Plan Review Details - Permit 18020662
Plan Review Stops For Permit 18020662
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2018-02-22 Cont ID  
Sent By aclange Date 2018-02-22 Time 13:27 Rev Time 0.00
Received By aclange Date 2018-02-22 Time 11:05 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2018-05-03 Cont ID  
Sent By jpearson Date 2018-05-03 Time 09:13 Rev Time 0.00
Received By jpearson Date 2018-05-03 Time 09:13 Sent To M
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2018-02-21 Cont ID  
Sent By jleahy Date 2018-02-21 Time 09:58 Rev Time 0.00
Received By jpearson Date 2018-02-21 Time 09:58 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2018-02-20 Cont ID  
Sent By pleduc Date 2018-02-20 Time   Rev Time 0.00
Received By pleduc Date 2018-02-20 Time 13:57 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date   Cont ID  
Sent By   Date 2018-05-10 Time   Rev Time 0.00
Received By lmarchan Date 2018-05-01 Time 11:07 Sent To  
Notes
2018-05-02 11:07:47RESUB ROUTED TO JPEARSON

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date   Cont ID  
Sent By   Date 2018-04-10 Time   Rev Time 0.00
Received By lmarchan Date 2018-04-06 Time 14:07 Sent To  
Notes
2018-04-09 14:08:07RESUB ROUTED TO CCOLE

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-04-09 Cont ID  
Sent By lmarchan Date 2018-04-09 Time 14:08 Rev Time 0.00
Received By lmarchan Date 2018-03-21 Time 15:57 Sent To  
Notes
2018-03-22 15:57:44RESUB ROUTED TO GJOHNSON

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-02-26 Cont ID  
Sent By gjohnson Date 2018-02-26 Time 11:10 Rev Time 0.00
Received By gjohnson Date 2018-02-15 Time 13:40 Sent To  
Notes
2018-02-16 13:44:35C13

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2018-05-10 Cont ID  
Sent By ccole Date 2018-05-10 Time 15:07 Rev Time 0.00
Received By ccole Date 2018-05-10 Time 15:07 Sent To I
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2018-04-10 Cont ID  
Sent By ccole Date 2018-04-10 Time 07:53 Rev Time 0.00
Received By ccole Date 2018-04-10 Time 07:14 Sent To I
Notes
2018-04-10 08:09:242ND REVIEW FBC-2014 MECHANICAL, WEST PALM BEACH
 AMENDMENTS TO THE FBC-14
 REVISION #18020662
 PERMIT #17120042
 4/10/18
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE ENGINEER OF RECORD WHO PREPARED THE ENERGY
 CALCULATIONS MUST PROVIDE HIS INK OR RAISED SEAL AND
 SIGNATURE ON THE CERTIFICATIONS PAGE #4 OF THE REVISED
 ENERGYGAUGE COMPLIANCE SUBMITTAL- SECTION C103.1.1.1.2
 FBC-14 ENERGY CONSERVATION. SEALS AND SIGNATURES ARE
 ALSO REQUIRED ON ANY AC CALCULATIONS FOR SYSTEMS
 GREATER THAN 15 TON- SECTION 105.3.1.2 WPB AMENDMENTS
 TO THE FBC.
  
 2) ADVISORY: COMMISSIONING OF THE MECHANICAL SYSTEMS IS
 REQUIRED PER SECTION C408.2 FBC-14 ENERGY CONSERVATION.
 SUBMIT A COMMISSIONING PLAN AS OUTLINED IN SECTION
 C408.2.1 AND DESCRIBED IN SECTIONS C403.2.2-
 C408.2.3.3. PLEASE NOTE THAT A COPY OF THE
 COMMISSIONING REPORT SHALL BE SUBMITTED TO THE
 OWNERSHIP, AND TO THE BUILDING DEPARTMENT FOR REVIEW AT
 FINAL INSPECTION.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2018-04-02 Cont ID  
Sent By ccole Date 2018-04-02 Time 09:55 Rev Time 0.00
Received By ccole Date 2018-04-02 Time 09:55 Sent To I
Notes
2018-04-02 10:11:092ND REVIEW FBC-2014 MECHANICAL, WEST PALM BEACH
 AMENDMENTS TO THE FBC-14
 PERMIT 318020662
 4/2/18
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE RESUBMITTED PLANS NEED TO BE BOUND TOGETHER FOR
 REVIEW PER SECTION 107.2.1.4 WPB AMENDMENTS TO THE
 FBC-17.
  
