY THE ENGINEER
 OF RECORD ON SHEET S-1 IS EXPIRED. REVISE INFORMATION
 ON SHEET S-1 AND PROVIDE 2 COPIES OF CURRENT SHINGLES
 PRODUCT APPROVAL.
  

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2018-03-16 Cont ID  
Sent By jgomez Date 2018-03-16 Time 19:05 Rev Time 0.00
Received By jgomez Date 2018-03-16 Time 19:05 Sent To  
Notes
2018-03-16 19:06:091- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.001 FOR:
 A) FLAT ROOF AS SHOWN ON PLANS. AND, CLEARLY MARK WHICH
 APPROVED ASSEMBLY IS GOING TO BE INSTALLED TO VERIFY
 COMPLIANCE WITH THE DESIGN PRESSURES OF SEC. R301.1
 FBC-RESIDENTIAL. IF THE SELECTED ASSEMBLY DOESN'T MEET
 THE DESIGN PRESSURES FOR ALL ROOF ZONES, THEN SIGNED
 AND SEALED RAS 117 CALCULATIONS ARE REQUIRED. RAS 117
 CALCULATIONS ARE REQUIRED TO HAVE THE FLORIDA
 ENGINEER'S SEAL AND ORIGINAL HANDWRITTEN SIGNATURE,
 COPIES OR OTHER FACSIMILES ARE NOT ACCEPTABLE. FAC
 61G15 - 23.002 DIGITAL SIGNATURES ARE ONLY ACCEPTABLE
 FOR ELECTRONICALLY TRANSMITTED PLANS AND DOCUMENTS.
  

Review Stop Z ZONING
Rev No 2 Status P Date   Cont ID  
Sent By mc Date 2018-05-23 Time   Rev Time 0.00
Received By   Date 2018-05-23 Time   Sent To PC
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2018-03-21 Cont ID  
Sent By AV Date 2018-03-21 Time 14:10 Rev Time 0.00
Received By ajones Date 2018-03-21 Time 14:10 Sent To I
Notes
***NONE***