Plan Review Details - Permit 18020559
Plan Review Stops For Permit 18020559
Review Stop B BUILDING (STRUCTURAL)
Rev No 7 Status P Date 2018-09-27 Cont ID  
Sent By dbattles Date 2018-09-27 Time 08:34 Rev Time 0.00
Received By dbattles Date 2018-09-27 Time 08:34 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2018-09-12 Cont ID  
Sent By dbattles Date 2018-09-12 Time 13:42 Rev Time 0.00
Received By dbattles Date 2018-09-12 Time 12:23 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status F Date 2018-07-20 Cont ID  
Sent By dbattles Date 2018-07-20 Time 08:43 Rev Time 0.00
Received By dbattles Date 2018-07-20 Time 07:51 Sent To  
Notes
2018-07-20 09:11:417/23/18 CONTRACTOR WILL ADDRESS PLUMBING AND SUBMIT NEW
 SHEETS INCLUDING A-4 THAT WAS MISSING FORM THE SECOND
 SET OF PLANS.
 MECHANICAL SHEET WAS INSERTED AND IT WILL GET
 RE-STAMPED.
  
 THIS WILL BE APPROVED, BUT WHEN I WAS STAMPING THE
 SECOND SET I NOTICED SHEET A-4 AND M-1 WERE MISSING
 FROM THE SET.
 I CHECKED VOIDS AND THEY ARE NOT IN THERE.
 DB CALLED CONTRACTOR AT 9:00 AM 7/20/18 AND HE WILL BE
 BRINGING THEM IN.

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2018-06-14 Cont ID  
Sent By rmcdouga Date 2018-06-14 Time 14:31 Rev Time 0.00
Received By rmcdouga Date 2018-06-13 Time 17:32 Sent To  
Notes
2018-06-13 18:10:17PLAN
 REVIEW COMMENTS
  
 4TH REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1A) THE RESPONSE LETTER FROM THE ARCHITECT (DESIGNER OF
 RECORD) ONLY ADDRESSES THE ADDITION TO THE EXISTING
 SINGLE FAMILY DWELLING AND THE SITE PLAN ON SHEET A-1
 HAS A NOTE THAT STATES THAT THE WORK AREA FOR THIS
 PERMIT IS THE MASTER BEDROOM AND OPEN PORCH ADDITION.
 HOWEVER, THE PLANS STILL HAVE THE STORAGE BUILDING
 SHOWN ON THEM. PLEASE CLARIFY. FBC 107.2.1 IF THE
 STORAGE BUILDING IS NOT PART OF THIS PERMIT, ALL
 DRAWINGS AND NOTES THAT PERTAIN TO IT NEED TO BE
 REMOVED FROM THE PLANS OR CROSSED OUT BY THE DESIGNER
 OF RECORD.
  
 1) (PARTIAL COMPLIANCE. ASCE 7-16-2018 IS SPECIFIED ON
 THE PLANS. THE 2016 EDITION OF ASCE 7 HAS NOT BEEN
 ADOPTED INTO THE 2017 FLORIDA BUILDING CODE (SIXTH
 EDITION). ASCE 7 - 10 IS THE EDITION THAT IS REFERENCED
 IN THE 2017 FBC. FBC-R CHAPTER 46 REFERENCED STANDARDS.
 PLEASE REVISE PLANS ACCORDINGLY.) FBC 107.3.5.3 -
 PROVIDE WIND DESIGN CRITERIA. (THE COMPONENT AND
 CLADDING PRESSURES FOR THE ROOF AND WALLS ON SHEET A-2
 ARE NOT CORRECT.) SPECIFY THE COMPONENT AND CLADDING
 DESIGN PRESSURES PURSUANT TO FBC-R301.2.1 ( THE ROOF
 SHEATHING FASTENERS ARE SPECIFIED AS RSRS 01. NAILS.
 CLARIFY.) SPECIFY THE ROOF SHEATHING FASTENING PER
 FBC-R803.2.3.1 (COMPLIED.) SPECIFY THE CODE EDITION AND
 THE LEVEL OF ALTERATION FOR THE ADDITION ON THE PLANS.)
  
 2) FBC ENERGY CONSERVATION - SECT. R103.1.1.2 CODE
 COMPLIANCE CERTIFICATION. THE BUILDING'S OWNER, THE
 OWNER'S ARCHITECT, OR OTHER AUTHORIZED AGENT LEGALLY
 DESIGNATED BY THE OWNER SHALL CERTIFY THAT THE BUILDING
 IS IN COMPLIANCE WITH THE CODE, AS PER SECTION 553.907,
 FLORIDA STATUTES, PRIOR TO RECEIVING THE PERMIT TO
 BEGIN CONSTRUCTION OR RENOVATION. FBC ENERGY
 CONSERVATION SECTIONS R101.5.1.1.1 OR R101.5.1.1.2.
 SUBMIT TWO SETS OF ENERGY COMPLIANCE FORMS AS REQUIRED.
 (ONE SET IS REQUIRED FOR THE ADDITION TO THE EXISTING
 DWELLING AND ANOTHER SET IS REQUIRED FOR THE NEW
 STORAGE BUILDING.)
  
 3) COMPLIED.
  
 4) COMPLIED. NO HEATING OR COOLING WAS SPECIFIED FOR
 THE NEW STORAGE STRUCTURE, WHICH SHALL NOT BE USED AS
 HABITABLE SPACE.
  
 5) COMPLIED.
  
 6) COMPLIED.
  
 7) ( SPECIFY THE SIZE AND SPACING OF THE VERTICAL
 REINFORCING FOR THE PARAPET.) PROVIDE STRUCTURAL
 CONSTRUCTION DETAILS FOR THE PARAPETS ON THE PLANS.
 FBC-R301.1
  
 8) PROVIDE STRUCTURAL CONSTRUCTION DETAILS FOR THE
 BEAMS AT THE PROPOSED COVERED PORCH ON THE PLANS.
 FBC-R301.1
  
 9) (SPECIFY THE FASTENER TYPE, SPACING AND EMBED DEPTH
 OF THE FASTENERS THAT WILL ATTACH THE LEDGERS.) PROVIDE
 STRUCTURAL DETAILS FOR THE WALL LEDGERS FOR THE ROOF
 RAFTERS AT THE PROPOSED PORCH AND MASTER BEDROOM
 ADDITION. FBC-R301.1
  
 10) COMPLIED.
  
 11) PROVIDE WINDOW AND DOOR BUCK DETAILS ON THE PLANS.
 FBC-R609.7.2.1
  
 12) (THE ROOF SCUPPERS ARE REQUIRED TO BE LEVEL WITH
 THE ROOF SURFACE. FBC 1503.4.2 ONLY THE OVERFLOW
 SCUPPERS ARE SHOWN AT 4" ABOVE THE ROOF SURFACE ON THE
 PLANS. NO CALCULATIONS ARE PROVIDED.) SPECIFY THE SIZES
 OF THE ROOF SCUPPERS ON THE PLANS AND PROVIDE ROOF
 SCUPPER SIZING CALCULATIONS. FBC-R903.4 & FBC 107.2.1.3
  
 13) SPECIFY THE SIZE AND LOCATION OF THE OVERFLOW
 SCUPPERS ON THE PLANS. FBC-R903.4
  
 14) SHOW COMPLIANCE WITH FBC-R318.5 FOR SCUPPER
 COLLECTORS AND DOWNSPOUTS THAT DISCHARGE AT LEAST ONE
 FOOT FROM THE STRUCTURE WALLS.
  
 15) COMPLIED.
  
 16) COMPLIED.
  
 17) COMPLIED.
  
 18) COMPLIED.
  
 19) COMPLIED.
  
 20) COMPLIED.
  
 21) COMPLIED.
  
 22) COMPLIED.
  
 23) IN ORDER TO REDUCE PLAN REVIEW TIME, PLEASE SUBMIT
 A RESPONSE LETTER INDICATING HOW EACH OF THE REVIEW
 COMMENTS HAS BEEN ADDRESSED. NOTE: DUE TO THE
 INFORMATION THAT IS MISSING FROM THE CONSTRUCTION
 DOCUMENTS ADDITIONAL COMMENTS MAY RESULT.
  
 24) NEW COMMENT. THE ROOF SLOPE IS SPECIFIED AS 1/8" ON
 THE PLANS. FBC - R905.11.1 REQUIRES A MINIMUM SLOPE OF
 1/4" PER FOOT FOR A BUILT UP ROOF ON NEW CONSTRUCTION.
  
 25) NEW COMMENT. AN 8X8 COLUMN WITH ONE #5 VERTICAL BAR
 IS SHOWN ON SHEET A-2 AT THE COVERED PORCH. CLARIFY.
 FBC-R301.1
  
 26) NEW COMMENT. THE COLUMN PAD NOTE ON SHEET A-2
 APPEARS TO HAVE A TYPO. IS THIS MEET TO BE #4S AT 6"
 O.C. E.W. (EACH WAY) RATHER THAN E.A.
  
 27) NEW COMMENT. ON OF THE DOWN SPOUTS FOR THE ROOF
 SCUPPERS IS SHOWN ON SHEET A-3 AT THE OPEN AREA OF THE
 COVER PORCH. FBC 107.2.1
  
 28) NEW COMMENT. SEE R STOP FOR ROOFING MATERIALS
 COMMENTS.
  
