Plan Review Details - Permit 18020563
Plan Review Stops For Permit 18020563
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2018-02-23 Cont ID  
Sent By shill Date 2018-02-23 Time 12:26 Rev Time 0.00
Received By shill Date 2018-02-23 Time 12:26 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-02-17 Cont ID  
Sent By shill Date 2018-02-17 Time 13:29 Rev Time 0.00
Received By shill Date 2018-02-17 Time 13:29 Sent To  
Notes
2018-02-17 13:41:31****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 1. PRODUCT APPROVAL IS INCOMPLETE. ALL PAGES WHICH
 APPLY TO ALL ASSEMBLIES SHOULD BE INCLUDED. THE PAGES
 APPLICABLE TO THE ASSEMBLY SHOULD BE INCLUDED. THE
 DESIGN PRESSURES FOR B, OPEN WERE PROVIDED, THIS
 PROJECT IS C, ENCLOSED.
  
 2. EXPOSURE B IS APPLICABLE WHEN THERE ARE SINGLE
 FAMILY SIZED DWELLINGS IN THE UPWIND DIRECTION FOR 1200
 FEET MINIMUM, WHICH IS NOT THE CASE FOR THIS STRUCTURE,
 PLEASE SEE AERIAL AND CHANGE EXPOSURE TO C OR CONTACT
 ME TO DISCUSS, FBC B 1609.
  
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-02-17 Cont ID  
Sent By shill Date 2018-02-17 Time 13:41 Rev Time 0.00
Received By shill Date 2018-02-13 Time 09:17 Sent To  
Notes
2018-02-14 09:17:46SHILL