 2) COMMENTS #2B & 6 HAVE NOT BEEN ADDRESSED. I HAVE
 REPRINTED THE COMMENTS BELOW- PLEASE COMPLY:
  
 2B) PROVIDE SIZING CALCULATIONS FOR THE NEW LIEBERT AND
 MITSUBISHI SYSTEMS, AND PROVIDE EQUIPMENT SCHEDULES FOR
 THE LIEBERT SYSTEMS.
  
 6) REVISE THE ENERGY COMPLIANCE REPORT TO INCLUDE THE
 NEW SYSTEMS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2018-02-23 Cont ID  
Sent By ccole Date 2018-02-23 Time 07:43 Rev Time 0.00
Received By ccole Date 2018-02-22 Time 17:08 Sent To  
Notes
2018-02-23 08:17:151ST REVIEW FBC-2014 MECHANICAL, ENERGY CONSERVATION,
 EXISTING BUILDING CODES
 REVISION 318020662
 MASTER #17120042
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET M2.1: PLEASE PROVIDE AN ENLARGED VIEW OF THE
 NEW MDF ROOM TO HELP EXPEDITE THE REVIEW PROCESS.
  
 2) M2.1: NOTE #6 IS CONFUSING. I AM NOT SEEING DUCTWORK
 FROM THE EXISTING AC-1 AND AC-2 SYSTEMS. IT APPEARS THE
 DUCTWORK IS FROM THE NEW LIEBERT SYSTEMS.
  
 2) PROVIDE SIZING CALCULATIONS FOR THE NEW LIEBERT AND
 MITSUBISHI SYSTEMS, AND PROVIDE EQUIPMENT SCHEDULES FOR
 THE LIEBERT SYSTEMS.
  
 3) PLEASE SHOW THE LOCATIONS OF AHU'S 8, 9, & 10.
  
 4) SHEET M2.3: DUCT SMOKE DETECTORS REQUIRED IN THE
 RETURN AIR SYSTEMS OF AHU'S 3, 4, 5, & 6.
  
 5) PROVIDE COMPLETE WIND LOAD ENGINEERING FOR
 INSTALLATION OF THE NEW LIEBERT UNITS, THE MITSUBISHI
 CONDENSING UNITS, AND THE CHILLERS- SECTION 301.5.
  
 6) REVISE THE ENERGY COMPLIANCE REPORT TO INCLUDE THE
 NEW SYSTEMS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2018-03-23 Cont ID  
Sent By gjohnson Date 2018-03-23 Time 13:04 Rev Time 0.00
Received By gjohnson Date 2018-03-23 Time 13:04 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2018-02-26 Cont ID  
Sent By gjohnson Date 2018-02-26 Time 08:01 Rev Time 0.00
Received By gjohnson Date 2018-02-26 Time 08:01 Sent To  
Notes
2018-02-26 11:10:261ST REVIEW: FBC 2017 6TH EDITION
  
 PLUMBING COMMENTS:
  
 1. SHT. A4.3 THE CONFERENCE ROOM SINKS SHALL COMPLY
 WITH FBC ACC 212.3, 606.2, 606.3
  
 2. PROVIDE DETAIL FOR SINK IN OPEN AREA SHALL COMPLY
 WITH FBC ACC 212.2, 804.4, 606
  
 3. SHT. LS.1 AND A3.1 SHOWS SINKS IN CONFERENCE ROOMS
 101, 102 THOSE SINKS ARE NOT SHOWN ON THE PLUMBING
 PLANS PLEASE CLARIFY. PER WPB AMEND TO FBC 107.2.1
  
 4. THE SINKS IN THE CONFERENCE ROOMS ARE NOT SHOW ON
 PLUMBING FIXTURE SCHEDULE PLEASE CLARIFY. PER WPB AMEND
 TO FBC 107.2.1
  
 5. A BACK FLOW IS REQUIRED ON THE REF. ICE MAKER PER
 FBC PL 608.3
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  