 29) FLORIDA STATUTE 553.80(2)(B) STATES THAT IF A LOCAL
 GOVERNMENT FINDS IT NECESSARY, IN ORDER TO ENFORCE
 COMPLIANCE WITH THE FLORIDA BUILDING CODE AND ISSUE A
 PERMIT, TO REJECT DESIGN DOCUMENTS REQUIRED BY THE CODE
 THREE OR MORE TIMES FOR FAILURE TO CORRECT A CODE
 VIOLATION SPECIFICALLY AND CONTINUOUSLY NOTED IN EACH
 REJECTION, INCLUDING, BUT NOT LIMITED TO, EGRESS, FIRE
 PROTECTION, STRUCTURAL STABILITY, ENERGY,
 ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL,
 MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER
 REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING
 COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL
 GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH
 REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION A
 FEE OF FOUR TIMES THE AMOUNT OF THE PORTION OF THE FEE
 ATTRIBUTED TO PLAN REVIEW.
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2018-04-20 Cont ID  
Sent By shill Date 2018-04-20 Time 17:47 Rev Time 0.00
Received By shill Date 2018-04-20 Time 17:29 Sent To  
Notes
2018-04-20 17:48:12****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 DENIED BY BUILDING - ONE SET OF PLANS HAVE A DATE OF
 2/1/18, THE OTHER SET HAS A DATE OF 4/4/18, APPEAR THE
 SAME, COMMENTS NOT ADDRESSED (SAME PLANS SUBMITTED AS
 PREVIOUS REVIEWS)
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) FBC 107.3.5.3 - PROVIDE WIND DESIGN CRITERIA.
 SPECIFY THE COMPONENT AND CLADDING DESIGN PRESSURES
 PURSUANT TO FBC-R301.2.1 SPECIFY THE ROOF SHEATHING
 FASTENING PER FBC-R803.2.3.1 (SPECIFY THE CODE EDITION
 AND THE LEVEL OF ALTERATION FOR THE ADDITION ON THE
 PLANS.)
  
 2ND REVIEW - WIND DESIGN CRITERIA SHOULD INCLUDE
 EXPOSURE CLASSIFICATION (MINIMUM EXPOSURE C).
  
 2-6) OK
  
 7) PROVIDE STRUCTURAL CONSTRUCTION DETAILS FOR THE
 PARAPETS ON THE PLANS. FBC-R301.1
  
 8) PROVIDE STRUCTURAL CONSTRUCTION DETAILS FOR THE
 BEAMS AT THE PROPOSED COVERED PORCH ON THE PLANS.
 FBC-R301.1
  
 9) PROVIDE STRUCTURAL DETAILS FOR THE WALL LEDGERS FOR
 THE ROOF RAFTERS AT THE PROPOSED PORCH AND MASTER
 BEDROOM ADDITION. FBC-R301.1
  
 10) SPECIFY THE STRUCTURAL CONNECTORS THAT WILL BE USED
 TO ANCHOR THE ROOF RAFTERS FOR THE ADDITION AND THE NEW
 CABANA BUILDING. PROVIDE A ROOF CONNECTOR SCHEDULE ON
 THE PLANS. FBC-R301.1
  
 11) PROVIDE WINDOW AND DOOR BUCK DETAILS ON THE PLANS.
 FBC-R609.7.2.1
  
 12) SPECIFY THE SIZES OF THE ROOF SCUPPERS ON THE PLANS
 AND PROVIDE ROOF SCUPPER SIZING CALCULATIONS.
 FBC-R903.4 & FBC 107.2.1.3
  
 13) SPECIFY THE SIZE AND LOCATION OF THE OVERFLOW
 SCUPPERS ON THE PLANS. FBC-R903.4
  
 14) SHOW COMPLIANCE WITH FBC-R318.5 FOR SCUPPER
 COLLECTORS AND DOWNSPOUTS THAT DISCHAGE AT LEAST ONE
 FOOT FROM THE STRUCTURE WALLS.
  
 15) SHOW THE DOOR AND WINDOW LINTELS AND PROVIDE A
 LINTEL SCHEDULE ON THE PLANS. PROVIDE A DROP BEAM
 DETAIL FOR THE POURED TIE BEAM IF THIS METHOD IS USED
 RATHER THAN LINTELS. FBC-R606.10
  
 16) COMPLIED.
  
 17) COMPLIED.
  
 18) COMPLIED.
  
 19) COMPLIED.
  
 20) COMPLIED.
  
 21) SPECIFY THE SIZE AND LOCATIONS OF THE WATER HEATERS
 FOR BOTH THE MAIN HOUSE AND THE STORAGE BUILDING ON THE
 PLANS. FBC-R306.4
  
 22) IN ORDER TO VERIFY THE VALUATION OF THIS PROJECT,
 PROVIDE A COPY OF THE SIGNED CONTRACT. FBC 109.3
 BUILDING PERMIT VALUATION. FOR PERMITTING PURPOSES,
 VALUATION OF BUILDINGS AND SYSTEMS SHALL BE TOTAL
 REPLACEMENT VALUE TO INCLUDE STRUCTURAL, ELECTRIC,
 PLUMBING, MECHANICAL, INTERIOR FINISH, RELATIVE SITE
 WORK, ARCHITECTURAL AND DESIGN FEES, MARKETING COSTS,
 OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE.
 VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED
 DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES
 (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY
 INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT
 VALUATION SHALL BE SET BY THE BUILDING OFFICIAL. THE
 CONTRACT THAT WAS SUBMITTED INCLUDES A POOL AND SPA
 THAT REQUIRES A SEPARATE PERMIT. PROVIDE THE VALUE OF
 THE POOL AND SPA, SO THAT IT CAN BE DEDUCTED FROM THE
 CONTRACT VALUE.
  
 23) IN ORDER TO REDUCE PLAN REVIEW TIME, PLEASE SUBMIT
 A RESPONSE LETTER INDICATING HOW EACH OF THE REVIEW
 COMMENTS HAS BEEN ADDRESSED. NOTE: DUE TO THE
 INFORMATION THAT IS MISSING FROM THE CONSTRUCTION
 DOCUMENTS ADDITIONAL COMMENTS MAY RESULT.
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2018-04-04 Cont ID  
Sent By rmcdouga Date 2018-04-04 Time 18:34 Rev Time 0.00
Received By rmcdouga Date 2018-04-04 Time 17:26 Sent To  
Notes
2018-04-04 18:34:41PLAN
 REVIEW COMMENTS
  
 2ND REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) FBC 107.3.5.3 - PROVIDE WIND DESIGN CRITERIA.
 SPECIFY THE COMPONENT AND CLADDING DESIGN PRESSURES
 PURSUANT TO FBC-R301.2.1 SPECIFY THE ROOF SHEATHING
 FASTENING PER FBC-R803.2.3.1 (SPECIFY THE CODE EDITION
 AND THE LEVEL OF ALTERATION FOR THE ADDITION ON THE
 PLANS.)
  
 2) FBC ENERGY CONSERVATION - SECT. R103.1.1.2 CODE
 COMPLIANCE CERTIFICATION. THE BUILDING'S OWNER, THE
 OWNER'S ARCHITECT, OR OTHER AUTHORIZED AGENT LEGALLY
 DESIGNATED BY THE OWNER SHALL CERTIFY THAT THE BUILDING
 IS IN COMPLIANCE WITH THE CODE, AS PER SECTION 553.907,
 FLORIDA STATUTES, PRIOR TO RECEIVING THE PERMIT TO
 BEGIN CONSTRUCTION OR RENOVATION. FBC ENERGY
 CONSERVATION SECTIONS R101.5.1.1.1 OR R101.5.1.1.2.
 SUBMIT TWO SETS OF ENERGY COMPLIANCE FORMS AS REQUIRED.
 (ONE SET IS REQUIRED FOR THE ADDITION TO THE EXISTING
 DWELLING AND ANOTHER SET IS REQUIRED FOR THE NEW
 STORAGE BUILDING.)
  
 3) COMPLIED.
  
 4) COMPLIED. NO HEATING OR COOLING WAS SPECIFIED FOR
 THE NEW STORAGE STRUCTURE, WHICH SHALL NOT BE USED AS
 HABITABLE SPACE.
  
 5) COMPLIED.
  
 6) COMPLIED.
  
 7) PROVIDE STRUCTURAL CONSTRUCTION DETAILS FOR THE
 PARAPETS ON THE PLANS. FBC-R301.1
  
 8) PROVIDE STRUCTURAL CONSTRUCTION DETAILS FOR THE
 BEAMS AT THE PROPOSED COVERED PORCH ON THE PLANS.
 FBC-R301.1
  
 9) PROVIDE STRUCTURAL DETAILS FOR THE WALL LEDGERS FOR
 THE ROOF RAFTERS AT THE PROPOSED PORCH AND MASTER
 BEDROOM ADDITION. FBC-R301.1
  
 10) SPECIFY THE STRUCTURAL CONNECTORS THAT WILL BE USED
 TO ANCHOR THE ROOF RAFTERS FOR THE ADDITION AND THE NEW
 CABANA BUILDING. PROVIDE A ROOF CONNECTOR SCHEDULE ON
 THE PLANS. FBC-R301.1
  
 11) PROVIDE WINDOW AND DOOR BUCK DETAILS ON THE PLANS.
 FBC-R609.7.2.1
  
 12) SPECIFY THE SIZES OF THE ROOF SCUPPERS ON THE PLANS
 AND PROVIDE ROOF SCUPPER SIZING CALCULATIONS.
 FBC-R903.4 & FBC 107.2.1.3
  
 13) SPECIFY THE SIZE AND LOCATION OF THE OVERFLOW
 SCUPPERS ON THE PLANS. FBC-R903.4
  
 14) SHOW COMPLIANCE WITH FBC-R318.5 FOR SCUPPER
 COLLECTORS AND DOWNSPOUTS THAT DISCHAGE AT LEAST ONE
 FOOT FROM THE STRUCTURE WALLS.
  
