Plan Review Details - Permit 18020636
Plan Review Stops For Permit 18020636
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status N Date 2018-02-26 Cont ID  
Sent By cthroop Date 2018-02-26 Time 14:39 Rev Time 0.00
Received By cthroop Date 2018-02-26 Time 14:36 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2018-03-16 Cont ID  
Sent By lcrespo Date 2018-03-16 Time 16:44 Rev Time 0.00
Received By lcrespo Date 2018-03-15 Time 10:56 Sent To  
Notes
2018-03-16 10:56:56RESUB ROUTED TO THUNT

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-03-09 Cont ID  
Sent By thunt Date 2018-03-09 Time 17:03 Rev Time 0.00
Received By thunt Date 2018-03-08 Time 10:58 Sent To I
Notes
2018-03-09 10:59:04RESUB ROUTED TO THUNT

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-02-26 Cont ID  
Sent By cthroop Date 2018-02-26 Time 14:39 Rev Time 0.00
Received By cthroop Date 2018-02-15 Time 13:49 Sent To I
Notes
2018-02-16 13:49:26ROUTED TO PLUMB <5K

Review Stop P PLUMBING
Rev No 3 Status P Date 2018-03-16 Cont ID  
Sent By lcrespo Date 2018-03-16 Time 16:44 Rev Time 0.00
Received By lcrespo Date 2018-03-16 Time 16:44 Sent To  
Notes
2018-03-16 16:45:2403/16/18 APPROVED AND SENT TO PROCESSING, LAC

Review Stop P PLUMBING
Rev No 2 Status F Date 2018-03-09 Cont ID  
Sent By thunt Date 2018-03-09 Time 16:45 Rev Time 0.00
Received By thunt Date 2018-03-09 Time 16:45 Sent To  
Notes
2018-03-09 17:03:0103/09/2018 PLUMBING 2ND REVIEW**DENIED**
  
 THE BUILDING WAS BUILT USING THE FAIR HOUSING DESIGN
 MANUAL IN 2006
  
 1) YOU WILL NOT BE ABLE TO REMOVE 1 SINK BASE TO
 INSTALL A DOUBLE VANITY AND COMPLY WITH THE REQUIRED
 CLEAR FLOOR SPACE FOR A SIDE APPROACH OF 30" X 48". THE
 SINK MUST REMAIN CENTERED AT A MIN 24".(FHA DESIGN
 MANUAL 7.48). IT ALSO DOES NOT COMPLY WITH FBC P
 405.3.1 AS YOUR SHOWING THE CENTER OF SINK @ 12" WHEN
 15" IS AND ALWAYS HAS BEEN THE MIN CODE.
  
 2) THE COUNTER TOP HEIGHT IS NOT EXISTING AS EXISTING
 AND FHA DESIGN MANUAL IS MAX 34" TO TOP OF RIM. ( FHA
 DESIGN MANUAL 7.52)
  
  
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2018-02-20 Cont ID  
Sent By thunt Date 2018-02-20 Time 14:44 Rev Time 0.00
Received By thunt Date 2018-02-20 Time 14:44 Sent To B
Notes
2018-02-20 14:51:4002/20/2018 PLUMBING 1ST REVIEW**DENIED**
  
 1) SHOW CLEAR FLOOR SPACING FOR THE SINKS AS REQUIRED
 BY FHA DESIGN MANUAL
  
 2) SHOW NEW CABINET HEIGHT. FBC 107.2.1
  
 3) SHOW BOTH SINK DIMENSIONS AND SPACE BETWEEN EACH
 THAT IT COMPLIES WITH FBC-P 405.3.1
  
 4) SHOW TOILET OPENING THAT IT WILL REMAIN IN HAVING
 THE REQUIRED 33" OPENING AS PER FHA DESIGN MANUAL
  
 TIM HUNT
 PLUMBING INSPECTOR / PLUMBING PLAN REVIEWER
 CITY OF WEST PALM BEACH DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 561-805-6695
 [email protected]
  