 15) SHOW THE DOOR AND WINDOW LINTELS AND PROVIDE A
 LINTEL SCHEDULE ON THE PLANS. PROVIDE A DROP BEAM
 DETAIL FOR THE POURED TIE BEAM IF THIS METHOD IS USED
 RATHER THAN LINTELS. FBC-R606.10
  
 16) COMPLIED.
  
 17) COMPLIED.
  
 18) COMPLIED.
  
 19) COMPLIED.
  
 20) COMPLIED.
  
 21) SPECIFY THE SIZE AND LOCATIONS OF THE WATER HEATERS
 FOR BOTH THE MAIN HOUSE AND THE STORAGE BUILDING ON THE
 PLANS. FBC-R306.4
  
 22) IN ORDER TO VERIFY THE VALUATION OF THIS PROJECT,
 PROVIDE A COPY OF THE SIGNED CONTRACT. FBC 109.3
 BUILDING PERMIT VALUATION. FOR PERMITTING PURPOSES,
 VALUATION OF BUILDINGS AND SYSTEMS SHALL BE TOTAL
 REPLACEMENT VALUE TO INCLUDE STRUCTURAL, ELECTRIC,
 PLUMBING, MECHANICAL, INTERIOR FINISH, RELATIVE SITE
 WORK, ARCHITECTURAL AND DESIGN FEES, MARKETING COSTS,
 OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE.
 VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED
 DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES
 (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY
 INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT
 VALUATION SHALL BE SET BY THE BUILDING OFFICIAL. THE
 CONTRACT THAT WAS SUBMITTED INCLUDES A POOL AND SPA
 THAT REQUIRES A SEPARATE PERMIT. PROVIDE THE VALUE OF
 THE POOL AND SPA, SO THAT IT CAN BE DEDUCTED FROM THE
 CONTRACT VALUE.
  
 23) IN ORDER TO REDUCE PLAN REVIEW TIME, PLEASE SUBMIT
 A RESPONSE LETTER INDICATING HOW EACH OF THE REVIEW
 COMMENTS HAS BEEN ADDRESSED. NOTE: DUE TO THE
 INFORMATION THAT IS MISSING FROM THE CONSTRUCTION
 DOCUMENTS ADDITIONAL COMMENTS MAY RESULT.
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-03-20 Cont ID  
Sent By rmcdouga Date 2018-03-20 Time 19:08 Rev Time 0.00
Received By rmcdouga Date 2018-03-19 Time 18:45 Sent To I
Notes
2018-03-20 15:23:03PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) FBC 107.3.5.3 - PROVIDE WIND DESIGN CRITERIA.
 SPECIFY THE COMPONENT AND CLADDING DESIGN PRESSURES
 PURSUANT TO FBC-R301.2.1 SPECIFY THE ROOF SHEATHING
 FASTENING PER FBC-R803.2.3.1
  
 2) FBC ENERGY CONSERVATION - SECT. R103.1.1.2 CODE
 COMPLIANCE CERTIFICATION. THE BUILDING'S OWNER, THE
 OWNER'S ARCHITECT, OR OTHER AUTHORIZED AGENT LEGALLY
 DESIGNATED BY THE OWNER SHALL CERTIFY THAT THE BUILDING
 IS IN COMPLIANCE WITH THE CODE, AS PER SECTION 553.907,
 FLORIDA STATUTES, PRIOR TO RECEIVING THE PERMIT TO
 BEGIN CONSTRUCTION OR RENOVATION. FBC ENERGY
 CONSERVATION SECTIONS R101.5.1.1.1 OR R101.5.1.1.2.
 SUBMIT TWO SETS OF ENERGY COMPLIANCE FORMS AS REQUIRED.
  
 3) SHOW THAT THE ADDITION IS IN COMPLIANCE WITH
 FBC-R303.9 REQUIRED HEATING. WHEN THE WINTER DESIGN
 TEMPERATURE IN TABLE R301.2(1) IS BELOW 60 DEGREES F ,
 EVERY DWELLING UNIT SHALL BE PROVIDED WITH HEATING
 FACILITIES CAPABLE OF MAINTAINING A MINIMUM ROOM
 TEMPERATURE OF 68 DEGREES F AT A POINT 3 FEET (914 MM)
 ABOVE THE FLOOR AND 2 FEET (610 MM) FROM EXTERIOR WALLS
 IN ALL HABITABLE ROOMS AT THE DESIGN TEMPERATURE. THE
 INSTALLATION OF ONE OR MORE PORTABLE SPACE HEATERS
 SHALL NOT BE USED TO ACHIEVE COMPLIANCE WITH THIS
 SECTION.
  
 4) FBC - 107.3.5.3 PROVIDE TWO SETS OF A MECHANICAL
 PLAN TO SHOW EQUIPMENT AND LOCATION AND DUCT SYSTEMS
 PER FBC-R M16 & BATH EXHAUST PER FBC-R M15.
  
 5) FBC-R - M1401.3 SIZING. HEATING AND COOLING
 EQUIPMENT SHALL BE SIZED BASED ON BUILDING LOADS
 CALCULATED IN ACCORDANCE WITH ACCA MANUAL J OR OTHER
 APPROVED HEATING AND COOLING CALCULATION METHODOLOGIES.
 PROVIDE EQUIPMENT SIZING CALCULATIONS.
  
 6) THE CABANA APPEARS TO HAVE A BEDROOM WITH A CEILING
 FAN AND A CLOSET, HOWEVER, IT IS MARKED AS STORAGE ON
 THE PLANS. PLEASE CLARIFY. IF THIS IS TO BE USED AS
 STORAGE THEN IT CAN NOT BE USED AS HABITABLE SPACE. IT
 WILL NEED TO BE SPECIFIED AS A STORAGE BUILDING RATHER
 THAN A CABANA ON THE PLANS AND THE PERMIT APPLICATION
 THIS AREA WILL NEED TO BE "BOLDLY" LABELED NOT TO BE
 USED AS HABITABLE SPACE ON THE PLANS. IF IT IS
 DETERMINED THAT THE STORAGE BUILDING IS BEING USED FOR
 OTHER THAN STORAGE IN THE FUTURE, YOU MAY BE SUBJECT TO
 BEING FINED AND WILL BE REQUIRED TO OBTAIN A BUILDING
 PERMIT IN ORDER TO HAVE A CHANGE OF USE FROM STORAGE TO
 HABITABLE SPACE. NEW PLANS AND AN IMPACT FEE REVIEW
 WILL BE REQUIRED. FBC105.1
  
 7) PROVIDE STRUCTURAL CONSTRUCTION DETAILS FOR THE
 PARAPETS ON THE PLANS. FBC-R301.1
  
 8) PROVIDE STRUCTURAL CONSTRUCTION DETAILS FOR THE
 BEAMS AT THE PROPOSED COVERED PORCH ON THE PLANS.
 FBC-R301.1
  
 9) PROVIDE STRUCTURAL DETAILS FOR THE WALL LEDGERS FOR
 THE ROOF RAFTERS AT THE PROPOSED PORCH AND MASTER
 BEDROOM ADDITION. FBC-R301.1
  
 10) SPECIFY THE STRUCTURAL CONNECTORS THAT WILL BE USED
 TO ANCHOR THE ROOF RAFTERS FOR THE ADDITION AND THE NEW
 CABANA BUILDING. PROVIDE A ROOF CONNECTOR SCHEDULE ON
 THE PLANS. FBC-R301.1
  
 11) PROVIDE WINDOW AND DOOR BUCK DETAILS ON THE PLANS.
 FBC-R609.7.2.1
  
 12) SPECIFY THE SIZES OF THE ROOF SCUPPERS ON THE PLANS
 AND PROVIDE ROOF SCUPPER SIZING CALCULATIONS.
 FBC-R903.4 & FBC 107.2.1.3
  
 13) SPECIFY THE SIZE AND LOCATION OF THE OVERFLOW
 SCUPPERS ON THE PLANS. FBC-R903.4
  
 14) SHOW COMPLIANCE WITH FBC-R318.5 FOR SCUPPER
 COLLECTORS AND DOWNSPOUTS THAT DISCHAGE AT LEAST ONE
 FOOT FROM THE STRUCTURE WALLS.
  
 15) SHOW THE DOOR AND WINDOW LINTELS AND PROVIDE A
 LINTEL SCHEDULE ON THE PLANS. PROVIDE A DROP BEAM
 DETAIL FOR THE POURED TIE BEAM IF THIS METHOD IS USED
 RATHER THAN LINTELS. FBC-R606.10
  
 16) FBC 107.3.4 - PROVIDE TWO SETS OF PRODUCT APPROVALS
 FOR THOSE PRODUCTS WHICH ARE REGULATED BY FAC
 61G20-3.001 PER FLORIDA STATUTE 553.842 (5) THAT HAVE
 BEEN REVIEWED AND APPROVED IN WRITING BY THE DESIGNER
 OF RECORD. PROVIDE TWO COMPLETE PRODUCT APPROVALS WITH
 FL OR NOA NUMBERS INCLUDING INSTALLATION INSTRUCTIONS
 AND MAXIMUM DESIGN PRESSURES FOR THE ROOFING MATERIALS,
 WINDOW TYPES AND EXTERIOR DOOR TYPES.
  
 17) THE DOOR SCHEDULE ON THE PLAN SPECIFIES FRENCH
 DOORS. THE DOORS ON THE FLOOR PLANS ARE DRAWN AS
 SLIDING GLASS DOORS AND PRODUCT APPROVALS WERE
 SUBMITTED FOR VINYL SLIDING GLASS DOORS. CLARIFY WHICH
 DOORS ARE BEING INSTALLED AND CORRECT THE PLANS
 ACCORDINGLY. FBC 107.2.1
  
 18) CLARIFY IF THE FRENCH DOORS #1 AND #2 IN THE
 SCHEDULE ARE A PAIR OF 3'-0" X 6'-8" AND IF SO INDICATE
 ON THE PLANS. ALSO, SHOW WHETHER THE DOORS ARE
 OUT-SWING OR IN-SWING ON THE PLANS. FBC 107.2.1
  
 19) PRODUCT APPROVALS WERE SUBMITTED FOR BOTH ALUMINUM
 AND PVC SINGLE HUNG WINDOWS. THE WINDOW SCHEDULE
 SPECIFIES ALUMINUM WINDOWS. CLARIFY. FBC 107.2.1
  
 20) THE PRODUCT APPROVAL DRAWINGS FOR THE ALUMINUM
 SINGLE HUNG WINDOWS THAT WERE SUBMITTED WERE NOT SHRUNK
 TO FIT ON 8-1/2" X 11" PAPER AND THEREFORE ARE MISSING
 INFORMATION. SUBMIT TWO SETS OF DRAWINGS THAT ARE
 COMPLETE. FBC 107.2.1.3
  
 21) SPECIFY THE SIZE AND LOCATIONS OF THE WATER HEATERS
 FOR BOTH THE MAIN HOUSE AND THE STORAGE BUILDING ON THE
 PLANS. FBC-R306.4
  
 22) IN ORDER TO VERIFY THE VALUATION OF THIS PROJECT,
 PROVIDE A COPY OF THE SIGNED CONTRACT. FBC 109.3
 BUILDING PERMIT VALUATION. FOR PERMITTING PURPOSES,
 VALUATION OF BUILDINGS AND SYSTEMS SHALL BE TOTAL
 REPLACEMENT VALUE TO INCLUDE STRUCTURAL, ELECTRIC,
 PLUMBING, MECHANICAL, INTERIOR FINISH, RELATIVE SITE
 WORK, ARCHITECTURAL AND DESIGN FEES, MARKETING COSTS,
 OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE.
 VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED
 DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES
 (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY
 INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT
 VALUATION SHALL BE SET BY THE BUILDING OFFICIAL.
  
 23) IN ORDER TO REDUCE PLAN REVIEW TIME, PLEASE SUBMIT
 A RESPONSE LETTER INDICATING HOW EACH OF THE REVIEW
 COMMENTS HAS BEEN ADDRESSED. NOTE: DUE TO THE
 INFORMATION THAT IS MISSING FROM THE CONSTRUCTION
 DOCUMENTS ADDITIONAL COMMENTS MAY RESULT.
  
  
  

Review Stop E ELECTRICAL
Rev No 6 Status P Date 2018-09-27 Cont ID  
Sent By ppetty Date 2018-09-27 Time 13:45 Rev Time 0.00
Received By ppetty Date 2018-09-27 Time 13:45 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 5 Status F Date 2018-08-28 Cont ID  
Sent By ppetty Date 2018-08-28 Time 11:12 Rev Time 0.00
Received By ppetty Date 2018-08-28 Time 11:12 Sent To  
Notes
2018-08-28 11:12:21 
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED
 SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS
 COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY
 HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW
 COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS.
  
 1. PROVIDE RISER DIAGRAM, SHOWING ALL DETAILS OF
 SERVICE EQUIPMENT, UNDERGROUND OR OVERHEAD SERVICE,
 WIRE AND BREAKER SIZES FOR SERVICE AND FEED TO ANY
 SUB-PANEL(S). SHOW GEC SIZE AND SYSTEM, SHOW
 INTERSYSTEM BONDING TERMINATION POINT. NEC 215.5, 230,
 250.50, 250.94, 408.30; FBC RE E3706.1, E3608.1,
 E3609.3; FBC 107.2.1 (NOT PROVIDED ON SHEET A-2 AS
 MENTIONED IN RESPONSE.)
 2. PROVIDE PANEL SCHEDULE INDICATING ANY NEW OR ALTERED
 CIRCUITS, THE WIRE AND BREAKER SIZE FOR THESE CIRCUITS,
 AND AFCI OR GFCI PROTECTION WHERE APPLICABLE TO COMPLY
 WITH CODE. NEC 210.8, 210.12, 215.5, 408.4; FBC RE
 E3706.2, E3902 (NOT PROVIDED ON SHEET A-2 AS MENTIONED
 IN RESPONSE.)
 3. CORRECTED.
 4. CORRECTED.
 5. CORRECTED.
 6. CORRECTED.
 7. PROVIDE LOAD CALCULATION FOR SERVICE, INCLUDE
 EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF SERVICE
 IS ADEQUATE. NEC 215.2, 220, 408.30; FBC RE E3602.2
 (NOT PROVIDED ON SHEET A-2 AS MENTIONED IN RESPONSE.)
 8. CORRECTED.
 9. CORRECTED.
 10. CORRECTED.
 11. PROVIDE FULL FLOOR PLAN SHOWING SMOKE ALARMS IN
 EACH LOCATION REQUIRED PER CODE. SHOW ON PLAN ALL
 EXISTING ALARMS. IF NONE ARE EXISTING OR NOT TO CODE,
 SHOW AS NEW INSTALLATIONS. SMOKE ALARMS MUST BE
 INSTALLED AT LEAST 3 FEET FROM BATHROOM DOOR, 3 FEET
 FROM CEILING FANS, AND 3 FEET FROM ANY MECHANICAL DUCT.
 PROVIDE CORRECTIONS. FBC RE R314.3(4), NFPA
 72:29.8.3.4; FBC R314.3, FBC 107.2.1 (NOT PROVIDED AS
 MENTIONED IN RESPONSE.)
 12. CORRECTED.
 13. CORRECTED.
 14. CORRECTED.
 15. FEE ADDED.
 PLEASE BE ADVISED THAT THIS COMMENT HAS NOT BEEN
 ADDRESSED FOR TWO REVIEWS. IF UPON THE THIRD REVIEW, IF
 IT IS NECESSARY TO REJECT THE SUBMITTED PLAN A THIRD
 TIME FOR THE SAME REASONS, AN ADDITIONAL PLAN REVIEW IS
 REQUIRED. FLORIDA STATUTES STATE: ?WITH RESPECT TO
 EVALUATION OF DESIGN PROFESSIONALS? DOCUMENTS, IF A
 LOCAL GOVERNMENT FINDS IT NECESSARY, IN ORDER TO
 ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING CODE AND
 ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS REQUIRED BY
 THE CODE THREE OR MORE TIMES FOR FAILURE TO CORRECT A
 CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY NOTED IN
 EACH REJECTION, INCLUDING, BUT NOT LIMITED TO, EGRESS,
 FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY,
 ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL,
 MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER
 REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING
 COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL
 GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH
 REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION,
 A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE
 PERMIT FEE ATTRIBUTED TO PLANS REVIEW. FS 553.80(2)(B)?
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 PHIL PETTY
 CHIEF ELECTRICAL INSPECTOR
 561-805-6742
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2018-07-20 Cont ID  
Sent By jpearson Date 2018-07-20 Time 10:14 Rev Time 0.00
Received By jpearson Date 2018-07-20 Time 09:55 Sent To P
Notes
2018-07-20 10:14:25 
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED
 SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS
 COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY
 HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW
 COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS.
  
 1. PROVIDE RISER DIAGRAM, SHOWING ALL DETAILS OF
 SERVICE EQUIPMENT, UNDERGROUND OR OVERHEAD SERVICE,
 WIRE AND BREAKER SIZES FOR SERVICE AND FEED TO ANY
 SUB-PANEL(S). SHOW GEC SIZE AND SYSTEM, SHOW
 INTERSYSTEM BONDING TERMINATION POINT. NEC 215.5, 230,
 250.50, 250.94, 408.30; FBC RE E3706.1, E3608.1,
 E3609.3; FBC 107.2.1 (NOT PROVIDED ON SHEET A-2 AS
 MENTIONED IN RESPONSE.)
 2. PROVIDE PANEL SCHEDULE INDICATING ANY NEW OR ALTERED
 CIRCUITS, THE WIRE AND BREAKER SIZE FOR THESE CIRCUITS,
 AND AFCI OR GFCI PROTECTION WHERE APPLICABLE TO COMPLY
 WITH CODE. NEC 210.8, 210.12, 215.5, 408.4; FBC RE
 E3706.2, E3902 (NOT PROVIDED ON SHEET A-2 AS MENTIONED
 IN RESPONSE.)
 3. CORRECTED.
 4. CORRECTED.
 5. CORRECTED.
 6. CORRECTED.
 7. PROVIDE LOAD CALCULATION FOR SERVICE, INCLUDE
 EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF SERVICE
 IS ADEQUATE. NEC 215.2, 220, 408.30; FBC RE E3602.2
 (NOT PROVIDED ON SHEET A-2 AS MENTIONED IN RESPONSE.)
 8. CORRECTED.
 9. CORRECTED.
 10. CORRECTED.
 11. PROVIDE FULL FLOOR PLAN SHOWING SMOKE ALARMS IN
 EACH LOCATION REQUIRED PER CODE. SHOW ON PLAN ALL
 EXISTING ALARMS. IF NONE ARE EXISTING OR NOT TO CODE,
 SHOW AS NEW INSTALLATIONS. SMOKE ALARMS MUST BE
 INSTALLED AT LEAST 3 FEET FROM BATHROOM DOOR, 3 FEET
 FROM CEILING FANS, AND 3 FEET FROM ANY MECHANICAL DUCT.
 PROVIDE CORRECTIONS. FBC RE R314.3(4), NFPA
 72:29.8.3.4; FBC R314.3, FBC 107.2.1 (NOT PROVIDED AS
 MENTIONED IN RESPONSE.)
 12. CORRECTED.
 13. CORRECTED.
 14. CORRECTED.
 15. FEE ADDED.
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 PHIL PETTY
 CHIEF ELECTRICAL INSPECTOR
 561-805-6742
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2018-05-17 Cont ID  
Sent By ppetty Date 2018-05-17 Time 12:57 Rev Time 0.00
Received By ppetty Date 2018-05-17 Time 12:57 Sent To  
Notes
2018-05-17 12:57:16 
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE RISER DIAGRAM, SHOWING ALL DETAILS OF
 SERVICE EQUIPMENT, UNDERGROUND OR OVERHEAD SERVICE,
 WIRE AND BREAKER SIZES FOR SERVICE AND FEED TO ANY
 SUB-PANEL(S). SHOW GEC SIZE AND SYSTEM, SHOW
 INTERSYSTEM BONDING TERMINATION POINT. NEC 215.5, 230,
 250.50, 250.94, 408.30; FBC RE E3706.1, E3608.1,
 E3609.3; FBC 107.2.1
 2. PROVIDE PANEL SCHEDULE INDICATING ANY NEW OR ALTERED
 CIRCUITS, THE WIRE AND BREAKER SIZE FOR THESE CIRCUITS,
 AND AFCI OR GFCI PROTECTION WHERE APPLICABLE TO COMPLY
 WITH CODE. NEC 210.8, 210.12, 215.5, 408.4; FBC RE
 E3706.2, E3902
 3. PROVIDE AFCI PROTECTION PER CODE: ?BRANCH CIRCUITS
 THAT SUPPLY 120-VOLT, SINGLE-PHASE, 15- AND 20-AMPERE
 OUTLETS INSTALLED IN KITCHENS, FAMILY ROOMS, DINING
 ROOMS, LIVING ROOMS, PARLORS, LIBRARIES, DENS,
 BEDROOMS, SUN-ROOMS, RECREATIONS ROOMS, CLOSETS,
 HALLWAYS, LAUNDRY AREAS AND SIMILAR ROOMS OR AREAS
 SHALL BE AFCI PROTECTED.? PROVIDE CORRECTION. NEC
 210.12; FBC RE E3902.16
 4. N/A
 5. LIGHTING IN BATHTUB OR SHOWER AREAS SHALL BE
 SUITABLE FOR DAMP LOCATIONS. PROVIDE CORRECTION. NEC
 410.10(D); FBC RE E4003.11
 6. PROVIDE COMPLIANCE: "A MINIMUM OF 75 PERCENT OF THE
 LAMPS IN PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 BE HIGH-EFFICACY LAMPS OR A MINIMUM OF 75 PERCENT OF
 THE PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 CONTAIN ONLY HIGH EFFICACY LAMPS". A NOTE WILL SUFFICE.
 FBC EC R404.1
 7. PROVIDE LOAD CALCULATION FOR SERVICE, INCLUDE
 EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF SERVICE
 IS ADEQUATE. NEC 215.2, 220, 408.30; FBC RE E3602.2
 8. N/A
 9. PROVIDE BLOCK NOTE THAT POOL WILL BE UNDER SEPARATE
 PERMIT. FBC 107.2.1, 105.1
 10. N/A
 11. PROVIDE FULL FLOOR PLAN SHOWING SMOKE ALARMS IN
 EACH LOCATION REQUIRED PER CODE. SHOW ON PLAN ALL
 EXISTING ALARMS. IF NONE ARE EXISTING OR NOT TO CODE,
 SHOW AS NEW INSTALLATIONS. SMOKE ALARMS MUST BE
 INSTALLED AT LEAST 3 FEET FROM BATHROOM DOOR, 3 FEET
 FROM CEILING FANS, AND 3 FEET FROM ANY MECHANICAL DUCT.
 PROVIDE CORRECTIONS. FBC RE R314.3(4), NFPA
 72:29.8.3.4; FBC R314.3, FBC 107.2.1
 12. PROVIDE TAMPER RESISTANT RECEPTACLES PER CODE. A
 NOTE WILL SUFFICE. NEC 406.12; FBC RE E4002.14
 13. A MINIMUM OF ONE 20 AMPERE BRANCH CIRCUIT SHALL BE
 PROVIDED TO SUPPLY BATHROOM RECEPTACLE OUTLET(S). SUCH
 CIRCUITS SHALL HAVE NO OTHER OUTLETS. PROVIDE PER CODE.
 NEC 210.11(C)(3) , FBC RE E3703.4
 14. PROVIDE GFCI PROTECTED OUTLET FOR SERVICING OF A/C
 EQUIPMENT PER CODE. NEC 210.63; FBC RE E3901.12
 15.PLEASE BE ADVISED THAT THESE COMMENTS HAVE NOT BEEN
 ADDRESSED FOR THREE REVIEWS. IF UPON THE NEXT REVIEW,
 IF IT IS NECESSARY TO REJECT THE SUBMITTED PLAN A
 FOURTH TIME FOR THE SAME REASONS, AN ADDITIONAL PLAN
 REVIEW IS REQUIRED. FLORIDA STATUTES STATE: ?WITH
 RESPECT TO EVALUATION OF DESIGN PROFESSIONALS?
 DOCUMENTS, IF A LOCAL GOVERNMENT FINDS IT NECESSARY, IN
 ORDER TO ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING
 CODE AND ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS
 REQUIRED BY THE CODE THREE OR MORE TIMES FOR FAILURE TO
 CORRECT A CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY
 NOTED IN EACH REJECTION, INCLUDING, BUT NOT LIMITED TO,
 EGRESS, FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY,
 ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL,
 MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER
 REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING
 COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL
 GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH
 REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION,
 A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE
 PERMIT FEE ATTRIBUTED TO PLANS REVIEW. FS 553.80(2)(B)?
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 PHIL PETTY
 CHIEF ELECTRICAL INSPECTOR
 561-805-6742
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2018-04-11 Cont ID  
Sent By ppetty Date 2018-04-11 Time 09:03 Rev Time 0.00
Received By ppetty Date 2018-04-11 Time 09:01 Sent To  
Notes
2018-04-11 09:03:49NO CHANGE TO PLAN
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE RISER DIAGRAM, SHOWING ALL DETAILS OF
 SERVICE EQUIPMENT, UNDERGROUND OR OVERHEAD SERVICE,
 WIRE AND BREAKER SIZES FOR SERVICE AND FEED TO ANY
 SUB-PANEL(S). SHOW GEC SIZE AND SYSTEM, SHOW
 INTERSYSTEM BONDING TERMINATION POINT. NEC 215.5, 230,
 250.50, 250.94, 408.30; FBC RE E3706.1, E3608.1,
 E3609.3; FBC 107.2.1
 2. PROVIDE PANEL SCHEDULE INDICATING ANY NEW OR ALTERED
 CIRCUITS, THE WIRE AND BREAKER SIZE FOR THESE CIRCUITS,
 AND AFCI OR GFCI PROTECTION WHERE APPLICABLE TO COMPLY
 WITH CODE. NEC 210.8, 210.12, 215.5, 408.4; FBC RE
 E3706.2, E3902
 3. PROVIDE AFCI PROTECTION PER CODE: ?BRANCH CIRCUITS
 THAT SUPPLY 120-VOLT, SINGLE-PHASE, 15- AND 20-AMPERE
 OUTLETS INSTALLED IN KITCHENS, FAMILY ROOMS, DINING
 ROOMS, LIVING ROOMS, PARLORS, LIBRARIES, DENS,
 BEDROOMS, SUN-ROOMS, RECREATIONS ROOMS, CLOSETS,
 HALLWAYS, LAUNDRY AREAS AND SIMILAR ROOMS OR AREAS
 SHALL BE AFCI PROTECTED.? PROVIDE CORRECTION. NEC
 210.12; FBC RE E3902.16
 4. RECEPTACLES IN STORAGE AREAS REQUIRE GFCI
 PROTECTION. PROVIDE CORRECTION. NEC 210.8; FBC RE
 E3902.2
 5. LIGHTING IN BATHTUB OR SHOWER AREAS SHALL BE
 SUITABLE FOR DAMP LOCATIONS. PROVIDE CORRECTION. NEC
 410.10(D); FBC RE E4003.11
 6. PROVIDE COMPLIANCE: "A MINIMUM OF 75 PERCENT OF THE
 LAMPS IN PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 BE HIGH-EFFICACY LAMPS OR A MINIMUM OF 75 PERCENT OF
 THE PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 CONTAIN ONLY HIGH EFFICACY LAMPS". A NOTE WILL SUFFICE.
 FBC EC R404.1
 7. PROVIDE LOAD CALCULATION FOR SERVICE, INCLUDE
 EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF SERVICE
 IS ADEQUATE. NEC 215.2, 220, 408.30; FBC RE E3602.2
 8. FOR DWELLING UNITS, ATTACHED GARAGES, AND DETACHED
 GARAGES WITH ELECTRIC POWER, AT LEAST ONE WALL
 SWITCH-CONTROLLED LIGHTING OUTLET SHALL BE INSTALLED ON
 THE EXTERIOR SIDE OF OUTDOOR ENTRANCES/EXITS WITH GRADE
 LEVEL ACCESS. PROVIDE CORRECTION. NEC 210.70(A)(2)(B),
 FBC RE E3903.3
 9. PROVIDE BLOCK NOTE THAT POOL WILL BE UNDER SEPARATE
 PERMIT. FBC 107.2.1, 105.1
 10. A BUILDING OR OTHER STRUCTURE THAT IS SERVED BY A
 BRANCH CIRCUIT OR FEEDER ON THE LOAD SIDE OF A SERVICE
 DISCONNECTING MEANS SHALL BE SUPPLIED BY ONLY ONE
 FEEDER OR BRANCH CIRCUIT. PROVIDE DETAILS. NEC 225.30
 11. PROVIDE FULL FLOOR PLAN SHOWING SMOKE ALARMS IN
 EACH LOCATION REQUIRED PER CODE. SHOW ON PLAN ALL
 EXISTING ALARMS. IF NONE ARE EXISTING OR NOT TO CODE,
 SHOW AS NEW INSTALLATIONS. SMOKE ALARMS MUST BE
 INSTALLED AT LEAST 3 FEET FROM BATHROOM DOOR, 3 FEET
 FROM CEILING FANS, AND 3 FEET FROM ANY MECHANICAL DUCT.
 PROVIDE CORRECTIONS. FBC RE R314.3(4), NFPA
 72:29.8.3.4; FBC R314.3, FBC 107.2.1
 12. PROVIDE TAMPER RESISTANT RECEPTACLES PER CODE. A
 NOTE WILL SUFFICE. NEC 406.12; FBC RE E4002.14
 13. A MINIMUM OF ONE 20 AMPERE BRANCH CIRCUIT SHALL BE
 PROVIDED TO SUPPLY BATHROOM RECEPTACLE OUTLET(S). SUCH
 CIRCUITS SHALL HAVE NO OTHER OUTLETS. PROVIDE PER CODE.
 NEC 210.11(C)(3) , FBC RE E3703.4
 14. PROVIDE GFCI PROTECTED OUTLET FOR SERVICING OF A/C
 EQUIPMENT PER CODE. NEC 210.63; FBC RE E3901.12
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 PHIL PETTY
 CHIEF ELECTRICAL INSPECTOR
 561-805-6742
 [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-03-14 Cont ID  
Sent By jpearson Date 2018-03-14 Time 10:16 Rev Time 0.00
Received By jpearson Date 2018-03-14 Time 09:15 Sent To  
Notes
2018-03-14 10:16:00CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE RISER DIAGRAM, SHOWING ALL DETAILS OF
 SERVICE EQUIPMENT, UNDERGROUND OR OVERHEAD SERVICE,
 WIRE AND BREAKER SIZES FOR SERVICE AND FEED TO ANY
 SUB-PANEL(S). SHOW GEC SIZE AND SYSTEM, SHOW
 INTERSYSTEM BONDING TERMINATION POINT. NEC 215.5, 230,
 250.50, 250.94, 408.30; FBC RE E3706.1, E3608.1,
 E3609.3; FBC 107.2.1
 2. PROVIDE PANEL SCHEDULE INDICATING ANY NEW OR ALTERED
 CIRCUITS, THE WIRE AND BREAKER SIZE FOR THESE CIRCUITS,
 AND AFCI OR GFCI PROTECTION WHERE APPLICABLE TO COMPLY
 WITH CODE. NEC 210.8, 210.12, 215.5, 408.4; FBC RE
 E3706.2, E3902
 3. PROVIDE AFCI PROTECTION PER CODE: ?BRANCH CIRCUITS
 THAT SUPPLY 120-VOLT, SINGLE-PHASE, 15- AND 20-AMPERE
 OUTLETS INSTALLED IN KITCHENS, FAMILY ROOMS, DINING
 ROOMS, LIVING ROOMS, PARLORS, LIBRARIES, DENS,
 BEDROOMS, SUN-ROOMS, RECREATIONS ROOMS, CLOSETS,
 HALLWAYS, LAUNDRY AREAS AND SIMILAR ROOMS OR AREAS
 SHALL BE AFCI PROTECTED.? PROVIDE CORRECTION. NEC
 210.12; FBC RE E3902.16
 4. RECEPTACLES IN STORAGE AREAS REQUIRE GFCI
 PROTECTION. PROVIDE CORRECTION. NEC 210.8; FBC RE
 E3902.2
 5. LIGHTING IN BATHTUB OR SHOWER AREAS SHALL BE
 SUITABLE FOR DAMP LOCATIONS. PROVIDE CORRECTION. NEC
 410.10(D); FBC RE E4003.11
 6. PROVIDE COMPLIANCE: "A MINIMUM OF 75 PERCENT OF THE
 LAMPS IN PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 BE HIGH-EFFICACY LAMPS OR A MINIMUM OF 75 PERCENT OF
 THE PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 CONTAIN ONLY HIGH EFFICACY LAMPS". A NOTE WILL SUFFICE.
 FBC EC R404.1
 7. PROVIDE LOAD CALCULATION FOR SERVICE, INCLUDE
 EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF SERVICE
 IS ADEQUATE. NEC 215.2, 220, 408.30; FBC RE E3602.2
 8. FOR DWELLING UNITS, ATTACHED GARAGES, AND DETACHED
 GARAGES WITH ELECTRIC POWER, AT LEAST ONE WALL
 SWITCH-CONTROLLED LIGHTING OUTLET SHALL BE INSTALLED ON
 THE EXTERIOR SIDE OF OUTDOOR ENTRANCES/EXITS WITH GRADE
 LEVEL ACCESS. PROVIDE CORRECTION. NEC 210.70(A)(2)(B),
 FBC RE E3903.3
 9. PROVIDE BLOCK NOTE THAT POOL WILL BE UNDER SEPARATE
 PERMIT. FBC 107.2.1, 105.1
 10. A BUILDING OR OTHER STRUCTURE THAT IS SERVED BY A
 BRANCH CIRCUIT OR FEEDER ON THE LOAD SIDE OF A SERVICE
 DISCONNECTING MEANS SHALL BE SUPPLIED BY ONLY ONE
 FEEDER OR BRANCH CIRCUIT. PROVIDE DETAILS. NEC 225.30
 11. PROVIDE FULL FLOOR PLAN SHOWING SMOKE ALARMS IN
 EACH LOCATION REQUIRED PER CODE. SHOW ON PLAN ALL
 EXISTING ALARMS. IF NONE ARE EXISTING OR NOT TO CODE,
 SHOW AS NEW INSTALLATIONS. SMOKE ALARMS MUST BE
 INSTALLED AT LEAST 3 FEET FROM BATHROOM DOOR, 3 FEET
 FROM CEILING FANS, AND 3 FEET FROM ANY MECHANICAL DUCT.
 PROVIDE CORRECTIONS. FBC RE R314.3(4), NFPA
 72:29.8.3.4; FBC R314.3, FBC 107.2.1
 12. PROVIDE TAMPER RESISTANT RECEPTACLES PER CODE. A
 NOTE WILL SUFFICE. NEC 406.12; FBC RE E4002.14
 13. A MINIMUM OF ONE 20 AMPERE BRANCH CIRCUIT SHALL BE
 PROVIDED TO SUPPLY BATHROOM RECEPTACLE OUTLET(S). SUCH
 CIRCUITS SHALL HAVE NO OTHER OUTLETS. PROVIDE PER CODE.
 NEC 210.11(C)(3) , FBC RE E3703.4
 14. PROVIDE GFCI PROTECTED OUTLET FOR SERVICING OF A/C
 EQUIPMENT PER CODE. NEC 210.63; FBC RE E3901.12
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  
  

Review Stop HIST HISTORICAL
Rev No 4 Status P Date 2018-05-30 Cont ID  
Sent By fmittner Date 2018-05-30 Time 11:23 Rev Time 0.00
Received By fmittner Date 2018-05-30 Time 11:23 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 3 Status F Date 2018-04-13 Cont ID  
Sent By destabro Date 2018-04-13 Time 10:51 Rev Time 0.00
Received By destabro Date 2018-04-13 Time 10:51 Sent To B
Notes
2018-04-13 10:54:394/13/2018 - APPLICANT NEEDS TO REVISE PLANS FOR
 CONSTRUCTION OF REAR ADDITION ONLY, WHICH WAS APPROVED
 AT STAFF LEVEL. THE REAR CABANA IS AWAITING HPB REVIEW
 IN MAY. DLE

Review Stop HIST HISTORICAL
Rev No 2 Status F Date 2018-04-06 Cont ID  
Sent By destabro Date 2018-04-06 Time 13:36 Rev Time 0.00
Received By destabro Date 2018-04-06 Time 13:36 Sent To Z
Notes
2018-04-06 13:37:184/6/2018 - AWAITING LEVEL 2 HISTORIC REVIEW - COA
 REQUIRED. APPLICANT INFORMED. DLE

Review Stop HIST HISTORICAL
Rev No 1 Status F Date 2018-02-28 Cont ID  
Sent By destabro Date 2018-02-28 Time 13:37 Rev Time 0.00
Received By destabro Date 2018-02-28 Time 08:16 Sent To Z
Notes
2018-02-28 13:52:392/28/2018 - THIS IS A CONTRIBUTING PROPERTY TO THE
 FLAMINGO PARK HISTORIC DISTRICT. ANY PROPOSED ADDITIONS
 OR EXTERIOR ALTERATIONS SHOULD FIRST BE SUBMITTED TO
 THE HISTORIC PRESERVATION OFFICE FOR REVIEW. ALSO,
 VINYL PRODUCTS ARE NOT PERMITTED FOR USE WITHOUT
 HISTORIC PRESERVATION BOARD APPROVAL. THE COA
 APPLICATION MAY BE FOUND HERE: HTTP://WPB.ORG/DEPARTMEN
 TS/DEVELOPMENT-SERVICES/HISTORIC-PRESERVATION/APPLICATI
 ONS?PAGE=2 QUESTIONS MAY BE DIRECTED TO DESIREE
 ESTABROOK, HISTORIC PRESERVATION PLANNER, AT
 561.822.1428 OR [email protected]
2018-02-28 08:16:29DESIREE

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2018-10-01 Cont ID  
Sent By hmoser Date 2018-10-01 Time 15:34 Rev Time 0.00
Received By hmoser Date 2018-09-14 Time 12:50 Sent To  
Notes
2018-09-17 12:50:40R36

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2018-09-12 Cont ID  
Sent By dbattles Date 2018-09-12 Time 13:44 Rev Time 0.00
Received By dbattles Date 2018-07-30 Time 14:23 Sent To  
Notes
2018-08-06 10:10:47R07
2018-07-31 14:24:58LIBRARY

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2018-07-23 Cont ID  
Sent By cpuell Date 2018-07-23 Time 11:00 Rev Time 0.00
Received By cpuell Date 2018-07-10 Time 10:51 Sent To  
Notes
2018-07-12 10:52:04R36

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2018-06-14 Cont ID  
Sent By rmcdouga Date 2018-06-14 Time 15:16 Rev Time 0.00
Received By rmcdouga Date 2018-05-11 Time 16:30 Sent To  
Notes
2018-05-15 16:30:08R26

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-04-20 Cont ID  
Sent By shill Date 2018-04-20 Time 17:50 Rev Time 0.00
Received By shill Date 2018-03-22 Time 13:12 Sent To  
Notes
2018-03-23 13:12:52R26

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-03-20 Cont ID  
Sent By rmcdouga Date 2018-03-20 Time 19:09 Rev Time 0.00
Received By rmcdouga Date 2018-02-13 Time 09:55 Sent To  
Notes
2018-02-14 09:55:37R33

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2018-05-04 Cont ID  
Sent By rmcdouga Date 2018-05-04 Time 17:40 Rev Time 0.00
Received By rmcdouga Date 2018-05-04 Time 17:40 Sent To  
Notes
2018-05-04 17:42:17MU2018 - 14955, NO FEES WERE DUE.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2018-03-19 Cont ID  
Sent By rmcdouga Date 2018-03-19 Time 18:57 Rev Time 0.00
Received By rmcdouga Date 2018-03-19 Time 18:45 Sent To  
Notes
2018-03-19 18:57:46BEFORE A PERMIT TO CONSTRUCT CAN BE ISSUED, IMPACT FEES
 MUST BE PAID TO PALM BEACH COUNTY. UPON APPROVAL, ONE
 SET OF PLANS SHALL BE SIGNED OUT AND SUBMITTED TO PALM
 BEACH COUNTY FOR AN IMPACT FEE REVIEW. THE PLANS WITH
 THE IMPACT FEE STAMP AND A COPY OF THE PAID RECEIPT
 MUST BE RETURNED TO THE CITY BUILDING DEPARTMENT BEFORE
 THE BUILDING PERMIT CAN BE ISSUED. FOR INFORMATION CALL
 PALM BEACH COUNTY IMPACT FEES AT (561) 233-5025.
 (ADDITION AND CABANA)
  
  

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2018-10-01 Cont ID  
Sent By hmoser Date 2018-10-01 Time 15:33 Rev Time 0.00
Received By hmoser Date 2018-10-01 Time 15:33 Sent To P
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2018-08-23 Cont ID  
Sent By cmontell Date 2018-08-23 Time 14:15 Rev Time 0.00
Received By cmontell Date 2018-08-23 Time 14:07 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2018-03-27 Cont ID  
Sent By cmontell Date 2018-03-27 Time 15:03 Rev Time 0.00
Received By cmontell Date 2018-03-27 Time 14:34 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2018-03-16 Cont ID  
Sent By cmontell Date 2018-03-16 Time 14:40 Rev Time 0.00
Received By cmontell Date 2018-03-16 Time 14:32 Sent To  
Notes
2018-03-16 14:45:46MECHANICAL PLAN REVIEW FAIL
  
 1 - 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE DIMENSIONED AND DRAWN
 UPON SUITABLE MATERIAL. ELECTRONIC MEDIA DOCUMENTS ARE
 PERMITTED TO BE SUBMITTED WHERE APPROVED BY THE
 BUILDING OFFICIAL. CONSTRUCTION DOCUMENTS SHALL BE OF
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT
 WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL.
  
  

Review Stop P PLUMBING
Rev No 6 Status P Date 2018-10-02 Cont ID  
Sent By tklarge Date 2018-10-02 Time 14:37 Rev Time 0.00
Received By tklarge Date 2018-10-02 Time 14:25 Sent To Z
Notes
***NONE***

Review Stop P PLUMBING
Rev No 5 Status F Date 2018-08-21 Cont ID  
Sent By tklarge Date 2018-08-21 Time 05:07 Rev Time 0.00
Received By tklarge Date 2018-08-21 Time 03:03 Sent To  
Notes
2018-08-21 04:18:361) SHT. A -1 - PLUMBING RISERS - SUBMIT TWO COPIES OF A
 CODE COMPLIANT SANITARY RISER DIAGRAM. 2ND REQUEST.
 NOTHING HAS BEEN DONE TO THE SANITARY RISERS TO CORRECT
 THE DEFICIENCIES.
 PLUMBING RISER - MASTER BATHROOM:
 A)THE DOUBLE LAVATORIES SHALL BE STACKED AND
 VENTED.2017 FBCR-SEC.P3101.2 P3101.2.1.
 B) THE MASTER BATHROOM SANITARY RISER SHOWS AN EXISTING
 SANITARY LINE FOR "BASEMENT PLUMBING" BUT THERE IS NO
 REFERENCE TO A BASEMENT NOR IS A BASEMENT SHOWN IN
 THESE PLANS . CLARIFY.
 2) SIZE ALL SECTIONS OF THE SANITARY DRAINAGE LINES AND
 VENT LINES ON BOTH SANITARY RISER DIAGRAMS.2ND REQUEST.
 3) THE PLANS SHOW A MASTER BATHROOM AND AN EXISTING
 BATHROOM BUT THE SANITARY RISER DIAGRAMS ARE FOR A
 MASTER BATH AND ALSO A NEW STORAGE BATH. CLARIFY.THE
 STORAGE ROOM IS SHOWN ON SHEET A-2 BUT HAS BEEN OMITTED
 FROM OTHER SHEETS. CLARIFY.
 4) SHT. A-2 - ADDITION ROOF PLAN - SUBMIT ADDITIONAL
 INFORMATION AS TO HOW THE SIZE OF THE SCUPPERS WERE
 CALCULATED. THERE IS NO TABLE IN THE PLUMBING CODE FOR
 SIZING SCUPPERS. THE ROOF PLAN REFERS TO TABLE 1106.3
 OF THE FLORIDA PLUMBING CODE FOR THE SIZING OF THE
 SCUPPERS. THIS TABLE IS FOR SIZING VERTICAL LEADERS,
 NOT SCUPPERS. SCUPPERS SHALL BE SIZED IN ACCORDANCE
 WITH 2017 FBC-PLUMBING SEC.1108.3, 1101.7. NOTE: THERE
 IS NO TABLE THAT SPECIFIES THE SQUARE FOOTAGE OF THE
 ROOF BEING DRAINED. ALL THE TABLES ARE BASED ON THE
 FLOW RATE.2017 FBC SEC.1101.7, 1108.1.
 5) THE SIZE OF THE MASTER BATH SHOWER SHALL COMPLY WITH
 2017 FBCR SEC.P2708.1.
 6) PLUMBING FIXTURES SHALL BE SPACED IN ACCORDANCE WITH
 2017 FBCR SEC.P2705.1.
  
 NOTE: I SUGGEST CONTACTING THIS PLAN REVIEWER TO
 DISCUSS THE COMMENTS SO COMPLIANCE CAN BE ACHIEVED AND
 THE PLUMBING CAN BE APPROVED.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  

Review Stop P PLUMBING
Rev No 4 Status F Date 2018-07-23 Cont ID  
Sent By tklarge Date 2018-07-23 Time 06:24 Rev Time 0.00
Received By tklarge Date 2018-07-20 Time 13:51 Sent To  
Notes
2018-07-20 15:25:151) SHT. A -1 - PLUMBING RISERS - SUBMIT TWO COPIES OF A
 CODE COMPLIANT SANITARY RISER DIAGRAM. THERE ARE TOO
 MANY CODE VIOLATIONS TO LIST. WPB AMEND.TO FBC SEC.
 107.2.1.
 2) SIZE ALL SECTIONS OF THE DRAINAGE LINES AND VENT
 LINES ON THE SANITARY RISER DIAGRAMS WHEN TEY ARE
 REVISED.
 3) THE PLANS SHOW A MASTER BATHROOM AND AN EXISTING
 BATHROOM BUT THE SANITARY RISER DIAGRAMS ARE FOR A
 MASTER BATH AND ALSO A NEW STORAGE BATH. CLARIFY.
 4) SHT. A-2 - ADDITION ROOF PLAN - SUBMIT A DETAIL OF
 THE ROOF SCUPPER. WPB AMEND. TO FBC SEC. 107.2.1.
 5) SHT. A-4 IS MISSING FROM ONE SET OF PLANS.
 6) THE ROOF PLAN REFERS TO TABLE 1106.3 OF THE FLORIDA
 PLUMBING CODE. THIS TABLE IS FOR VERTICAL LEADER
 SIZING, NOT SCUPPERS.CLARIFY.
 7) SHOW REQUIREMENTS FOR SECONDARY (EMERGENCY) ROOF
 DRAINAGE PER 2017 FBC-PLUMBING SEC. 1108.1.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  

Review Stop P PLUMBING
Rev No 3 Status F Date 2018-06-12 Cont ID  
Sent By gjohnson Date 2018-06-12 Time 16:54 Rev Time 0.00
Received By gjohnson Date 2018-06-12 Time 15:12 Sent To  
Notes
2018-06-12 17:02:401ST REVIEW: FBC 2017 6TH EDITION
  
 PLUMBING COMMENTS:
  
 1. WE RECEIVED A LETTER FROM MERCURIO CONSTRUCTION
 STATING THAT THE CABANA BATHROOM AND STORAGE WAS BEING
 REMOVED FROM THE SCOPE OF WORK FOR THIS PERMIT BUT THE
 PLANS STILL HAVE A FLOOR PLAN, PLUMBING RISER,
 ELECTRICAL PLAN AND ELEVATION SHOWING THE CABANA THEY
 WILL NEED TO BE REMOVED FROM THE PLANS I CANNOT APPROVE
 A SET OF PLANS THAT HAS WORK THAT IS NOT UNDER THE
 SCOPE OF THE PERMIT BEING ISSUED. PER WPB AMEND TO FBC
 107.2.1
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2018-03-26 Cont ID  
Sent By lcrespo Date 2018-03-26 Time 16:15 Rev Time 0.00
Received By lcrespo Date 2018-03-26 Time 16:15 Sent To  
Notes
2018-03-26 16:17:4603/26/18 APPROVED BY PLUMBING AND PUT BACK IN R26, LAC

Review Stop P PLUMBING
Rev No 1 Status F Date 2018-03-16 Cont ID  
Sent By gjohnson Date 2018-03-16 Time 16:40 Rev Time 0.00
Received By gjohnson Date 2018-03-16 Time 15:37 Sent To  
Notes
2018-03-16 16:46:141ST REVIEW: FBC 2017 6TH EDITION
  
 PLUMBING COMMENTS:
  
 1. PROVIDE BATHROOM DIMENSIONS TO SHOW COMPLIANCE WITH
 FBC RES
  
 P2708.1 GENERAL.SHOWER COMPARTMENTS SHALL HAVE NOT LESS
 THAN 900 SQUARE INCHES (0.6 M2) OF INTERIOR
 CROSS-SECTIONAL AREA. SHOWER COMPARTMENTS SHALL BE NOT
 LESS THAN 30 INCHES (762 MM) IN MINIMUM DIMENSION
 MEASURED FROM THE FINISHED INTERIOR DIMENSION OF THE
 SHOWER COMPARTMENT, EXCLUSIVE OF FIXTURE VALVES, SHOWER
 HEADS, SOAP DISHES, AND SAFETY GRAB BARS OR RAILS. THE
 MINIMUM REQUIRED AREA AND DIMENSION SHALL BE MEASURED
 FROM THE FINISHED INTERIOR DIMENSION AT A HEIGHT EQUAL
 TO THE TOP OF THE THRESHOLD AND AT A POINT TANGENT TO
 ITS CENTERLINE AND SHALL BE CONTINUED TO A HEIGHT OF
 NOT LESS THAN 70 INCHES (1778 MM) ABOVE THE SHOWER
 DRAIN OUTLET. HINGED SHOWER DOORS SHALL OPEN OUTWARD.
 THE WALL AREA ABOVE BUILT-IN TUBS HAVING INSTALLED
 SHOWER HEADS AND IN SHOWER COMPARTMENTS SHALL BE
 CONSTRUCTED IN ACCORDANCE WITH SECTION R702.4. SUCH
 WALLS SHALL FORM A WATER-TIGHT JOINT WITH EACH OTHER
 AND WITH EITHER THE TUB, RECEPTOR OR SHOWER FLOOR.
  
  
 P2705.1 (5) .WATER CLOSETS, LAVATORIES AND BIDETS. A
 WATER CLOSET, LAVATORY OR BIDET SHALL NOT BE SET CLOSER
 THAN 15 INCHES (381 MM) FROM ITS CENTER TO ANY SIDE
 WALL, PARTITION OR VANITY OR CLOSER THAN 30 INCHES (762
 MM) CENTER-TO-CENTER BETWEEN ADJACENT FIXTURES. THERE
 SHALL BE A CLEARANCE OF NOT LESS THAN 21 INCHES (533
 MM) IN FRONT OF A WATER CLOSET, LAVATORY OR BIDET TO
 ANY WALL, FIXTURE OR DOOR.
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop R ROOF PLAN REVIEW
Rev No 3 Status P Date 2018-07-23 Cont ID  
Sent By rmcdouga Date 2018-07-23 Time 07:13 Rev Time 0.00
Received By rmcdouga Date 2018-07-23 Time 07:13 Sent To  
Notes
2018-07-23 07:14:58FL#2533-R19 SYSTEM NO. W-97

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status F Date 2018-06-14 Cont ID  
Sent By rmcdouga Date 2018-06-14 Time 15:16 Rev Time 0.00
Received By rmcdouga Date 2018-06-14 Time 15:16 Sent To  
Notes
2018-06-14 15:11:38PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1. A ROOF SUB PERMIT WAS SUBMITTED. INDICATE WHICH
 ASSEMBLY IS PROPOSED AND PROVIDE ENGINEERING FOR ZONE 2
 AND 3 IF APPLICABLE. IF THIS INFORMATION IS NOT
 PROVIDED, THE ROOF SUB PERMIT APPLICATION WILL BE
 VOIDED AND A ROOF SUB PERMIT WITH ALL REQUIRED
 INFORMATION (PRODUCT APPROVAL, ASSEMBLY PROPOSED, AND
 ENGINEERING IF APPLICABLE) WILL BE REQUIRED PRIOR TO
 INSTALLATION.
  
 2) TWO SETS OF A ROOFING PRODUCT APPROVAL WERE
 SUBMITTED. THE PROPOSED ASSEMBLY WAS NOT INDICATED. FBC
 107.2.1
  
 3) FBC 107.3.4 - PROVIDE TWO SETS OF PRODUCT APPROVALS
 FOR THOSE PRODUCTS WHICH ARE REGULATED BY FAC
 61G20-3.001 PER FLORIDA STATUTE 553.842 (5) THAT HAVE
 BEEN REVIEWED AND APPROVED IN WRITING BY THE DESIGNER
 OF RECORD. PROVIDE TWO COMPLETE PRODUCT APPROVALS WITH
 FL OR NOA NUMBERS INCLUDING INSTALLATION INSTRUCTIONS
 AND MAXIMUM DESIGN PRESSURES FOR THE ROOFING MATERIALS.
  
  
  
  

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2018-04-20 Cont ID  
Sent By shill Date 2018-04-20 Time 17:48 Rev Time 0.00
Received By shill Date 2018-04-20 Time 17:48 Sent To  
Notes
2018-04-20 17:50:40****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. A ROOF SUB PERMIT WAS SUBMITTED. INDICATE WHICH
 ASSEMBLY IS PROPOSED AND PROVIDE ENGINEERING FOR ZONE 2
 AND 3 IF APPLICABLE. IF THIS INFORMATION IS NOT
 PROVIDED, THE ROOF SUB PERMIT APPLICATION WILL BE
 VOIDED AND A ROOF SUB PERMIT WITH ALL REQUIRED
 INFORMATION (PRODUCT APPROVAL, ASSEMBLY PROPOSED, AND
 ENGINEERING IF APPLICABLE) WILL BE REQUIRED PRIOR TO
 INSTALLATION.
  
  

Review Stop Z ZONING
Rev No 4 Status P Date 2018-10-05 Cont ID  
Sent By fmittner Date 2018-10-05 Time 16:46 Rev Time 0.00
Received By fmittner Date 2018-10-05 Time 16:46 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status P Date 2018-05-30 Cont ID  
Sent By fmittner Date 2018-05-30 Time 11:24 Rev Time 0.00
Received By fmittner Date 2018-05-30 Time 11:24 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status F Date 2018-04-06 Cont ID  
Sent By destabro Date 2018-04-06 Time 13:37 Rev Time 0.00
Received By destabro Date 2018-04-06 Time 13:37 Sent To B
Notes
2018-04-06 13:37:334/6/2018 - AWAITING LEVEL 2 HISTORIC REVIEW - COA
 REQUIRED. APPLICANT INFORMED. DLE

Review Stop Z ZONING
Rev No 1 Status F Date 2018-02-28 Cont ID  
Sent By destabro Date 2018-02-28 Time 13:35 Rev Time 0.00
Received By destabro Date 2018-02-28 Time 13:35 Sent To B
Notes
2018-02-28 13:36:592/28/2018 - PLEASE ADDRESS HISTORIC COMMENTS AND SUBMIT
 COA FOR REVIEW. PROPOSED ADDITION AND OPEN PORCH SHOULD
 FALL WITHIN THE CALCULATED LOT COVERAGE MAXIMUMS FOR
 THIS LOT AND PROPERTY. QUESTIONS MAY BE DIRECTED TO
 DESIREE ESTABROOK, HISTORIC PRESERVATION PLANNER, AT
 561.822.1428.